background image

GB - 9

61 AF

E N G L I S H

Nominal system water flow control

General

The optional water circulation pumps of the 61AF units 
have been sized to allow the hydronic modules to cover all 

possible configurations based on the specific installation 

conditions, i.e. for various temperature differences between 

the entering and the leaving water (

T) at full load, which can 

vary between 3 and 10 K. This required difference between 

the entering and leaving water temperature determines the 
nominal system flow rate. 

The pump of the hydronic module is a variable speed pump. 

Two different water flow controls can be selected:

-    Fixed speed control
-     Variable speed control based on constant temperature   

difference. 

The default factory setting is fixed speed and the default 
speed is 100%. Settings change need to be done by a 

Carrier Service representative.

For both flow control and for energy saving, the speed of the 

pump will be reduced to its minimum when unit capacity is 
0%.

It is essential to know the nominal system flow rate to be 
able to control it, using the variable pump speed or a 
manual valve that must be on the water leaving piping of 
the system (item 21 in the typical hydronic circuit 
diagram). 

The flow control with the pump speed or with the valve 
permits adjustment of the pressure/system flow rate curve 
in accordance with the pump pressure/flow rate curve to 
obtain the nominal flow rate at the required operating point. 
A differential pressure gauge must be installed at the unit 
inlet and outlet or using pressure gauge (item 4and 5) on 

the hydronic module.

Use the specification of the unit selection to know the 
system operating conditions and to deduce the nominal 
flow rate and the plate heat exchanger pressure drop at the 
specified conditions. If this information is not available at 

the system start-up, contact the technical service department 

responsible for the installation to get it.

These characteristics can be obtained with the technical 

literature using the unit performance tables for a 

T of 5 

K at the water heat exchanger or with the Electronic 
Catalogue selection program for all 

T conditions in the 

range of 3 to 10 K.

For domestic hot water applications (leaving water tempera-

ture above 60°C) the control cannot be made at a 

below 8 K at the condenser.
It is therefore necessary to ensure a minimum pump 

entering pressure of 40 kPa (0.4 bar) during operation and 
at shut-down. In order to obtain sufficient pressure, it is 
recommended:

•       to pressurise the hydronic circuit between 1 and 3 bars 

(maximum),

•       to clean the hydronic circuit before charging water 

(see chapter after),

•      to regularly clean the screen filter,

ATTENTION

The use of integrated hydronic kits in the 

open loop is not permitted.

Water flow control procedure (fixed speed)

Hydronic circuit cleaning procedure

• 

Open the valve fully (item 21) if present.

• 

Start-up the system or unit pump (by quick test), if the 

unit is equipped with a hydronic module with a pump.

• 

Read the difference of pressure between the pressure 

gauge connected to the unit inlet and outlet (item 3).

• 

Let the pump run for two consecutive hours to clean the 

system hydronic circuit (presence of solid contaminants).

• 

Take another reading.

• 

Compare this value to the initial value.

• 

If the difference of pressure has decreased, this 

indicates that the screen filter must be removed and 

cleaned, as the hydronic circuit contains solid 
particles. In this case close the shut-off valves at the 

water inlet and outlet (item 1) and remove the screen 
filter (item 2) after emptying the hydronic section of 
the unit (item 5).

• 

Purge the air from the circuit (item 6).

• 

Renew, if necessary, to ensure that the filter is not 

contaminated.

Water flow control procedure 
• 

When the circuit is cleaned, run the pump at speed  
100% and read the differential pressure of the unit 

(items 3) 

• 

Find the flow rate with the pump curve 100%

• 

If the flow rate is higher than the value specified close 

the control valve or reduce the pump speed.

• 

Verify the minimum speed pump (when unit capacity 
is 0%) is compatible with the flow switch protection 
(no flow switch alarm for minimum speed).

NOTE: If the system has an excessive pressure drop in 
relation to the available static pressure provided by the 
system pump the nominal water flow rate cannot be 
obtained (the resulting flow rate is lower) and the tempera-
ture difference between the condenser entering and leaving 
water will increase.

To reduce the pressure drops of the hydronic system, it is 

necessary:

• 

To reduce the individual pressure drops as much as 

possible (bends, level changes, accessories, etc.).

• 

To use a correctly sized piping diameter.

• 

To avoid hydronic system extensions, wherever 
possible.

Water flow control procedure (variable speed)

61AF units with variable-speed hydronic module include a 

water pump that automatically adjusts the flow to maintain 

a constant temperature difference. 

No control is required at start-up, but the control mode 
must be selected in the unit control by a Carrier service 
representant.

Verify the minimum speed pump (when unit capacity is 
0%) is compatible with the flow switch protection (no flow 

switch alarm for minimum speed).

Summary of Contents for 61AF014

Page 1: ...INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS 61AF B Nominal heating capacity 14 20 kW 50 Hz High temperature heat pumps Original document ...

Page 2: ......

Page 3: ...ntrol circuit fuse__________________________A Main circuit breaker rating_______________________________________________________________________________________ PHYSICAL DATA Coil Plate heat exchanger Entering air temp ____________________________ C Entering water temp _____________________ C Leaving air temp ____________________________ C Leaving water temp ______________________ C Pressure drop ...

