background image

AGAGC9PNS01D Gas Conversion Kit, Propane to Natural: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

11

5. Install the remaining manifold mounting screws.
6. Connect the wires to the flame sensor and hot surface igniter.
7. Connect the connector harness to gas valve.

NOTE: 

Do not use PTFE thread-seal tape.

8. Insert the gas pipe through the grommet in the casing. Apply a thin

layer of pipe dope to the threads of the pipe and thread the pipe by

into the gas valve.

NOTE: 

Use  a  back-up  wrench  on  the  gas  valve  to  prevent  the  valve

from rotating on the manifold or damaging the mounting to the burner

box.

9. With  a  back-up  wrench on the inlet boss of  the  gas valve, finish

tightening the gas pipe to the gas valve.

10. Turn gas on at electric switch on gas valve.

CHECK INLET GAS PRESSURE

NOTE: 

This kit is to be used only when inlet gas pressure is between

4.5-in. w.c. and 13.6-in. w.c.

1. On  some  models,  remove  1/8-in.  (3  mm)  pipe  plug  from  inlet

pressure tap (see 

Fig. 18

 and 

Fig. 19

) and insert pressure tap. Or, on

some models, loosen set screw on inlet tower pressure tap no more

than  one  full  turn  with  the  3/32-in.  hex  wrench,  see 

Fig. 11

  or

Fig. 12

.

2. Verify manometer is connected to inlet pressure tap on gas valve,

see 

Fig. 11

 or 

Fig. 12

.

3. Turn on furnace power supply.
4. Turn gas supply manual shutoff valve to ON position.
5. Turn furnace gas valve switch to ON position.

Single Stage Gas Valve

A190022

Representative drawing only, some models may vary in appearance.

A210192

Representative drawing only, some models may vary in appearance.

Fig. 20 – Example of Single Stage Furnace Control

1. Jumper R-W thermostat connections on control.
2. When main  burners  ignite,  confirm inlet  gas  pressure is  between

4.5-in. w.c. and 13.6-in. w.c.

3. Remove  jumper  across  R-W  thermostat  connections  to  terminate

call for heat.

4. Turn furnace gas valve switch to OFF position.
5. Turn gas supply manual shutoff valve to OFF position.
6. Turn off furnace power supply.
7. Remove  manometer  and  on  some  models  remove  pressure  tap

fitting.

8. On some models, apply pipe dope sparingly to end of inlet gas pipe

plug and install into unused end of 1/8-in. (3 mm) tee. Use a small

back-up wrench on tee when tightening gas inlet pipe plug. Or, on

some models, tighten set screw on inlet tower pressure tap with a

3/32-in. hex wrench, see 

Fig. 11

 or 

Fig. 12

.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in unit damage.
DO  NOT  operate  furnace  more  than  one  minute  to  check  inlet  gas

pressure, as conversion is not complete at this time.

WARNING

!

FIRE, EXPLOSION, ELECTRICAL SHOCK

HAZARD

Failure to follow this warning could result in personal injury, death or

property damage.

Gas  supply  MUST  be  shut  off  before  disconnecting  electrical  power

and proceeding with conversion.

WARNING

!

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury, death or

property damage.

Before  installing,  modifying,  or  servicing  system,  main  electrical

disconnect switch must be in the OFF position and install a lockout tag.

There  may  be  more  than  one  disconnect  switch.  Lock  out  and  tag

switch  with  a  suitable  warning  label.  Verify  proper  operation  after

servicing.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

24-V THERMOSTAT 

TERMINALS 

P2 

 (115VAC) HOT SURFACE IGNITER & 

INDUCER MOTOR 115V SUPPLY CONNECTOR 

115-VAC (L2) NEUTRAL 

CONNECTIONS  

115-VAC (BL-1) BLOWER MOTOR LINE 

VOLTAGE  CONNECTION  

EAC-1 TERMINAL 

 (115-VAC 1.0 AMP MAX.)  

P1 

 LOW VOLTAGE MAIN HARNESS 

CONNECTOR 

TRANSFORMER 24-VAC 

CONNECTIONS  

3-AMP FUSE  

STATUS LED LIGHT  

HEAT OFF-DELAY 

HUMIDIFIER TERMINAL 
(24-VAC 0.5 AMP MAX.) 

