16
4.4 - short-circuit stability current for all units
30Xa
252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702
short-circuit stability current (TN system)*
Circuits A + B**
kA 38
38
38
38
38
38
50
50
50
50
50
50
50
50
50
50
50
50
50
50
Circuits C + D**
kA -
-
-
-
-
-
-
-
-
-
-
-
-
50
50
50
50
50
50
50
Units with option 81
A -
-
-
-
-
-
-
-
-
-
-
-
-
50
50
50
50
50
50
-
* Type of system earthing
** rms value
4.5 - Electrical data 30Xa - standard unit (including option 81)
30Xa
252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702
Power circuit
Nominal power supply
V-ph-Hz 400-3-50
Voltage range
V 360-440
Control circuit
24 V via internal transformer
Maximum start-up current*
Circuit A+B
A 269 269 287 402 505 505 574 606 773 803 805 893 941 574 773 803 891 893 941 805
Circuit C+D††
A -
-
-
-
-
-
-
-
-
-
-
-
-
587 587 587 587 587 587 805
Option 81
A -
-
-
-
-
-
-
-
-
-
-
-
-
991 1079 1155 1242 1248 1294 -
Nominal start-up current**
Circuit A+B
A 245 245 263 378 481 481 539 562 738 759 761 845 869 539 738 759 843 845 869 761
Circuit C+D††
A -
-
-
-
-
-
-
-
-
-
-
-
-
587 587 587 587 587 587 761
Option 81
A -
-
-
-
-
-
-
-
-
-
-
-
-
909 993 1036 1156 1125 1143 -
Cosine Phi maximum***
0.88 0.88 0.87 0.88 0.88 0.88 0.88 0.88 0.86 0.86 0.87 0.85 0.86 0.88 0.86 0.87 0.85 0.85 0.86 0.87
Cosine Phi nominal****
0.85 0.85 0.84 0.84 0.86 0.86 0.87 0.87 0.84 0.85 0.85 0.83 0.84 0.85 0.84 0.85 0.83 0.83 0.84 0.85
Maximum power input†
Circuit A+B
kW 121 131 141 165 185 204 247 267 293 312 343 359 420 247 293 342 388 390 420 343
Circuit C+D††
kW -
-
-
-
-
-
-
-
-
-
-
-
-
210 210 210 209 210 210 343
Option 81
A -
-
-
-
-
-
-
-
-
-
-
-
-
457 503 552 597 600 630 -
Nominal unit current draw****
Circuit A+B
A 151 167 184 210 240 266 322 349 406 431 452 516 556 322 406 449 569 538 556 452
Circuit C+D††
A -
-
-
-
-
-
-
-
-
-
-
-
-
278 278 278 292 278 278 452
Option 81
A -
-
-
-
-
-
-
-
-
-
-
-
-
600 684 727 861 816 834 -
Maximum unit current draw (Un)†
Circuit A+B
A 198 215 233 270 303 335 404 436 492 522 572 611 707 404 492 568 655 661 707 572
Circuit C+D††
A -
-
-
-
-
-
-
-
-
-
-
-
-
354 354 354 352 354 354 572
Option 81
A -
-
-
-
-
-
-
-
-
-
-
-
-
758 845 922 1007 1015 1061 -
Maximum unit current draw (Un -10%)***
Circuit A+B
A 208 232 251 290 326 360 435 469 529 561 615 657 760 435 529 611 705 711 760 615
Circuit C+D††
A -
-
-
-
-
-
-
-
-
-
-
-
-
380 380 380 378 380 380 615
Option 81
A -
-
-
-
-
-
-
-
-
-
-
-
-
815 909 991 1083 1091 1141 -
* Instantaneous start-up current (operating current of the smallest comp fan c locked rotor current in star connection of the largest compressor). Values
obtained at operation with maximum unit power input.
** Instantaneous start-up current (operating current of the smallest comp fan c locked rotor current in star connection of the largest compressor). Values
obtained at standard Eurovent unit operating conditions: air 35°C, water 12/7°C
*** Values obtained at operation with maximum unit power input.
**** Values obtained at standard Eurovent unit operating conditions: air 35°C, water 12/7°C
† Values obtained at operation with maximum unit power input. Values given on the unit name plate
†† Circuit D - only for size 1702
Note:
Motor and fan electrical data if the unit operates at Eurovent conditions (motor ambient temperature 50°C): 1.9 A
Start-up current: 8.4 A
Power input: 760 W
Summary of Contents for Aqua Force 30XA