Table 3 - ICVC display data (continued)
Example 11 - OVERRIDE display screen
To access this display from the ICVC default screen:
1. Press
MenU
.
. Press
SeRVICe
.
3. Scroll down to highlight
ContRoL ALGoRItHM StAtUS.
4. Press
SeLeCt
.
5. Scroll down to highlight
oVeRRIDe.
DESCRIPTION
STATUS
UNITS
POINT
Comp Motor Winding Temp
Comp Motor Temp Override
Condenser Pressure
Cond Press Override
Calc Evap Sat Temp
Evap Sat Override Temp
Comp Discharge Temp
Comp Discharge Alert
Rectifier Temperature
Rectifier Temp Override
Inverter Temperature
Inverter Temp Override
Discharge Superheat
Condenser Refrig Temp
-38 to 118
65.5 to 93.3
-46 to 2896
1034 to 1792
-38 to 118
-16.6 to 7.2
-38 to 118
51.6 to 93.3
17.7 to 148.8
51.6 to 93.3
17.7 to 148.8
-11.1 to 55
3.3 to 55
-38 to 118
°C
°C
kPa
kPa
°C
°C
°C
°C
°C
°C
°C
K
K
°C
MTRW
MT_OVER
CRP
CP_OVER
ERT
ERT_OVER
CMPD
CD_ALERT
RECT_TEMP
REC_OVER
INV_TEMP
INV_OVER
SUPRHEAT
CRT
Note:
All variables with CAPITAL LETTER point names are available for CCN read operation. Forcing shall not be supported on maintenance screens.
Example 12 - LL_MAINT display screen
To access this display from the ICVC default screen:
1. Press
MenU
.
. Press
SeRVICe
.
3. Scroll down to highlight
ContRoL ALGoRItHM StAtUS.
4. Press
SeLeCt
.
5. Scroll down to highlight
LL_MAInt.
DESCRIPTION
STATUS
UNITS
POINT
Lead Lag Control
- LEADLAG: Configuration
- Current Mode
- Load Balance Option
- LAG Start Time
- LAG Stop Time
- Prestart Fault Time
- Pulldown: Delta T/Min
Satisfied?
- LEAD CHILLER in Control
- LAG CHILLER: Mode
- Run Status
- Start/Stop
- Recovery Start Request
- STANDBY CHILLER: Mode
- Run Status
- Start/Stop
- Recovery Start Request
- Spare Temperature 1
- Spare Temperature 2
NOTE 1
NOTE 2
0/1
2 to 60
2 to 60
2 to 30
x.xx
0/1
0/1
NOTE 3
NOTE 4
NOTE 5
0/1
NOTE 3
NOTE 4
NOTE 5
0/1
-38 to 118
-38 to 118
DSABLE/ENABLE
Minutes
Minutes
Minutes
K
NO/YES
NO/YES
NO/YES
NO/YES
°C
°C
leadlag
llmode
loadbal
lagstart
lagstop
preflt
pull_dt
pull_sat
leadctrl
lagmode
lagstat
lag_s_s
lag_rec
stdmode
stdstat
Std_s_s
std_rec
SPARE_T1
SPARE_T2
Notes:
1. DISABLE, LEAD, LAG, STANDBY, INVALID
2. DISABLE, LEAD, LAG, STANDBY, RECOVERY, CONFIG
3. Reset, Off, Local, CCN, Blank
4. Timeout, Ready, Recycle, Prestart, Startup, Ramping, Running, Demand, Override, Shutdown, Tripout, Pumpdown, Lockout, Ctl Test
5. Stop, Start, Retain
6. All variables with CAPITAL LETTER point names are available for CCN read operation. Forcing shall not be supported on maintenance screens.