26
CURBS & WEIGHTS DIMENSIONS -- CHASSIS 2 (cont.)
C08532
Fig. 7 -- Dimensions 50TC 08--12
C08309
Fig. 8 -- Curb Dimensions
GASKET
(SUPPLIED WITH CURB)
NAIL
COUNTER FLASHING
(FIELD SUPPLIED)
ROOFING FELT
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
ROOFING FELT
(FIELD SUPPLIED)
C07457
Fig. 9 -- Curb Installation Detail (Typical)
C
B
A
D
C08337
Fig. 10 -- Service Clearance
LOC
DIMENSION
CONDITION
A
48” (1219 mm) Unit disconnect is mounted on panel
36” (914 mm)
If dimension---B is 12” (305 mm)
18” (457 mm)
No disconnect, convenience outlet option
18” (457 mm)
Recommended service clearance (use electric screwdriver)
12” (305 mm)
Minimum clearance (use manual ratchet screwdriver)
B
36” (914 mm)
Unit has economizer
12” (305 mm)
If dimension---A is 36” (914 mm)
Special
Check for sources of flue products within 10---ft of unit fresh air intake hood
C
36” (914 mm)
Side condensate drain is used
18” (457 mm)
Minimum clearance
D
42” (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
36” (914 mm)
Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
50TC
Summary of Contents for 50TC Series
Page 23: ...23 CURBS WEIGHTS DIMENSIONS CHASSIS 1 C08529 Fig 1 Dimensions 50TC 04 07 50TC ...
Page 25: ...25 CURBS WEIGHTS DIMENSIONS CHASSIS 2 C08531 Fig 6 Dimensions 50TC 08 12 50TC ...
Page 27: ...27 CURBS WEIGHTS DIMENSIONS CHASSIS 3 C08533 Fig 11 Dimensions 50TC 14 50TC ...
Page 84: ...84 C08536 Fig 25 2 Stage Cooling Typical Power Diagram 50TC ...
Page 86: ...86 C08576 Fig 27 2 Stage Typical Wiring Diagram 50TC ...