BOARD PART NUMBER 

LOCATION  

COOLING SPEED 

TAP  

HEATING SPEED 

TAP 

XFMR 

115-VAC (PR-1) TRANSFORMER 

PRIMARY  

J2 DEFEAT 

JUMPER 

TEST/TWIN 

J2 

HEAT OFF-DELAY 

JUMPER SELECT 

L1 

PLT -FACTORY RUN TEST PORT  

PRODUCTION USE ONLY 

BL-1 

115-VAC (L1) LINE VOLTAGE  

CONNECTION  

FAN SPEED TAP 

J1 

HUM 

Summary of Contents for AGAGC9PNS01D

Page 1: ...n personal injury or death This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire explosion or production of carbon monoxide could result causing property damage personal injury or los...

Page 2: ...o OFF A190014 Fig 1 Representative Furnace Drawing MANIFOLD ORIFICE BURNER REMOVAL NOTE Use a back up wrench on the gas valve to prevent the valve from rotating on the manifold or damaging the mounting to the burner box 1 Disconnect the gas pipe from gas valve and remove pipe from the furnace casing see Fig 1 2 Disconnect the connector harness from gas valve Disconnect wires from Hot Surface Ignit...

Page 3: ...line to point of intersection to find orifice size and manifold pressure settings For Modulating Furnaces Follow Steps 1 and 2 above For Step 3 use Table 6 for all sizes 20 000 BTUh Max Heat 8 000 BTUh Min Heat per burner except 60 000 BTUh models in a 21 in wide cabinet Table 7 for 60 000 BTUh models in a 21 in wide cabinet 20 200 BTUh Max Heat 8 000 BTUh Min Heat per burner 1 For both tables fol...

Page 4: ...No High Low No High Low 900 43 3 8 1 6 42 3 2 1 4 42 3 3 1 4 42 3 4 1 4 0 925 43 3 6 1 5 43 3 7 1 6 43 3 8 1 6 42 3 2 1 4 0 950 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 43 3 7 1 6 975 44 3 7 1 6 44 3 8 1 6 43 3 4 1 5 43 3 6 1 5 to 1000 44 3 5 1 5 44 3 6 1 5 44 3 8 1 6 43 3 4 1 4 1025 44 3 3 1 4 44 3 5 1 5 44 3 6 1 5 44 3 7 1 6 2000 1050 44 3 2 1 3 44 3 3 1 4 44 3 4 1 4 44 3 5 1 5 610 1075 45 3 7 1 6 45 3 ...

Page 5: ... 3 3 0 50 44 3 4 0 55 44 3 5 0 55 44 3 6 0 55 2743 775 45 3 7 0 60 44 3 2 0 50 44 3 3 0 50 44 3 4 0 55 9001 600 42 3 3 0 55 42 3 4 0 55 42 3 6 0 55 42 3 7 0 60 2744 625 43 3 7 0 60 42 3 2 0 50 42 3 3 0 55 42 3 4 0 55 650 43 3 5 0 55 43 3 6 0 55 43 3 7 0 60 43 3 8 0 60 675 44 3 7 0 60 44 3 8 0 60 43 3 4 0 55 43 3 5 0 55 10000 700 44 3 4 0 55 44 3 5 0 55 44 3 7 0 60 44 3 8 0 60 3048 725 44 3 2 0 50 ...

Page 6: ...y time specifications and designs without notice and without obligations 6 SINGLE STAGE GAS VALVE A221025 A221025FR Fig 5 Conversion Kit Rating Plate 40 000 BTUh to 140 000 BTUh ONLY Single Stage Furnace TWO STAGE GAS VALVE A221024 A221024FR Fig 6 Conversion Kit Rating Plate 40 000 BTUh to 140 000 BTUh ONLY Two Stage Furnace ...

Page 7: ...to plug the hole in the burner when the mixer screws are removed A11460 Fig 8 Mixer Screw Location REINSTALL BURNER ASSEMBLY To reinstall burner assembly 1 Attach flame sensor to burner assembly 2 Insert one piece burner in slot on sides of burner box and slide burner back in place 3 Reattach HSI wires to HSI 4 Verify igniter to burner alignment see Fig 9 Fig 10 A11405 Fig 9 Igniter Position Back ...

