87
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Evap Pressure Sensor
Cond Pressure Sensor
Eco Pressure Sensor
Diff Pressure Sensor
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: PRSCAL01
PIC 5 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Evap Pressure Sensor
LINE
PIC 5 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Evap Pressure Sensor
2
Calibration Enable
cal_en
DSABLE/ENABLE
DSABLE
RW
3
Current Pressure
cur_pres
psig
RO
4
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
5
Calib Press2 (100-250PSI)
cal_p2
9 digit numeric string
0
psig
RW
6
Calibrated Slope
cal_s
RO
7
Calibrated Intercept
cal_i
RO
8
Calibration Completed
cal_st
NO/YES
NO
RO
CCN TABLE NAME: PRSCAL02
PIC 5 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Cond Pressure Sensor
LINE
PIC 5 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Cond Pressure Sensor
2
Calibration Enable
cal_en
DSABLE/ENABLE
DSABLE
RW
3
Current Pressure
cur_pres
psig
RO
4
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
5
Calib Press2 (100-250PSI)
cal_p2
9 digit numeric string
0
psig
RW
6
Calibrated Slope
cal_s
RO
7
Calibrated Intercept
cal_i
RO
8
Calibration Completed
cal_st
NO/YES
NO
RO
CCN TABLE NAME: PRSCAL03
PIC 5 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Eco Pressure Sensor
LINE
PIC 5 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Eco Pressure Sensor
2
Calibration Enable
cal_en
DSABLE/ENABLE
DSABLE
RW
3
Current Pressure
cur_pres
psig
RO
4
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
5
Calib Press2 (100-250PSI)
cal_p2
9 digit numeric string
0
psig
RW
6
Calibrated Slope
cal_s
RO
7
Calibrated Intercept
cal_i
RO
8
Calibration Completed
cal_st
NO/YES
NO
RO
CCN TABLE NAME: PRSCAL04
PIC 5 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Diff Pressure Sensor
LINE
PIC 5 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Diff Pressure Sensor
2
Calibration Enable
cal_en
DSABLE/ENABLE
DSABLE
RW
3
Current Pressure
cur_pres
psig
RO
4
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
5
Calib Press2 (100-250PSI)
cal_p2
9 digit numeric string
0
psig
RW
6
Calibrated Slope
cal_s
RO
7
Calibrated Intercept
cal_i
RO
8
Calibration Completed
cal_st
NO/YES
NO
RO
RO — Read Only
RW — Read/Write