91
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
System Status
LEGEND
*Default value is shown only if configurable in this table.
Alarms Menu Description
Alarm Reset
LEGEND
*Default value is shown only if configurable in this table.
NOTE: For more information about viewing and resetting alarms,
see the Diagnostics and Troubleshooting section on page 32.
CCN TABLE NAME: SYS_STAT
PIC 5 PATH: Main Menu
Maintenance Menu
System Status
LINE
PIC 5 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
System Control Mode
sys_ctlm
RO
2
System Status
sys_stat
RO
3
Master Run Status
mas_stat
RO
4
Slave Run Status
sla_stat
RO
5
System Percent Load
sys_perl
%
RO
6
System KW
sys_kw
kW
RO
7
System Control Point
sys_stlp
°F
RO
8
System Demand Limit
sys_dem
%
RO
9
Supply Liquid Temp
sys_supt
RO
10
Return Liquid Temp
sys_rent
RO
RO — Read Only
ICON
DISPLAYED TEXT
ACCESS
ASSOCIATED TABLE
PAGE
NO.
Reset Alarms
All
ALARMRST
Current Alarms
All
CUR_ALM
History Alarms
All
ALMHIST1
Prognostics
All
HEALTH
CCN TABLE NAME: ALARMRST
PIC 5 PATH: Main Menu
Alarm Menu
Alarm Reset
LINE
PIC 5 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Alarm Reset
RST_ALM
NO/YES
NO
RW
2
Alarm State
ALM_STAT
RO
3
Current Alarm 1
alarm_1c
RO
4
Current Alarm 2
alarm_2c
RO
5
Current Alarm 3
alarm_3c
RO
6
Current Alarm 4
alarm_4c
RO
7
Current Alarm 5
alarm_5c
RO
8
Jbus Current Alarm 1
alarm_1
RO
9
Jbus Current Alarm 2
alarm_2
RO
10
Jbus Current Alarm 3
alarm_3
RO
11
Jbus Current Alarm 4
alarm_4
RO
12
Jbus Current Alarm 5
alarm_5
RO
RO — Read Only
RW — Read/Write