3.7 - 30XAV 1150
3.8 - Multiple chiller installation
It is recommended to install multiple chillers in a single row,
arranged as shown in the example below, to avoid recycling
of warm air from one unit to another.
1.5 m
mini
1.5 m
mini
If the situation at the site does not permit this arrangement,
contact your Carrier distributor to evaluate the various
possible arrangements. In certain situations an accessory
(supplied loose at the time of purchase) can be added.
3.9 - Distance to the wall
To ensure correct operation for most cases:
If h < H (2.3 m), minimum S = 3 m
If h > H or S < 3 m, contact your Carrier distributor to
evaluate the various possible arrangements. In certain
situations an accessory (supplied loose at the time of
purchase) can be added.
H
S
h
Wall
Anti-vibration
mounts
Legend:
All dimensions are given in mm.
Required clearances for maintenance (see note)
Recommended space for evaporator tube removal
Water inlet for standard unit
For options 5, 6, 100A, 100C, 107 refer to the certified drawing.
Water outlet for standard unit
For options 5, 6, 100A, 100C, 107 refer to the certified drawing.
Air outlet – do not obstruct
Power supply and control connection
C
Control circuit connection for option 158
NOTES:
•
Drawings are not contractually binding.
•
Before designing an installation, consult the certified
dimensional drawings, available on request.
•
For the positioning of the fixing points, weight
distribution and centre of gravity coordinates please
refer to the dimensional drawings.
•
If any unit(s) are close to walls, please refer to chapters
3.8 - 3.9 - “Distance to the wall” of this document to
determine the space required.