ELECTRICAL DATA
Be sure that your outlet matches the appropriate
blade configuration of the supplied plug and that it is
within reach of the service cord. A hardwire kit is
available as an accessory to change cord-connected
units to hardwired units. The junction box can be
mounted with manufacturer’s non-electric subbase ac-
cessory. (See Accessories section, page 18.)
ALL UNITS
■
WIRE SIZE —
Use recommended wire size given in
Table 1 and install a single branch circuit. All wiring
must comply with local and national codes. All units
are designed to operate off single branch cir-
cuits only.
NOTE: Use copper conductors only.
■
GROUNDING
— For safety and protection, the unit
is grounded through the service cord plug or through
separate ground wire provided on hardwired units. Be
sure that the branch circuit or general purpose outlet
is grounded.
TABLE 1 — SUGGESTED BRANCH CIRCUIT
WIRE SIZES*
LEGEND
AWG —
American Wire Gage
*Single circuit from main box.
†Based on copper wire at 60 C temperature rating.
ELECTRICAL SHOCK HAZARD
DO NOT alter cord or plug, and DO NOT use an
extension cord. Personal injury or damage to the
unit may result.
IMPORTANT: All packaged terminal 265-v units
can either be hardwired or cord-connected with
accessory kits. Both accessories must be purchased
separately through your order correspondent.
NAMEPLATE AMPS
AWG WIRE SIZE
7.0 to 12
14
12.1 to 16
12
16.1 to 24
10
FIGURE 3 — MODEL NUMBER NOMENCLATURE