background image

20

Table 6—

Troubleshooting Chart

SYMPTOM

CAUSE

REMEDY

Compressor and outdoor fan

will not start

Power failure

Call power company

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

Defective contactor, transformer, control relay, or high--

pressure, loss--of--charge or low--pressure switch

Replace component

Insufficient line voltage

Determine cause and correct

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

User Interface setting too low/too high

Reset UI setting

Compressor will not start but condenser fan

runs

Faulty wiring or circuit

Loose connections in compressor

Check wiring and repair or replace

Compressor motor burned out, seized, or

Determine cause

internal overload open

Replace compressor

Defective run capacitor, overload, or PTC (positive

temperature coefficient) thermistor

Determine cause and replace

One leg of 3--phase power dead

Replace fuse or reset circuit breaker

Determine cause

Low input voltage (20 percent low)

Determine cause and correct

Three--phase scroll compressor (size 030--

Scroll compressor is rotating in the wrong direction

Correct the direction of rotation by reversing the

060 unit) has a low pressure differential

3--phase power leads to the unit

Compressor cycles (other than normally sat-

isfying) cooling/heating calls

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and re-

charge to capacities shown on rating plate

Defective compressor

Replace and determine cause

Insufficient line voltage

Determine cause and correct

Blocked outdoor coil

Determine cause and correct

Defective run/start capacitor, overload or start relay

Determine cause and replace

Faulty outdoor fan motor or capacitor

Replace

Restriction in refrigerant system

Locate restriction and remove

Compressor operates continuously

Dirty air filter

Replace filter

Unit undersized for load

Decrease load or increase unit size

UI temperature set too low

Reset UI setting

Low refrigerant charge

Locate leak, repair, and recharge

Air in system

Recover refrigerant, evacuate system, and re-

charge

Outdoor coil dirty or restricted

Clean coil or remove restriction

Excessive head pressure

Dirty air filter

Replace filter

Dirty indoor or outdoor coil

Clean coil

Refrigerant overcharged

Recover excess refrigerant

Air in system

Recover refrigerant, evacuate system, and re-

charge

Indoor or outdoor air restricted or air short--cycling

Determine cause and correct

Head pressure too low

Low refrigerant charge

Check for leaks, repair and recharge

Restriction in liquid tube

Remove restriction

Excessive suction pressure

High heat load

Check for source and eliminate

Reversing valve hung up or leaking internally

Replace valve

Refrigerant overcharged

Recover excess refrigerant

Suction pressure too low

Dirty air filter

Replace filter

Low refrigerant charge

Check for leaks, repair and recharge

Metering device or low side restricted

Remove source of restriction

Insufficient coil airflow

Check filter–replace if necessary

Temperature too low in conditioned area

Reset UI setting

Outdoor ambient below 55

°

F

Install low--ambient kit

Filter drier restricted

Replace

50SD

Summary of Contents for 50SD024

Page 1: ...Rater Piston 19 TROUBLESHOOTING 19 START UP CHECKLIST 19 C99001 Fig 1 Unit 50SD SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical com...

Page 2: ...re that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a n...

Page 3: ...UNIT 2 00 50 8 SIDE OPPOSITE DUCTS 14 00 355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36...

Page 4: ...m BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 1066 8 Refer...

Page 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 50SD024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Page 6: ...follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is engineered and designed to be ins...

Page 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Page 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Page 9: ...res connected to the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor cont...

Page 10: ...erminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component System contains oil and refrigerant under pressure 5 To rem...

Page 11: ...83 3 80 90 208 230 3 60 187 253 11 7 88 0 0 9 4 1 19 6 19 6 25 25 3 8 5 0 10 4 12 0 19 6 20 2 25 25 7 2 10 0 20 8 24 1 31 2 35 2 35 40 11 3 15 0 31 3 36 1 44 2 50 2 15 0 20 0 41 7 48 1 57 2 65 3 60 7...

Page 12: ...n time delay expires when FAN switch is placed in AUTO position 2 Place SYSTEM switch in COOL position and FAN switch in AUTO position Set cooling control below room temperature Observe that compresso...

Page 13: ...604 1538 1457 1362 1271 High Watts 798 772 738 700 CFM 1720 1648 1540 1414 048 Low Watts 627 617 607 584 567 548 528 503 CFM 1550 1530 1493 1461 1414 1361 1320 1250 Med Watts 771 755 734 711 690 665 6...

Page 14: ...14 A05112 Fig 13 Wiring Diagram 208 230 1 60 50SD...

Page 15: ...15 A06307 Fig 14 Wiring Diagram 208 230 3 60 50SD...

Page 16: ...16 A06485 Fig 15 Wiring Diagram 460 3 60 50SD...

Page 17: ...o change the speed of the indoor fan motor IFM remove the fan motor speed leg lead from the time delay relay TDR This wire is attached to terminal 3 of TDR for 3 phase units To change the speed remove...

Page 18: ...g season Clean when necessary 4 Check electrical connections for tightness and controls for proper operation each cooling season Service when necessary 5 Ensure electric wires are not in contact with...

Page 19: ...e grille ELECTRICAL CONTROLS AND WIRING Inspect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panel to locate all the electri...

Page 20: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Page 21: ...AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE ____...

Page 22: ...t 2006 Carrier Corporation Printed in the U S A Edition Date 09 06 Catalog No 50SD 4SI Replaces 50SD 3SI Manufacturer reserves the right to change at any time specifications and design without notice...

Reviews: