37
MONITORED PARAMETER
ALARM/ALERT LIMIT
COMMENTS
Temperature Sensors Out of Range 260-271,140,141 0.06 > Voltage Ratio > 0.98 or – 40 F > Temperature >
118°C for 3 seconds
Preset Alarm, Voltage Ratio = Input Voltage/ Voltage
Reference (5 V)
Pressure Transducers Out of
Range
260-271
0.06 > Voltage Ratio > 0.98 for 3 seconds
Preset Alarm, Voltage Ratio = Input Voltage/ Voltage
Reference (5 V)
High Compressor Discharge
Temperature
231
COMP DISCHARGE TEMP > 104°C
Preset Alarm, Configure COMP DISCHARGE ALERT in
SETUP1 screen
167
COMP DISCHARGE TEMP > COMP DISCHARGE
ALERT
Configure COMP DISCHARGE ALERT in SETUP1
screen
103
COMP DISCHARGE TEMP > COMP DISCHARGE
ALERT – 5.6°C
Prestart Alert, Configure COMP DISCHARGE ALERT in
SETUP1 screen
High Motor Temperature
233
COMP MOTOR WINDING TEMP > 104°C
Preset Alarm, Configure COMP MOTOR TEMP
OVERRIDE in SETUP1 screen
102
COMP MOTOR WINDING TEMP > COMP MOTOR
TEMP OVERRIDE – 5.6 K
Prestart Alert, Configure COMP MOTOR TEMP
OVERRIDE in SETUP1 screen
Compressor Thrust Bearing
Temperature
101
COMP THRUST BRG TEMP > COMP THRUST BRG
ALERT – 5.6°C
Preset Alert, Configure COMP THRUST BRG ALERT in
SETUP1 screen
234
COMP THRUST BRG TEMP > 85°C
Preset Alarm
Low Evaporator Temperature
(Freeze Protection)
243
Chiller in RECYCLE SHUTDOWN and EVAP TEMP<
EVAP REFRIG TRI 0.5°C
Preset Alarm, configure EVAP REFRIG TRIPPOINT in
SETUP1 screen
232
EVAP REFRIG TEMP < 0.5°C (water) and EVAP
APPROACH > EVAP APPROACH ALERT
Preset Alarm, Configure EVAP APPROACH ALERT in
SETUP1 screen
-17.8°C < EVAP REFRIG TEMP < 4.4°C (brine) and
EVAP APPROACH > EVAP APPROACH ALERT
Configure EVAP REFRIG TRIP POINT and CHILLED
MEDIUM in SETUP1 screen
104
EVAPORATOR REFRIG TEMP < 0.5°C + REFRIG
OVERRIDE DELTA T (water)
Prestart Alert, Configure REFRIG OVERRIDE DELTA T
in SETUP1 screen
EVAPORATOR REFRIG TEMP < EVAP REFRIG
TRIPPOINT (brine)
Prestart Alert, Configure EVAP REFRIG TRIPPOINT and
CHILLED MEDIUM in SETUP1 screen
Transducer Voltage Fault
239
5.5 V d.c. < Voltage Reference < 4.5 V d.c.
Preset Alarm
High Condenser Pressure
- Control
235
CONDENSER PRESSURE > 1137 kPa
Preset Alarm, Configure COND PRESS OVERRIDE in
SETUP1 screen
- Switch
207
High Pressure Switch Open (1137 ± 35 kPa) & VFD
START = YES
Preset Alarm, Switch closes at 758 kPa
- Prestart
106
CONDENSER PRESSURE > COND PRESS
OVERRIDE – 137 kPa
Prestart Alert, Configure COND PRESS OVERRIDE in
SETUP1 screen
CONDENSER PRESSURE > 1000 kPa
Prestart Alert
Low Condenser Pressure
(Freeze Protection)
244
Chiller in PUMPDOWN mode and CONDENSER
REFRIG TEMP < CONDENSER FREEZE POINT
Preset Alarm, Configure CONDENSER FREEZE POINT
in SETUP1 screen.
154
Energises condenser pump relay if CONDENSER
REFRIG TEMP < CONDENSER FREEZE POINT.