Page 4: ...0µPa A weighting Declared dualnumber noise emission values in accordance with ISO 4871 with an associated uncertainty of 3dB A For information calculated from the sound power level Lw A 61AF standard unit Without PUMP With PUMP 014X7 014X9 019X9 014H7 014H9 019H9 Power circuit Nominal power supply V ph Hz 230 1 50 400 3 50 400 3 50 230 1 50 400 3 50 400 3 50 Voltage range V 207 253 360 440 360 440...

Page 5: ...ation of connections mm 1 water outlet 2 water inlet 3 relief valve outlet 4 electrical connections 1 2 3 4 61AF019 Fixing Holes Fixing Holes Fixing Holes 0 10 Fixing Holes 0 10 1 water outlet 2 water inlet 3 relief valve outlet 4 electrical connections ...

Page 6: ...scribed in section Electronic control 61AF014 61AF019 Minimum Clearances mm B B B F C C C C G G A D E A E B B B B F C C C C G G A D E A E B 61AF 014 019 A 100 300 B 250 200 C 500 400 D 100 200 E 670 700 F 400 500 G 670 1000 User Interface User Interface Disconnector Service Door Service Door ...

Page 7: ...cted by access panels In case of any malfunctioning turn the unit off disconnect the mains power supply and contact a qualified service engineer All of the manufacturing and packaging materials used for your new appliance are compatible with the environment and can be recycled Dispose of the packaging material in accordance with local requirements This equipment contains refrigerant R 407C that mu...

Page 8: ...h 7 water drain 1 shut off valve 2 line filter for water 10 mesh cm 3 pressure gauges 4 filling valve 5 system drain valve at the lowest points of the circuit 6 air flushing valve in the highest parts of the circuit 7 3 way valve 8 sanitary water accumulation tank 9 inside system 10 water circulation pump 11 expansion vessel Typical water circuit diagram for units without hydronic module 014P 019P...

Page 9: ...e adequately insulated and supported Installation of the following components is obligatory 1 The presence of particles in the water can lead to obstructions in the heat exchanger It is therefore necessary to protect the heat exchanger inlet with an extractable mesh filter The filter mesh gauge must be at least 10 mesh cm2 The equipment standard version with hydronic module is equipped with mesh f...

Page 10: ... Outlet available static pressure of the unit with hydronic module Water pressure drop of the unit without hydronic module 1 2 3 2 1 3 2 1 10 20 30 40 50 60 70 80 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 Available pressure kPa Water flow rate l s 014 100 014 80 014 50 10 20 30 40 50 60 70 80 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 Available pressure kPa Water flow rate l s 019 100 019 80 01...

Page 11: ...ecommended to pressurise the hydronic circuit between 1 and 3 bars maximum to clean the hydronic circuit before charging water see chapter after to regularly clean the screen filter ATTENTION The use of integrated hydronic kits in the open loop is not permitted Water flow control procedure fixed speed Hydronic circuit cleaning procedure Open the valve fully item 21 if present Start up the system o...

Page 12: ... all connections re install the protection box by fixing the two screws which were previously removed Liquid refrigerant charge Checking the charge WARNING When adjusting the refrigerant charge always ensure that water is circulating in the heat exchanger to prevent any possibility of freezing up Damage caused by freezing is not covered by the product warranty 61AF units are shipped with a full op...

Page 13: ... e g unoccupied mode and operation at low fan speed e g during the night This option also permits cascade operation of two units and remote control via communication bus RS 485 serial port Unit start up is done by the electronic control described above and must always be carried out under the supervision of a qualified air conditioning engineer This appliance is not intended for use by persons inc...

Page 14: ...ovided based on the water loop volume the fluid used and its concentration Expansion Tank Volume required of water loop volume pure water 3 10 ethylene glicol 3 20 ethylene glicol 3 5 30 ethylene glicol 3 8 40 ethylene glicol 4 2 70 70 70 70 70 70 65 70 65 70 65 70 65 70 65 70 65 70 60 65 70 60 65 70 60 65 70 60 65 70 60 65 70 60 65 70 60 65 70 55 60 65 70 55 60 65 70 55 60 65 70 55 60 65 70 50 55...

Page 15: ...g pressures are normal Check the cleanliness of the refrigerant water heat exchangers by checking the pressure drop across them Controls Check the operation of all the electrical components the high pressurestat and of the high and low pressure transducers and the water air and defrost temperature detector Maintenance Servicing recommendations Maintenance of the unit must be carried out by skilled...

Page 16: ...uously cuts out at low pressure Refrigerant losses CHECK AND ADD THE NECESSARY QUANTITY Low water flow in the exchanger CHECK WATER PUMP Unit start up delay WAIT UNTIL THE SYSTEM HAS STABILISED Unit continuously cuts out at high pressure Defective high pressurestat CHECK AND IF NECESSARY REPLACE PRESSURESTAT Blocked expansion valve CHECK AND REPLACE IF NECESSARY Blocked filter drier CHECK AND IF N...

Page 17: ......

Page 18: ...003 01 2017 Manufacturer CARRIER SCS MontluelFrance The manufacturer reserves the right to change the specification without prior notice Printed in the European Union www eurovent certification com www certiflash com www ecodesign hvac carrier com ...

Reviews: