Fig. 55 — Relief Valve Arrangements
NOTE: All valves relieve at 185 psig (1275 kPa).
Table 21 — Relief Valve Locations
LOCATION
FRAME
SIZE
RELIEF VALVE OUTLET SIZE
QUANTITY WITHOUT
ISOLATION VALVES
QUANTITY WITH
ISOLATION VALVES
Discharge Pipe Assembly
3-5
1-1/4-in. NPT FEMALE CONNECTOR
1
1
A,B
1-1/4-in. NPT FEMALE CONNECTOR
N/A
1
Cooler
3-5, A,B
1-1/4-in. NPT FEMALE CONNECTOR
2
1
Condenser
3-5, A,B
1-1/4-in. NPT FEMALE CONNECTOR
2
2
Optional Storage Tank
N/A
1-1/4-in. NPT FEMALE CONNECTOR
2
2
WITH OPTIONAL ISOLATION
WITHOUT OPTIONAL ISOLATION
UNITS WITH R COMPRESSOR
a23-1657
UNITS WITH Q COMPRESSOR
WITHOUT OPTIONAL ISOLATION
WITH OPTIONAL ISOLATION
WITH OPTIONAL ISOLATION
WITHOUT OPTIONAL ISOLATION
UNITS WITH P COMPRESSOR