145
Table 38 —
Air Handler VFD Factory-Set Parameters (cont)
* Factory Programmed as follows: For 208-230v / 60 Hz = 208, 460v / 60 Hz = 460, 200-230v / 50 Hz = 200, 380 / 50 Hz = 400.
† Motor Nameplate Amps. Factory programmed per Programmed Settings in Table
37. This value should always be compared to the actual motor nameplate value
before start-up.
**Maximum Output Amps — Factory programmed per Table
37.
GROUP
NUMBER
PARAMETER
NUMBER
DESCRIPTION
VFD DRIVE ONLY
PARAMETERS
VFD WITH E-CLIPSE DESCRIPTION /
PARAMETER
31
3101
Number of Retries
2
2
3102
Trial Time
600 sec.
600 sec.
3103
Delay Time
5 sec.
5 sec.
3104
AR Overcurrent
Enable
Enable
3105
AR Overvoltage
Enable
Enable
3106
AR Under voltage
Enable
Enable
3107
AR AI< Minimum
(0) Disable
(0) Disable
3108
AR External Fault
(0) Disable
(0) Disable
34
3415
Signal Parameter 3
Speed
Speed
3416
Signal 3 Minimum
0
0
3417
Signal 3 Maximum
30000
30000
3418
Output 3 DSP From
0
0
3419
Output 3 DSP units
rpm
rpm
3420
Output 3 Minimum
0
0
3421
Output 3 Maximum
3000
3000
40
4001
Gain
0.7
0.7
4002
Integration Time
30 sec.
30 sec.
4005
Error Value Invert
no
no
4006
Units
volts
volts
4007
Display Format
x.xxx
x.xxx
4010
Setpoint Select
Internal
Internal
4011
Internal Setpoint
Field Program (0.0v~10,0v)
Field Program (0.0v~10,0v)
4012
Setpoint Minimum
0 v
0 v
4013
Setpoint Maximum
10.0v
10.0v
4016
ACT 1 Input
AI-2
AI-2
4027
PID Parameter Set
SET 1
SET 1
53
5301
EFB Protocol ID
0
118
5303
EFB Baud Rate
9.6
76.8
5304
EFB Parity
8 NONE 1
8 EVEN 1
5305
EFB Control Profile
ABB DRV LIM
DCU PROFILE
5310
EFB PAR 10
0
103
5311
EFM PAR 11
0
104
98
9802
Comm Prot SEL
NOT SEL
STD MODBUS