Table 2 —
39MN,MW Component Weights and Lengths, Sizes 22T to 42T
SECTION DIMENSIONS (in.) AND WEIGHTS (lb)
Nominal cfm at
500 fpm
11000 12500 125000 15000 15000 17500 18000 18500 20000 21000
Unit Size
22T
25W
25T
30W
30T
35T
36W
37T
40W
42T
Indoor H (in.)
78
60
83
60
83
86
71
102
77
113
Outdoor H (in.)
82
64
87
64
87
90
75
106
81
117
Indoor W (in.)
60
86
61
104
72
80
109
72
109
80
Outdoor W (in.)
63
89
64
107
75
83
112
75
112
83
ITEM
NO.
DESCRIPTION
AWL (in.) (INDOOR/OUTDOOR)
WEIGHT (lb)
1
Mixing box
39
327
27
315
45
354
27
409
45
399
45
444
36
503
45
461
39
538
51
506
2
Side inlet mixing box
33
437
45
439
33
473
51
601
39
531
39
590
57
656
39
613
57
741
45
672
3
Filter mixing box
48
624
36
622
53
681
36
766
51
776
53
872
45
903
50
910
48
971
58
1003
4
Air Mixer
30
444
30
445
30
485
36
606
36
553
36
621
36
666
36
648
42
741
42
716
5
Exhaust Box
39
370
27
347
45
400
27
455
45
452
45
503
36
570
45
523
39
612
51
575
6
Side outlet exhaust box
33
450
45
457
33
484
51
618
39
652
39
600
57
728
39
623
57
752
45
681
7
Internal face and bypass damper section
18
247
18
243
18
258
18
323
18
276
18
295
18
357
18
302
18
365
18
321
8
External face and bypass damper section
39
664
27
697
45
731
27
858
45
841
45
951
33
1022
45
995
33
1097
†
9
Horizontal flat filter section (2-in. or 4-in. side loading)
12
425
12
444
12
456
12
555
12
506
12
557
12
620
12
557
12
657
12
628
Horizontal flat filter with pre-filter (2-in. or 4-in. side
loading)
14
436
14
456
14
467
14
568
14
519
14
570
14
635
14
591
14
673
14
642
10
Horizontal angle filter section (2-in. or 4-in. side
loading)
23
493
24
514
30
517
24
638
30
584
23
640
26
725
27
663
24
749
26
720
11
Horizontal bag/cartridge filter section, SL
(6-in. or 12-in. median with 2-in. pre-filter)
24
500
24
520
24
534
24
645
24
591
24
648
24
729
24
671
24
770
24
727
Horizontal bag/cartridge filter section, SL
(15-in. or 30-in. media with or without header)
42
599
42
625
42
638
42
770
42
702
42
765
42
864
42
791
42
909
42
855
12
Horizontal bag/cartridge filter section, SL
48
633
48
660
48
673
48
811
48
739
48
805
48
912
48
831
48
958
48
897
13
Horizontal Blow-Thru HEPA Filter Section, FL
48
633
48
660
48
673
48
811
48
739
48
805
48
913
48
831
48
959
48
898
14
Coil and variable length plenum (with drain pan)
24
280
24
278
24
293
24
365
24
314
24
336
24
402
24
344
24
411
24
365
15
Coil and variable length plenum (without drain pan)
12
213
12
208
12
223
12
282
12
239
12
256
12
312
12
262
12
319
12
278
16
Dual coil and variable length plenum (with drain pan)
30
280
30
278
30
293
30
365
30
314
30
336
—
—
—
—
—
—
30
365
17
Vertical Coil
*
60
520
*
60
672
*
*
60
769
*
60
799
*
18
Multi-zone Damper
AWL
ZONES
*
5
13
*
5
16
*
*
5
17
*
5
17
*
19
Multi-zone/Dual Duct Heating/Cooling Section with
Drain Pan†
*
73
1252
*
73
1528
*
*
85
1756
*
91
1923
*
20
Internal face and bypass coil
24
280
24
278
24
293
14
365
24
314
24
336
24
402
24
344
24
411
24
365
21
Internal face and bypass heating coil
12
213
12
208
12
223
12
282
12
239
12
256
12
312
12
262
12
319
12
278
22
Internal face and bypass heating coil section
48
460
48
424
48
500
48
537
48
473
48
507
48
590
48
635
48
605
48
555
23
Electric Heat Section with Control
Box — Low Amp
Indoor (in.)
30
506
30
528
30
543
30
661
30
605
30
667
30
762
30
692
30
803
30
754
Electric Heat Section with Control
Box — High Amp
Indoor (in.)
42
532
42
556
42
568
30
661
42
628
42
687
30
762
42
711
30
803
*
24
Gas Heat — Low Capacity
*
91
1282
*
97
1440
97
1534
97
1693
100
2092
100
1756
99
2174
*
Gas Heat — Medium Capacity
*
127
1861
*
108
1708
108
2193
169
2485
100
2456
100
2602
166
3635
*
Gas Heat — High Capacity
*
127
1965
*
163
3365
163
2700
169
3016
189
3133
189
3143
166
4363
*
H
H
W
W
AWL
AWL