background image

13

OPERATING CONTROLS

The following controls are located on the right side of 
the chassis. (See Figure 20.) To obtain access to op-
erating controls, remove the unit front panel as shown 
on page 2.

■  

FAN CYCLE SWITCH

 — (Not available on RC 

units.) This allows the fan to operate in two modes: 
CON — This setting allows the fan to run continu-
ously, circulating air even when the temperature set-
ting has been satisfied. This switch helps to maintain 
the room temperature closer to the thermostat setting. 
Use this switch position when maximum comfort is 
desired. 
CYC — This setting allows the fan to cycle on and off 
with the compressor during heating or cooling. The fan 
stops when the temperature setting is satisfied. This 
results in longer unit off-time and wider variations in 
room temperature and humidity.

■  

OUTDOOR THERMOSTAT (52SQ HEAT PUMP 

UNITS ONLY)

 — If the setscrew is left at the factory 

setting (in the fully clockwise position), the unit will 
operate in the reverse cycle heating mode. The control 
is the defrost thermostat in this mode. The 52SQ ther-
mostat sensing capillary is located between the fins of 
the outdoor coil. When the temperature at the capil-
lary reaches 25° F, the outdoor frost thermostat closes, 
shutting off the compressor and energizing the electric 
heater. The electric heater remains on until the tem-
perature at the outdoor thermostat capillary reaches 
40° F; then the electric heater is shut off and the com-
pressor is energized. To set unit to operate in electric 
heat mode only, turn the setscrew to the fully counter-
clockwise position. Once in electric heat mode, the 
compressor is disabled for heating and cooling.

■  

VENT CONTROL

 — See Adjustments on page 10 

for vent operating information.

 

CARE AND MAINTENANCE

In order to maintain proper performance of your pack-
aged terminal air conditioner or heat pump, it is very 
important that the fan and outdoor coils, the blower 
wheel, blower scroll, electric heater, and all drain pas-
sages are thoroughly cleaned at least once per year. 
Carrier recommends that as a minimum, the cleaning 
should be conducted prior to the start of each heating 
season. The air inlet filter should be cleaned every 
month.
Depending on local conditions, more frequent clean-
ing of the unit may be required to ensure optimum 
performance and long operating life. Examples of 
these special conditions include areas where construc-
tion dust or heavy airborne dirt is found, or environ-
ments that promote the growth of fungus.

AIR INLET FILTER

■  

AIR INLET FILTER

 should be cleaned once each 

month.

1. If front panel has not been removed, remove panel 

as shown in Figure 2. To remove filter, grasp two
filter tabs and pull the filter forward (Figure 21).

IMPORTANT: When unit is first started, high 
humidity conditions can cause condensation to 
form on grille. Keep doors and windows closed. 
Room humidity decreases and moisture
evaporates.

Some local conditions and environments can cause 
fungi to grow inside the air conditioner, especially 
on indoor blower section. Dried fungi, dirt and other 
foreign material are fire hazards. Be sure to clean 
unit according to the instructions that follow.

HEAT

PUMP

ELECTRIC

HEAT

VENT

CLOSED

OPEN

CON

CYC

OUTDOOR
THERMOSTAT
(ON HEAT
PUMP ONLY)

FAN CYCLE
SWITCH
(NOT ON RC
UNITS)

VENT
LEVER

HEAT
MODE

HEAT
PUMP

ELECTRIC

NOTE: ELECTRIC HEAT
MODE WILL DISABLE
COMPRESSOR OPERATING.

52SQ506082 REV-

VENT

OPEN/CLOSED

FIGURE 20 — TYPICAL 52S SERIES

OPERATING CONTROLS

Summary of Contents for 52SC

Page 1: ...ELECTRICAL DATA 3 4 ALL UNITS 3 VOLTAGE SUPPLY 4 LOW VOLTAGE CONNECTIONS REMOTE CONTROL AND ENERGY MANAGEMENT ACCESSORY 4 INSTALLATION 5 11 SLEEVE INSTALLATION REQUIREMENTS 5 ACCESSORY INSTALLATION 9...

Page 2: ...igure 1 lists the model number voltage ranges and other important electrical information about this product Reading and under standing this material is important for proper use of this unit To access...

Page 3: ...nductors only GROUNDING For safety and protection the unit is grounded through the service cord plug or through separate ground wire provided on hardwired units Be sure that the branch circuit or gene...

Page 4: ...CONNECTIONS REMOTE CONTROL AND ENERGY MANAGEMENT ACCESSORY Energy Management Accessory must be ordered sepa rately and field installed Low voltage connections must be made for Energy Management Units...

Page 5: ...d sleeve extension field fabricated should be connected before installing in wall opening 2 Sleeve extension is water bearing It must be watertight when installed against unit sleeve Use quality grade...

Page 6: ...ommodate service cord except for units with subbase see Note 4 4 When using subbase accessory wall sleeve must extend 31 4 in minimum into room and 31 4 in minimum to 51 2 in maximum above floor 5 Dim...

Page 7: ...ille Only a Carrier outdoor grille should be used with the 52S unit air conditioner Use of any other grille must be approved by Carrier in Syracuse New York In deep wall applications if an existing gr...

Page 8: ...ier to separate condenser air from the major components compressor and fan motor If baffles are not installed properly loss of perfor mance and premature damage to the major compo nents can result Cha...

Page 9: ...from terminals on the thermostat to terminals on chassis terminal board See Fig ures 13A and 13B 5 Reinstall cover with two screws 6 Mount field supplied thermostat to wall 7 Set thermostat anticipato...

Page 10: ...air grille is mounted on the unit so that the air dis charges forward If upward discharge is required remove the grille invert it and reinstall on the chassis ADJUST VENT The VENT knob is located on t...

Page 11: ...thermostat so that the rib on the vent control lever assembly which is located under the limiter is positioned between the temperature limits desired NOTE The numbers stamped on the limiter repre sent...

Page 12: ...ed comfort level this setting is not required See Finding Temperature Setting section below for more information LOW HEAT OR LOW COOL Push button and rotate temperature knob to desired comfort level T...

Page 13: ...d for heating and cooling VENT CONTROL See Adjustments on page 10 for vent operating information CARE AND MAINTENANCE In order to maintain proper performance of your pack aged terminal air conditioner...

Page 14: ...ned at least once each year DISCONNECT POWER TO UNIT CORD CONNECTED UNITS 1 REMOTE CONTROL UNITS Set switch on wall mounted thermostat to OFF ALL OTHER UNITS Push OFF button on unit control panel 2 Di...

Page 15: ...four screws fastening chassis to sleeve and two screws on top of duct adapter See Figure 24 3 Slide out chassis Lift by holding the unit basepan 4 Remove aluminum top panel one screw each side See Fig...

Page 16: ...indoor coil and stator side of the out door coil by washing or vacuuming 2 Clean vent screen by washing or vacuuming Open vent door and pull screen out See Figure 30 3 Clean basepan including drain pa...

Page 17: ...urface of the blower scroll with a 3 solution of hydrogen peroxide to kill any fungus spores Wipe up excess solution in the bottom of the blower scroll with a clean cloth See Figure 32 9 Clean the ins...

Page 18: ...base 265 v Cord Kit Corrosion Protected Polymer Sleeve Standard Architectural Grille in Aluminum or Plastic Lateral Duct Kit Hardwire Kit Locking Control Door Kit Standard Manual Changeover Thermostat...

Page 19: ...19...

Page 20: ...nufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations PC 132 Catalog No 535 232 Printed in U S A Form 52S 47SI P...

Reviews: