background image

5

INSTALLATION

SLEEVE INSTALLATION
REQUIREMENTS

Reminder: Units are shipped without sleeve.

■  

INSPECT WALL SLEEVE INSTALLATION

 — In a 

replacement or retrofit situation, it is recommended 
that a sleeve be used with a chassis from the same 
manufacturer. Refer to Figures 5 and 6 for typical wall 
installation and unit dimensions.

1. For lateral airflow applications, an accessory lat-

eral duct must be used. Refer to Figure 7.

2. The sleeve must be mounted so that it is level in 

all directions. A 

1

/

4

-in. pitch is built into the unit

chassis for proper condensate drainage. An acces-
sory drain kit is available if needed.

3. The sleeve should be caulked on all sides, includ-

ing both inside and outside of the building.

IMPORTANT: If more than 4 in. of the sleeve 
projects into the room or the wall is less than 2 in. 
thick, an accessory subbase must be used for sup-
port. Refer to Figure 8.

TYPICAL WALL INSTALLATION (52SC,SE,SQ)

NOTES:
1. Sleeve may be flush mounted to floor, and front panel may have to be notched

to accommodate service cord. 

2. If more than 4 in. of sleeve projects into room an accessory subbase must be

used.

3. If wall is less than 2 in. thick, an accessory subbase must be used. 

TYPICAL CURTAIN WALL INSTALLATION

(All Models)

WALL SLEEVE AND SLEEVE EXTENSION

(Field-Fabricated) (All Models)

NOTES:

1. Unit sleeve and sleeve extension (field-fabricated) should be connected

before installing in wall opening.

2. Sleeve extension is water-bearing. It must be watertight when installed

against unit sleeve. Use quality grade sealant on all butting flanges. Attach
both sections with bolts and nuts or self-tapping screws installed from unit
sleeve to extension. Cut drain slots in front and rear flanges of extension to
line up with drain openings in unit sleeve.

3. Install 2 center baffles inside sleeve extension to prevent recirculation of out-

door air circuit.

4. Leave 

3

/

8

-in. roomside projection of extension and 

5

/

8

-in. outdoor projection

of sleeve. This allows for unit casing clearance to finished wall plus ample
edging to apply weather sealant between unit sleeve/extension assembly
and wall opening.

5. Paint sleeve extension and seal corner and lap joints; clear all drain holes of

excess sealant, paint, etc., to permit free drainage.

6. Install quality flashing under unit sleeve and extension using quality sealant

between flashing and wall.

7. Install unit casing/extension assembly following standard practices. Seal

assembly to wall on all 4 sides, indoors and outdoors.

8. Make provision for a condensate drain extension tube for routing excess con-

densate from the wall sleeve through the sleeve extension to the building
exterior.

9. Attach grille to the outside of the sleeve extension (using field-supplied

fasteners).

10. Seal any gaps between grille and sleeve extension on all sides.

FIGURE 5 — TYPICAL WALL INSTALLATIONS

Summary of Contents for 52SC

Page 1: ...ELECTRICAL DATA 3 4 ALL UNITS 3 VOLTAGE SUPPLY 4 LOW VOLTAGE CONNECTIONS REMOTE CONTROL AND ENERGY MANAGEMENT ACCESSORY 4 INSTALLATION 5 11 SLEEVE INSTALLATION REQUIREMENTS 5 ACCESSORY INSTALLATION 9...

Page 2: ...igure 1 lists the model number voltage ranges and other important electrical information about this product Reading and under standing this material is important for proper use of this unit To access...

Page 3: ...nductors only GROUNDING For safety and protection the unit is grounded through the service cord plug or through separate ground wire provided on hardwired units Be sure that the branch circuit or gene...

Page 4: ...CONNECTIONS REMOTE CONTROL AND ENERGY MANAGEMENT ACCESSORY Energy Management Accessory must be ordered sepa rately and field installed Low voltage connections must be made for Energy Management Units...

Page 5: ...d sleeve extension field fabricated should be connected before installing in wall opening 2 Sleeve extension is water bearing It must be watertight when installed against unit sleeve Use quality grade...

Page 6: ...ommodate service cord except for units with subbase see Note 4 4 When using subbase accessory wall sleeve must extend 31 4 in minimum into room and 31 4 in minimum to 51 2 in maximum above floor 5 Dim...

Page 7: ...ille Only a Carrier outdoor grille should be used with the 52S unit air conditioner Use of any other grille must be approved by Carrier in Syracuse New York In deep wall applications if an existing gr...

Page 8: ...ier to separate condenser air from the major components compressor and fan motor If baffles are not installed properly loss of perfor mance and premature damage to the major compo nents can result Cha...

Page 9: ...from terminals on the thermostat to terminals on chassis terminal board See Fig ures 13A and 13B 5 Reinstall cover with two screws 6 Mount field supplied thermostat to wall 7 Set thermostat anticipato...

Page 10: ...air grille is mounted on the unit so that the air dis charges forward If upward discharge is required remove the grille invert it and reinstall on the chassis ADJUST VENT The VENT knob is located on t...

Page 11: ...thermostat so that the rib on the vent control lever assembly which is located under the limiter is positioned between the temperature limits desired NOTE The numbers stamped on the limiter repre sent...

Page 12: ...ed comfort level this setting is not required See Finding Temperature Setting section below for more information LOW HEAT OR LOW COOL Push button and rotate temperature knob to desired comfort level T...

Page 13: ...d for heating and cooling VENT CONTROL See Adjustments on page 10 for vent operating information CARE AND MAINTENANCE In order to maintain proper performance of your pack aged terminal air conditioner...

Page 14: ...ned at least once each year DISCONNECT POWER TO UNIT CORD CONNECTED UNITS 1 REMOTE CONTROL UNITS Set switch on wall mounted thermostat to OFF ALL OTHER UNITS Push OFF button on unit control panel 2 Di...

Page 15: ...four screws fastening chassis to sleeve and two screws on top of duct adapter See Figure 24 3 Slide out chassis Lift by holding the unit basepan 4 Remove aluminum top panel one screw each side See Fig...

Page 16: ...indoor coil and stator side of the out door coil by washing or vacuuming 2 Clean vent screen by washing or vacuuming Open vent door and pull screen out See Figure 30 3 Clean basepan including drain pa...

Page 17: ...urface of the blower scroll with a 3 solution of hydrogen peroxide to kill any fungus spores Wipe up excess solution in the bottom of the blower scroll with a clean cloth See Figure 32 9 Clean the ins...

Page 18: ...base 265 v Cord Kit Corrosion Protected Polymer Sleeve Standard Architectural Grille in Aluminum or Plastic Lateral Duct Kit Hardwire Kit Locking Control Door Kit Standard Manual Changeover Thermostat...

Page 19: ...19...

Page 20: ...nufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations PC 132 Catalog No 535 232 Printed in U S A Form 52S 47SI P...

Reviews: