4.4 - Electrical data, optional hydronic module
The pumps that are factory-installed in these units comply with the European Ecodesign directive ErP. The additional
electrical data required* is as follows:
For low pressure pump motors (options 116F & 116G)
N°** Description***
Units
30XAV
500
600
1
Nominal efficiency at full load and nominal voltage
%
89,4
89,4
1
Nominal efficiency at 75% rated load and nominal voltage
%
88,9
88,9
1
Nominal efficiency at 50% rated load and nominal voltage
%
86,7
86,7
2
Efficiency level
-
IE3
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model
at the time of incorporation. Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial registration number and place of
manufacturerw
-
Same as above
5
Product's model number
-
Same as above
6
Number of motor poles
-
2
2
7-1 Rated shaft power output at full load and nominal voltage (400Vw)
kW
5,5
5,5
7-2 Maximum power input † (400 V)
kW
6,15
6,15
8
Rated input frequency
Hz
50
50
9-1
Rated voltage
V
3 x 400
3 x 400
9-2 Maximum current drawn †† (400 V)
A
9,7
9,7
10
Rated speed
r/s - rpm
49 -2930 49 -2930
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specifically designed
I. Altitudes above sea level
m
< 1000****
II. Ambient air temperature
°C
< 40* (up to 50°C with reduced water flow)
III. Maximum air temperature
°C
Please refer to the operating conditions given in this manual or in
the specific conditions in the Carrier selection programs.
IV. Potentially explosive atmosphere
-
Non ATEX environment
For of high pressure pump motors (options 116B & 116C)
N°* Description***
Units
30XA
500
600
1
Nominal efficiency at full load and nominal voltage
%
91,3
91,3
1
Nominal efficiency at 75% rated load and nominal voltage
%
91,4
91,4
1
Nominal efficiency at 50% rated load and nominal voltage
%
90,3
90,3
2
Efficiency level
-
IE3
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model
at the time of incorporation. Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial registration number and place of
manufacturer
-
Same as above
5
Product's model number
-
Same as above
6
Number of motor poles
-
2
2
7-1 Rated shaft power output at full load and nominal voltage (400V)
kW
11
11
7-2 Maximum power input † (400 V)
kW
12
12
8
Rated input frequency
Hz
50
50
9-1
Rated voltage
V
3 x 400
3 x 400
9-2 Maximum current drawn †† (400 V)
A
18.7
18.7
10
Rated speed
r/s - rpm
49 - 2945 49 - 2945
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specifically designed
I. Altitudes above sea level
m
< 1000****
II. Ambient air temperature
°C
< 40* (up to 50°C with reduced water flow)
III. Maximum air temperature
°C
Please refer to the operating conditions given in this manual or in
the specific conditions in the Carrier selection programs.
IV. Potentially explosive atmosphere
-
Non ATEX environment
*
Required by regulation 640/2009 with regard to the application of directive 2009/125/EC on the eco-design requirements for electrical motors
**
Item number imposed by regulation 640/2009, annex I2b
***
Description given by regulation 640/2009, annex I2b
****
Above 1000m, a degradation of 3% for each 500m should be taken into consideration
†
To obtain the maximum power input for a unit with hydronic module, add the maximum unit power input from the elctricial data table to the pump power input
††
To obtain the maximum unit operating current drawfor a unit with hydronic module, add the maximum unit current draw from electrical data table to the pump current draw