WIRING
All wires must be sized per NEC (National Electrical Code) or
CEC (Canadian Electrical Code) and local codes. Use Electrical
Data table MCA (minimum circuit amps) and MOCP (maximum
over current protection) to correctly size the wires and the
disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt
rating and 2/64--inch thick insulation must be used.
The use of BX cable is not recommended.
Recommended Connection Method for Power and
Communication Wiring -- Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied
14/3 power/communication wiring from the outdoor unit to indoor
unit consists of four (4) wires and provides the power for the
indoor unit. Two wires are high voltage AC power, one is
communication wiring and the other is a ground wire.
Recommended Connection Method for Power and
Communication Wiring (To minimize communication wiring
interference)
Power Wiring:
The main power is supplied to the outdoor unit. The field supplied
power wiring from the outdoor unit to indoor unit consists of three
(3) wires and provides the power for the indoor unit. Two wires are
high voltage AC power and one is a ground wire.
To minimize voltage drop, the factory recommended wire size is
14/2 stranded with a ground.
Communication Wiring:
A separate shielded copper conductor only, with a minimum 300
volt rating and 2/64--inch thick insulation, must be used as the
communication wire from the outdoor unit to the indoor unit.
Please use a separate shielded 16GA stranded control wire.
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S
Wires should be sized based on NEC and local codes.
S
Use copper conductors only with a minimum 300 volt
rating and 2/64 inch thick insulation.
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S
Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S
Every wire must be connected firmly. Loose wiring
may cause terminal to overheat or result in unit
malfunction. A fire hazard may also exist. Therefore, be
sure all wiring is tightly connected.
S
No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S
Disconnecting means must be provided and shall be
located within sight and readily accessible from the air
conditioner.
S
Connecting cable with conduit shall be routed through
hole in the conduit panel.
CONNECTION DIAGRAM
Fig. 9 – Connection Diagram
Summary of Contents for 538FEQ009RBGA
Page 6: ...6 DIMENSIONS OUTDOOR Fig 3 Dimensions Fig 4 Dimensions Fig 5 Dimensions Fig 6 Dimensions...
Page 10: ...10 Outdoor Unit Fig 11 Sizes 09 12...
Page 47: ...47 Shut off power hold both ends of horizontal...
Page 48: ...48...
Page 49: ...49...
Page 50: ...50 ziptie side cutters...
Page 51: ...51...
Page 52: ...52...
Page 53: ...53...
Page 54: ...54...
Page 67: ...67 6 7 8...
Page 68: ...68 9 Remove electric box 10 Remove evaporator...
Page 69: ...69...
Page 70: ...70 11 Remove swing blade...
Page 71: ...71 12 Remove cross flow blade and motor...
Page 72: ...72 13 Remove drive box...
Page 84: ...84 APPENDIX Appendix 1 Reference Sheet of Celsius and Fahrenheit...
Page 89: ...89 UNIT BREAKDOWNS a b c d e...
Page 90: ...90 f g h...
Page 91: ...91...
Page 92: ...92...
Page 93: ...93...