4. Diagnosis for anti--high temperature, overload protection (AP1 below is control board of the outdoor unit).
Main detection points:
S
If the outdoor ambient temperature is in the normal range
S
If the indoor and outdoor fan is running normal
S
Are the units clear of dirt and debris?
Malfunction diagnosis process:
1. Check if fan terminal
OFAN is connected well
2. Test if resistance value
of any two terminals is less
than 1k with ohmic meter
Do the indoor and outdoor
fan work?
After the unit
de-energized for 20min
Replace
control board
AP1
Outdoor unit coils clean?
Clean coils
Replace
outdoor fan
Y
Replace fan
capacitor C1
High temperature,
overload protection
Above operating envelope
If the outdoor ambient temperature is
higher than 127 ºF?
No
No
Y
No
End
Yes
Yes
Yes
Fig. 40 – Troubleshooting
Summary of Contents for 538FEQ009RBGA
Page 6: ...6 DIMENSIONS OUTDOOR Fig 3 Dimensions Fig 4 Dimensions Fig 5 Dimensions Fig 6 Dimensions...
Page 10: ...10 Outdoor Unit Fig 11 Sizes 09 12...
Page 47: ...47 Shut off power hold both ends of horizontal...
Page 48: ...48...
Page 49: ...49...
Page 50: ...50 ziptie side cutters...
Page 51: ...51...
Page 52: ...52...
Page 53: ...53...
Page 54: ...54...
Page 67: ...67 6 7 8...
Page 68: ...68 9 Remove electric box 10 Remove evaporator...
Page 69: ...69...
Page 70: ...70 11 Remove swing blade...
Page 71: ...71 12 Remove cross flow blade and motor...
Page 72: ...72 13 Remove drive box...
Page 84: ...84 APPENDIX Appendix 1 Reference Sheet of Celsius and Fahrenheit...
Page 89: ...89 UNIT BREAKDOWNS a b c d e...
Page 90: ...90 f g h...
Page 91: ...91...
Page 92: ...92...
Page 93: ...93...