Page 8: ... or improper operation DO NOT use this kit if the gas valve has a green label 26 000 BTUh model on it The 26 000 BTUh model uses a different conversion kit available from your distributor CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in unit damage The gas valve must be converted and pre adjusted before operating on propane gas If not converted and pre adjusted sooting and c...

Page 9: ...r for the modulating gas valve is very small Needle nose pliers are required to remove the jumper from the valve If the jumper is not removed the valve will not operate properly on natural gas pressures 1 Locate the round LP GAS sticker on the top of the gas valve 2 Peel the sticker off and discard 3 Note the small square opening in the top of the gas valve 4 Note the two jumper pins inside the mo...

Page 10: ...ided in kit and install in the 1 8 in 3 mm tapped inlet pressure tap opening in the gas valve DO NOT over tighten Check for gas leaks after gas supply has been turned on A170142 Fig 19 LGPS for casing wider than 14 3 16 and vent does not pass between inducer and burner assembly INSTALL MANIFOLD 1 Refer to Fig 2 and Fig 3 2 Align the orifices in the manifold assembly with the support rings on the e...

Page 11: ...rmostat connections to terminate call for heat 4 Turn furnace gas valve switch to OFF position 5 Turn gas supply manual shutoff valve to OFF position 6 Turn off furnace power supply 7 Remove manometer and on some models remove pressure tap fitting 8 On some models apply pipe dope sparingly to end of inlet gas pipe plug and install into unused end of 1 8 in 3 mm tee Use a small back up wrench on te...

Page 12: ...TIONING A C AIRFLOW SETUP SWITCHES COMMUNICATION CONNECTOR CONTINUOUS FAN CF AIRFLOW SETUP SWITCHES OUTDOOR AIR TEMP CONNECTOR HUMIDIFIER TERMINAL 24 VAC 0 5 AMP MAX FLASH UPGRADE CONNECTOR FACTORY ONLY SW4 SETUP SWITCHES SOFTWARE VERSION PART NUMBER AND DATE CODE WWYY 24 V THERMOSTAT TERMINALS PL2 HOT SURFACE IGNITER INDUCER MOTOR CONNECTOR 115 VAC L2 NEUTRAL CONNECTIONS 115 VAC L1 LINE VOLTAGE C...

Page 13: ... than one full turn with the 3 32 in hex wrench 3 Attach manometer to manifold pressure tap on gas valve see Fig 11 Fig 12 Fig 13 Fig 14 or Fig 17 4 Turn gas supply manual shutoff valve to ON position 5 Turn furnace gas valve switch to ON position 6 Check all threaded pipe connections for gas leaks 7 Turn on furnace power supply GAS INPUT RATE INFORMATION See furnace rating plates see Fig 5 Fig 6 ...

Page 14: ...crease input rate or clockwise in to increase input rate 12 Replace caps that conceal gas valve regulator adjustment screws 13 When correct input is obtained main burner flame should be clear blue almost transparent see Fig 24 14 Remove jumper across R W1 and W2 after high heat adjustment to terminate call for heat 15 Turn setup switch SW1 TT on furnace control to OFF position 16 Turn furnace gas ...

Page 15: ...sure table on Conversion Kit Rating Plate 4 To adjust the Minimum Heat manifold pressure Slowly turn the rotary adjustment switch counterclockwise to decrease manifold pressure or clockwise to increase manifold pressure 5 Turn rotary adjustment switch no more than one click per second until you obtain the required manifold pressure This adjustment will not affect the previous Maximum Heat adjustme...

Page 16: ...to Blower Access Door of furnace Date name and address of organization making this conversion are required see Fig 26 2 Attach Conversion Rating Plate Label 348712 201 204 206 207 208 or 209 to outer door of furnace see Fig 5 Fig 6 or Fig 7 3 Attach Gas Control Conversion Label 348712 202 to gas valve Do not use 348712 203 which is similar CHECKOUT 1 Observe unit operation through two complete hea...

Reviews: