background image

This feature helps diagnose a system problem in case of a
component failure. To initiate component test procedure, short
(jumper) the TEST 1/4-in. quick connect terminal on control
board (adjacent to diagnostic light) and the Com terminal on
thermostat connection block for approximately 2 sec. (See Fig.
11.)

NOTE:

Component test feature will not operate if any thermostat

signal is present at control center.

Component test sequence is as follows.

a. Momentarily jumper TEST and Com terminals until LED

goes off.

b. LED will display previous fault 4 times.

c. Inducer motor operates for 10 sec, then stops.

d. Hot surface ignitor is energized for 15 sec, then de-

energized.

e. Blower motor operates on cooling speed for 10 sec, then

stops.

f. Blower motor operates on heating speed for 10 sec, then

stops.

3. To operate furnace, follow procedures on operating instruction

label attached to furnace.

4. With furnace operating, set thermostat below room tempera-

ture and observe that furnace goes off. Set thermostat above
room temperature and observe that furnace restarts.

ADJUSTMENTS

1. Set gas input rate.

There are 2 methods of adjusting the gas input rate. The
preferred method is by using Table 7 and following instruc-
tions in item a. The second method is by clocking the gas
meter and following instructions in item b.

The gas valve regulator has been nominally set at 3.5-in. wc
for natural gas. When adjusting input rate, do not set manifold
pressure above 3.8-in. wc or below 3.2-in. wc.

a. Check gas input rate using Table 7.

(1.) Obtain average yearly heat value for local gas supply.

(2.) Obtain average yearly specific gravity for local gas

supply.

(3.) Verify furnace model. Table 7 can only be used for

model 58RAV Furnaces.

(4.) Check and verify orifice size in furnace. NEVER

ASSUME THE ORIFICE SIZE. ALWAYS CHECK
AND VERIFY.

DO NOT redrill burner orifices. Improper drilling (burrs,
out-of-round holes, etc.) can cause excessive burner noise and
misdirection of burner flames. This can result in flame
impingement of the burners and heat exchangers, causing
failure.

(5.) Find natural gas heat value and specific gravity in

Table 7.

(6.) Follow heat value and specific gravity lines to point of

intersection. Find orifice size and manifold pressure
settings for proper operation at given natural gas
conditions.

EXAMPLE:
Heat value 1070 Btu/cu ft
Specific gravity 0.58
Therefore; Orifice No. 44 *

Manifold pressure 3.6-in. wc

* The furnace is shipped with No. 43 orifices. Therefore, in
this example all main burner orifices must be changed and
the manifold pressure must be adjusted.

(7.) Proceed to item c to adjust manifold pressure.

b. Check gas input rate by clocking gas meter.

(1.) Obtain average yearly heat value for local gas supply.

(2.) Check and verify orifice size in furnace. NEVER

ASSUME THE ORIFICE SIZE. ALWAYS CHECK
AND VERIFY.

(3.) Turn off all other gas appliances and pilots.

(4.) Start furnace and let run for 3 minutes.

(5.) Measure time (in sec) for gas meter to complete 1

revolution.

(6.) Refer to Table 8 for cu ft of gas per hr.

(7.) Multiply gas rate (cu ft/hr) by heating value (Btu/cu

ft).

EXAMPLE:
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 1070 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 72 sec
Gas rate = 100 X 1070 = 107,000 Btuh

(8.) Check to make sure that measured gas input does not

exceed gas input on unit rating plate.

(9.) Proceed to item c to adjust manifold pressure.

c. Adjust gas input.

(1.) Remove regulator adjustment seal cap. (See Fig. 14.)

(2.) Turn adjusting screw counterclockwise to decrease

input. Turn screw clockwise to increase input. DO
NOT set manifold pressure less than 3.2-in. wc or
more than 3.8-in. wc for natural gas. Make any major
adjustments by changing main burner orifices.

(3.) When correct input is obtained, replace regulator

adjustment seal cap. Main burner flame should be
clear blue, almost transparent. (See Fig. 15.)

d. High altitude—In the United States, gas input on unit rating

plate is for altitudes up to 2000 ft. Ratings for altitudes over
2000 ft must be 4 percent less for each 1000 ft above sea
level. To obtain the adjusted altitude rating, adjust the
manifold pressure, item c, and replace the main burner
orifices as needed. Refer to NFGC Appendix F, Table F-4
for proper orifice sizing at high altitudes.

e. Canadian installations only—The Canadian ratings are

approved for altitudes up to 2000 ft for natural and propane
gases. High-altitude ratings are from 2000 ft to 4500 ft
above sea level. See Table 9 for nominal burner orifice
size. High-altitude input ratings include a 10 percent
derated as required by Canadian standards.

2. Set temperature rise.

Furnace must operate within range of temperature rise speci-
fied on the unit rating plate. Determine the air temperature rise
as follows.

12

Summary of Contents for 58RAV Series

Page 1: ...erve precautions in the literature on tags and on labels attached to or shipped with the unit and other safety precautions that may apply Follow all safety codes In the United States follow all safety codes including the National Fuel Gas Code NFGC NFPA No 54 1992 ANSI Z223 1 1992 In Canada refer to the current ama CANADIAN GAS ASSOCIATION APPROVED R Table 1 Clearances From Combustible Materials I...

Page 2: ...charges from personnel and hand tools which are held during the procedure These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace the control and the person at the same electrostatic potential 1 Disconnect all power to the furnace DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CON TROL PRIOR TO DISCHARGING YOUR BODY S ELEC TROSTATIC CHARGE...

Page 3: ...e personal injury or death For accessory installation details refer to the applicable installa tion literature NOTE Remove all shipping brackets and materials before oper ating the furnace Step 1 Location GENERAL Do not install furnace in a corrosive or contaminated atmo sphere Make sure all combustion and circulating air require ments are followed in addition to all local codes and ordinances Do ...

Page 4: ...sume that wood louvers have a 20 percent free area and metal louvers or grilles have a 60 percent free area Screens when used must not be smaller than 1 4 in mesh Louvers and grilles must be constructed so they cannot be closed The size of the openings depends upon whether the air comes from inside or outside the structure 1 All air from inside the structure a Each opening MUST have at least 1 sq ...

Page 5: ...12 MAX 1 SQ IN PER 4000 BTUH OUTDOORS 1 SQ IN PER 4000 BTUH 1 SQ IN PER 2000 BTUH 12 MAX Use any of the following combinations of openings A B C D D E F G NOTE Minimum dimensions of 3 In F G For Example 58RAV FURNACE INPUT BTUH FREE AREA PER OPENING SQ IN ROUND PIPE IN DIA 46 000 11 5 4 69 000 17 3 5 92 000 23 0 6 115 000 28 8 7 135 000 34 5 7 For Example 58RAV FURNACE INPUT BTUH FREE AREA PER OPE...

Page 6: ...rom each corner by hanger bolts 4 each 3 8 in all thread rod cut to desired length 1 X 3 8 in flat washer 3 8 in lockwasher and 3 8 in nut Dimples are provided for hole locations See Fig 1 Since horizontal crawlspace installation is very similar to the attic installation refer to Step 4 The installation of a sheet metal shield in front of the louvered control panel is covered in Step 4 For a crawl...

Page 7: ... 1 8 in NPT plugged tapping accessible for test gage connection must be installed immediately upstream of the gas supply connection to the furnace and downstream of the manual shut off valve Place a ground joint union between the gas control manifold and the manual shut off Install a sediment trap in the riser leading to the furnace The trap can be installed by connecting a tee to the riser leadin...

Page 8: ...in control board Any direct shorts during installation service or maintenance could cause this fuse to blow If fuse replacement is required use ONLY a 3 amp fuse of identical size ACCESSORIES 1 Electronic air cleaner EAC Two quick connect terminals marked EAC 1 and EAC 2 are provided for EAC connection See Fig 11 These terminals are energized with 115v 1 5 amp maximum during blower motor operation...

Page 9: ...TE 2 FIELD SUPPLIED FUSED DISCONNECT CONDENSING UNIT TWO WIRE FURNACE R G C W C R G Y GND GND FIELD 24 VOLT WIRING FIELD 115 208 230 460 VOLT WIRING FACTORY 24 VOLT WIRING FACTORY 115 VOLT WIRING 208 230 OR 460 VOLT THREE PHASE 208 230 VOLT SINGLE PHASE WHT BLK WHT BLK NOTES Connect Y terminal as shown for proper operation Some thermostats require a C terminal connection as shown If any of the ori...

Page 10: ...or cooling R G and R Y circuits close The R Y circuit starts the outdoor condensing unit and combined R Y and R G circuits start the furnace blower motor on cooling speed The EAC 1 terminal is energized with 115v whenever the blower is operating on cooling speed When the thermostat is satisfied R G and R Y circuits are broken Furnace blower and EAC continue operating on cooling speed for an additi...

Page 11: ...COMPONENT TEST TWIN TERMINAL TRAN TRANSFORMER 115VAC 24VAC JUNCTION UNMARKED TERMINAL PCB TERMINAL FACTORY WIRING 115VAC FACTORY WIRING 24VAC FIELD WIRING 115VAC FIELD WIRING 24VAC CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 NEUTRAL L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 1 HEAT SPARE 2 COOL NOTE 8 COM HSIR EAC...

Page 12: ... given natural gas conditions EXAMPLE Heat value 1070 Btu cu ft Specific gravity 0 58 Therefore Orifice No 44 Manifold pressure 3 6 in wc The furnace is shipped with No 43 orifices Therefore in this example all main burner orifices must be changed and the manifold pressure must be adjusted 7 Proceed to item c to adjust manifold pressure b Check gas input rate by clocking gas meter 1 Obtain average...

Page 13: ... 40 41 3 2 3 5 40 41 3 3 3 6 40 41 39 3 4 3 7 3 2 40 41 39 3 5 3 8 3 3 40 38 39 3 6 3 2 3 4 40 38 39 3 8 3 3 3 5 38 39 3 4 3 6 38 39 3 4 3 7 890 41 42 3 2 3 6 41 42 3 4 3 7 40 41 3 2 3 5 40 41 3 3 3 6 40 41 39 3 4 3 7 3 2 40 41 39 3 5 3 8 3 3 40 39 3 6 3 4 40 38 39 3 7 3 2 3 5 40 38 39 3 8 3 3 3 6 905 42 3 5 41 42 3 2 3 6 41 42 3 4 3 7 40 41 3 2 3 5 40 41 3 3 3 6 40 41 39 3 4 3 7 3 2 40 41 39 3 5 ...

Page 14: ... 8 Gas Rate Cu Ft Hr SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL 1 cu ft 2 cu ft 5 cu ft 1 cu ft 2 cu ft 5 cu ft 10 11 12 13 14 360 327 300 277 257 720 655 600 555 514 1800 1636 1500 1385 1286 50 51 52 53 54 72 71 69 68 67 144 141 138 136 133 360 355 346 340 333 15 16 17 18 19 240 225 212 200 189 480 450 424 400 379 1200 1125 1059 1000 947 55 56 57 58 59 6...

Page 15: ...econnect inducer motor wires replace control door and turn on 115 v power to furnace 4 Check auxiliary limits when used a Turn off 115 v power to furnace b Remove blower access door c Disconnect red motor lead at blower speed selector Mark terminal for proper re connection d Replace blower access door e Turn on 115 v power to furnace Be sure room thermostat is calling for heat f Allow furnace to o...

Page 16: ...ce Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 962 9212 Packaged Service Training Classroom Service Training Copyright 1995 CARRIER Corp 7310 W Morris St Indianapolis IN 46231 58ra10si Manufacturer reserves the right...

Reviews: