9 - hEaT REClaIM CONDENsER OPTION
9.1 - Technical data, 30Xa units with heat reclaim condenser option
30Xa heat reclaim mode
252
302
352
402
452
502
602
702
752
802
852
902
1002
Cooling capacity*
kW
261
291
311
379
438
493
603
665
707
775
814
875
971
Heating capacity in heat reclaim mode* kW
336
373
401
481
554
620
760
832
894
974
1027
1105
1229
Total power input (unit)*
kW
82
90
99
113
128
140
172
183
206
219
234
253
283
Total energy efficiency ratio (EER/COP) kW/kW 3.16/
3.22/
3.15/
3.36/
3.40/
3.53/
3.52/
3.63/
3.43/
3.53/
3.48/
3.45/
3.42/
4.07
4.13
4.06
4.27
4.31
4.46
4.44
4.55
4.35
4.45
4.40
4.38
4.35
Operating weight**
kg
4230
4270
4280
5260
5380
5880
7000
7100
7470
7680
8320
8670
9280
Refrigerant charge
Circuit A
kg
36
37
37
53
54,5
62
62
62
70
74
77
74
96
Circuit B
kg
38
38
39
37
39
39
62
66
62
69
68
77
94
heat reclaim condenser
Flooded multi-pipe condenser
Water volume
l
38
38
38
55
68
68
55 + 55 55 + 55 55 + 68 55 + 68 55 + 68 68 + 68 68 + 68
Water connections
Victaulic
Diameter
in
3-1/2
3-1/2
3-1/2
4
4
4
4
4
4
4
4
4
4
Outside diameter
mm
93
93
93
106
106
106
106
106
106
106
106
106
106
* Entering and leaving water temperature: evaporator 12°C/7°C; heat reclaim condenser: 40°C/45°C
** Weights are for guidance only
9.2 - Dimensions, clearances
9.2.1 - 30Xa 252-352 - heat reclaim option
legend:
All dimensions are given in mm.
Required clearances for maintenance and air flow
Recommended space for evaporator tube removal
Water inlet
Water outlet
Air outlet – do not obstruct
Power supply connection
Control circuit connection
Heat reclaim condenser
ATTENTION: The Victaulic flange sleeves of the condenser
are not installed, but supplied with the unit. The sealing
joints are in the control box. The temperature sensors and
the condenser flow switch are wired and fixed in the
machine. They must be installed as described in the chapter
“Condenser water connections”.
NOTE: Drawings are not contractually binding. Before
designing an installation, consult the certified dimensional
drawings supplied with the unit or available on request.
For the positioning of the fixing points, weight distribution
and centre of gravity coordinates please refer to the dimen-
sional drawings.
1
2
C
A
C
A
A
A
Ø141.30
2297
1500
3582
2231
2253
500
1500
2200
470
2238
1500
3604
209
560