Deenergises condenser pump relay when
CONDENSER REFRIG TEMP > CONDENSER
FREEZE POINT + 2.8 K and ENTERING COND
LIQUID > CONDENSER FREEZE POINT
Configure CONDENSER FREEZE POINT in SETUP1
screen
Oil
- Low Pressure
228
OIL PRESSURE DELTA P < 90 kPa and VFD START
= TRUE
Preset Alarm
- Low Pressure
OIL PRESSURE DELTA P < 124 kPa and startup
complete after OIL PRESS VERIFY TIME elapsed
Preset Alarm, Configure OIL PRESS VERIFY TIME in
SETUP1 screen
- Low Pressure
142
OIL PRESSURE DELTA P < 124 kPa and startup
complete
Preset Alert
- Pressure Sensor Fault
227
OIL PRESSURE DELTA P > 28 kPa immediately
before oil pump turned on
Preset Alarm
- Low Temperature
105
OIL SUMP TEMP < 66°C and OIL SUMP TEMP <
EVAP REFRIG TEMP + 27.8°C
Prestart Alert
Line Voltage
- High
211/145
Line voltage > approximately 528 V, limits are
calculated by VFD
Preset Alarm/Alert
- High
108
PERCENT LINE VOLTAGE > Overvoltage threshold
Preset Prestart Alert
- Low
212/146
DC BUS VOLTAGE < approximately 408 V, limits are
calculated by a VFD
Preset Alarm/Alert
- Low
107
PERCENT LINE VOLTAGE < Undervoltage threshold Preset Prestart Alert
- Imbalance
216
LINE VOLTAGE IMBALANCE > LINE VOLTAGE %
IMBALANCE
Configure LINE VOLTAGE % IMBALANCE and LINE
VOLT IMBALANCE TIME in VFD CONF screen
Line Current - Single Cycle Dropout 210/144
Line Voltage on 2 Phases < 50% for 1 Cycle
Preset Alarm
- Imbalance
209/143
LINE CURRENT IMBALANCE>LINE CURRENT %
IMBALANCE
Configure LINE CURRENT % IMBALANCE and LINE
CURRENT IMBALANCE TIME in VFD_CONF screen
Power - Line Frequency Out of
Range
222
47 Hz < LINE FREQUENCY < 63 Hz
Preset Alarm
- ICVC Power on Reset
214/148
Loss of control power to ICVC for excessive time
period
Preset Alarm
Motor - Surge
238
> 5 surge events within SURGE TIME PERIOD and
VFD SPEED > 90%
Preset Alarm, Configure SURGE DELTA% AMPS and
SURGE TIME PERIOD in OPTIONS screen
Surge
236
> 5 surge events within SURGE TIME PERIOD and
VFD SPEED < 90%
Preset Alarm, Configure SURGE DELTA% AMPS and
SURGE TIME PERIOD in OPTIONS screen
Current Imbalance
225
MOTOR CURRENT IMBALANCE > MOTOR
CURRENT % IMBALANCE
Configure MOTOR CURRENT % IMBALANCE and
MOTOR CURRENT IMBAL TIME in VFD_CONF screen
Overload Trip
217
Any LOAD CURRENT PHASE > 108% for Excessive
Time Period
Preset Alarm, Configure MOTOR LOAD ACTIVE
DEMAND LIMIT in MAINSTAT screen
Excessive Amps
208
PERCENT LOAD CURRENT > 110% for 30 seconds. Preset Alarm
Acceleration Fault
203
PERCENT LOAD CURRENT > 95% and VFDSTART
= TRUE for 5 to 40 seconds
Preset Alarm, PERCENT LOAD CURRENT = AVERAGE
LOAD CURRENT/MOTOR RATED LOAD AMPS
Amps Not Sensed
202
PERCENT LOAD CURRENT < 5% for 3 seconds and
VFD START=TRUE for 20 seconds
Preset Alarm, PERCENT LOAD CURRENT = AVERAGE
LOAD CURRENT/MOTOR RATED LOAD AMPS
Table 5 - Protective limits and control settings