27
7.2 - Victaulic water connections
Inlet/outlet diameters without hydronic module
30Xa
252-502
602
702-902
1002
1102
1202-1302
1352-1502
1702
standard
Diameter
in
5
5
6
8
6/6
6/6
8/6
6/6
Outside diameter
mm
141.3
141.3
168.3
219.1
168.3/168.3
168.3/168.3
219.3/168.3
168.3/168.3
Options 5, 6 and 100a
Diameter
in
4
5
5
6
5/5
6/5
8/5
6/6
Outside diameter
mm
114.3
141.3
141.3
168.3
141.3/141.3
168.3/141.3
219.1/141.3
168.3/168.3
Option 100C
Diameter
in
5
6
6
8
-
-
-
-
Outside diameter
mm
141.3
168.3
168.3
219.1
-
-
-
-
Inlet/outlet diameters with hydronic module (option)
30Xa (option 116)
252
302
352
402
452
502
Diameter
in
4
4
4
5
5
5
Outside diameter
mm
114.3
114.3
114.3
139.7
139.7
139.7
Expansion tank volume
l
50
50
50
50
50
80
Max. operating pressure
kPa
400
400
400
400
400
400
Typical water circuit diagram
Installation components
16 Flexible connection
17 Check valve
18 Charge valve
--- Hydronic module (supplied as an option)
legend
Components of the unit and hydronic module
A Pressure sensor (A-B = ΔP evaporator)
B Pressure sensor
C Pressure sensor (C-D = ΔP water filter)
D Pressure sensor
1 Victaulic screen filter
2 Expansion tank
3 Safety valve
4 Available pressure pump
5 Drain valve
6 Flow control valve
7 Evaporator
8 Evaporator defrost heater (option)
9 Hydronic module defrost heater (option)
10 Air vent (evaporator)
11 Water drain (evaporator)
12 Expansion compensator (flexible connections)
13 Flow switch
14 Water temperature sensor
15 Air vent
1
2
17
16
18
1 2
9
9
9
11
10
12
14
A
5
15
9
9
16
7
8
17
13
B
C
D
6
4
3