LEGEND TO TABLES 10A-10J
CCN
— Carrier Comfort Network®
CCM
— Chiller Control Module
DPI
— Drive Peripheral Interface
ICVC
— International Chiller Visual Control
PIC III
— Product Integrated Controls III
TXV
— Thermostatic Expansion Valve
VFD
— Variable Frequency Drive
VFG
— Variable Frequency (Drive) Gateway
Table 10 - Alarm and alert messages
A. MANUAL STOP
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
MANUALLY STOPPED - PRESS
CCN OR LOCAL TO START
PIC III in OFF mode, press CCN or LOCAL softkey to start unit.
TERMINATE PUMPDOWN MODE
TO SELECT CCN OR LOCAL
Enter the CONTROL TEST table and select TERMINATE LOCKOUT to unlock
compressor.
SHUTDOWN IN PROGRESS
COMPRESSOR UNLOADING
Chiller unloading before shutdown due to soft/stop feature.
SHUTDOWN IN PROGRESS
COMPRESSOR DEENERGISED
Chiller compressor is being commanded to stop. Water pumps are deenergised within
one minute.
ICE BUILD
OPERATION COMPLETE
Chiller shutdown from Ice Build operation.
SHUTDOWN IN PROGRESS
RECYCLE RESTART PENDING
Chilled water temperature below recycle setpoint. Cooling load is less than chiller
minimum capacity.
B. READY TO START
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
READY TO START IN XX MIN
UNOCCUPIED MODE
Time schedule for PIC III is unoccupied. Chillers will start only when occupied. Check
OCCPCnnS and Holidays screens.
READY TO START IN XX MIN
REMOTE CONTACTS OPEN
Remote contacts are open. Close contacts to start.
READY TO START IN XX MIN
STOP COMMAND IN EFFECT
Chiller START/STOP on MAINSTAT manually forced to stop. Release SUPERVISOR
force to start.
READY TO START IN XX MIN
OCCUPIED MODE
Chiller timer counting down. Unit ready to start.
READY TO START IN XX MIN
REMOTE CONTACTS CLOSED
Chiller timer countdown complete. Unit will proceed to start. Remote contact enabled
and closed.
READY TO START IN XX MIN
START COMMAND IN EFFECT
Chiller START/STOP on MAINSTAT manually forced to start.
Release SUPERVISOR force to start under normal control.
READY TO START IN XX MIN
RECYCLE RESTART PENDING
Chiller in recycle mode.
READY TO START
UNOCCUPIED MODE
Time schedule for PIC III is unoccupied in OCCPC01S screen. Chiller will start when
state changes to occupied. Make sure the time and date are correct in the TIME AND
DATE screen.
READY TO START
REMOTE CONTACTS OPEN
Remote contacts have stopped the chiller. Close contacts to start.
READY TO START
STOP COMMAND IN EFFECT
Chiller START/STOP on MAINSTAT manually forced to stop. Release SUPERVISOR
force to start.
READY TO START
OCCUPIED MODE
Chiller timer countdown complete. Unit will proceed to start.
READY TO START
REMOTE CONTACTS CLOSED
Chiller timer countdown complete. Unit ready for start.
READY TO START
START COMMAND IN EFFECT
Chiller START/STOP on MAINSTAT has been manually forced to start.
Chiller will start regardless of time schedule or remote contact status.
STARTUP INHIBITED
LOADSHED IN EFFECT
CCN loadshed module commanding chiller to stop.
C. IN RECYCLE SHUTDOWN
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
RECYCLE RESTART PENDING
OCCUPIED MODE
Unit in recycle mode, chilled water temperature is not sufficiently above setpoint to start.
RECYCLE RESTART PENDING
REMOTE CONTACT CLOSED
Unit in recycle mode, chilled water temperature is not sufficiently above setpoint to start.
RECYCLE RESTART PENDING
START COMMAND IN EFFECT
Chiller START/STOP on MAINSTAT manually forced to start, chilled water temperature
is not sufficiently above setpoint to start.
RECYCLE RESTART PENDING
ICE BUILD MODE
Chiller in ICE BUILD mode. Chilled water temperature is satisfied for ICE BUILD
conditions.