7.2.2 - Piping limitations
Depending on the unit size and options, the space between
water box connections and the nearest component can vary.
This results in piping limitations. In the case of straight pipes,
the space remaining available for pipe insulation are listed
in the table below.
Clearance
Straight pipes clearance with nominal diameter
XAV
500
600
700
800
950
1050
1150
Standard unit
Inlet (mm)
118
105
105
25
49
23
23
Outlet (mm)
118
105
105
25
49
23
23
Unit with option 100C
Inlet (mm)
118
105
105
25
49
23
23
Outlet (mm)
Elbow mandatory
Elbow mandatory
Elbow mandatory
Elbow mandatory
Elbow mandatory
Elbow mandatory
Elbow mandatory
Unit with option 107
Inlet (mm)
Elbow mandatory
Elbow mandatory
Elbow mandatory
Elbow mandatory
Elbow mandatory
Outlet (mm)
Elbow mandatory
Elbow mandatory
Elbow mandatory
Elbow mandatory
Elbow mandatory
For installation that requires thicker insulation, it is advised to use a pipe reduction or an elbow to avoid the closest component.
When straight pipe is not possible, use an elbow. Check elbow connection limitation in the table below.
Elbow connection
XAV
500
600
700
800
950
1050
1150
Standard unit
Inlet (mm)
Check dimension
Check dimension
Check dimension
OK
OK
OK
OK
Outlet (mm)
Check dimension
Check dimension
Check dimension
OK
OK
OK
OK
Unit with option 100C
Inlet (mm)
Check dimension
Check dimension
Check dimension
OK
OK
OK
OK
Outlet (mm)
OK
OK
OK
OK
OK
OK
OK
Unit with option 107
Inlet (mm)
Check dimension
Check dimension
Check dimension
Check dimension
Check dimension
Outlet (mm)
Check dimension
Check dimension
Check dimension
Check dimension
Check dimension
Check dimension : it is possible to install an elbow, but space available is limited and choice of the elbow size must be done in accordance with the dimensional drawings.