background image

18

NOTE

: Once the compressor has started and then has stopped, it

should not be started again until 5 minutes have elapsed.
The cooling cycle remains on until the room temperature drops to

a point that is slightly below the cooling control setting of the room

thermostat. At this point, the thermostat breaks the circuit between
thermostat terminal R to terminals Y and G. These open circuits

deenergize contactor coil C and relay coil TDR. The condenser and
compressor motors stop. After a 30--second delay, the blower motor

stops. The unit is in a standby condition, waiting for the next call for

cooling from the room thermostat.

MAINTENANCE

To ensure continuing high performance, and to minimize the

possibility of premature equipment failure, periodic maintenance

must be performed on this equipment. This cooling unit should be
inspected at least once each year by a qualified service person. To

troubleshoot unit, refer to Table 6, Troubleshooting Chart.
NOTE TO EQUIPMENT OWNER: Consult your local dealer

about the availability of a maintenance contract.

PERSONAL INJURY AND UNIT DAMAGE HAZARD

Failure to follow this warning could result in personal injury

or death and possible unit component damage.
The ability to properly perform maintenance on this

equipment requires certain expertise, mechanical skills, tools

and equipment. If you do not possess these, do not attempt to

perform any maintenance on this equipment, other than those

procedures recommended in the Owner’s Manual.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow these warnings could result in personal

injury or death:

1. Turn off electrical power to the unit before performing any

maintenance or service on this unit.

2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact

with the unit.

!

WARNING

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
Errors made when reconnecting wires may cause improper

and dangerous operation. Label all wires prior to

disconnecting when servicing.

CAUTION

!

The minimum maintenance requirements for this equipment are as
follows:

1. Inspect air filter(s) each month. Clean or replace when

necessary.

2. Inspect indoor coil, drain pan, and condensate drain each

cooling season for cleanliness. Clean when necessary.

3. Inspect blower motor and wheel for cleanliness each cooling

season. Clean when necessary.

4. Check electrical connections for tightness and controls for

proper operation each cooling season. Service when

necessary.

5. Ensure electric wires are not in contact with refrigerant

tubing or sharp metal edges.

AIR FILTER

IMPORTANT

: Never operate the unit without a suitable air filter

in the return--air duct system. Always replace the filter with the same
dimensional size and type as originally installed. See Table 1 for
recommended filter sizes.

Inspect air filter(s) at least once each month and replace

(throwaway--type) or clean (cleanable--type) at least twice during
each cooling season and twice during the heating season, or

whenever the filter becomes clogged with dust and lint.
INDOOR BLOWER AND MOTOR

NOTE

: All motors are pre--lubricated. Do not attempt to lubricate

these motors.

For longer life, operating economy, and continuing efficiency, clean
accumulated dirt and grease from the blower wheel and motor

annually.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Disconnect and tag electrical power to the unit before cleaning

and lubricating the blower motor and wheel.

!

WARNING

To clean the blower motor and wheel:

1. Remove and disassemble blower assembly as follows:

a. Remove unit access panel.

b. Disconnect motor lead from time delay relay (TDR).

Disconnect yellow lead from terminal L2 of the contactor.

c. On all units remove blower assembly from unit. Remove

screws securing blower to blower partition and slide

assembly out. Be careful not to tear insulation in blower
compartment.

d. Ensure proper reassembly by marking blower wheel and

motor in relation to blower housing before disassembly.

e. Loosen setscrew(s) that secures wheel to motor shaft,

remove screws that secure motor mount brackets to
housing, and slide motor and motor mount out of

housing.

2. Remove and clean blower wheel as follows:

a. Ensure proper reassembly by marking wheel orientation.

b. Lift wheel from housing. When handling and/or cleaning

blower wheel, be sure not to disturb balance weights

(clips) on blower wheel vanes.

c. Remove caked--on dirt from wheel and housing with a

brush. Remove lint and/or dirt accumulations from wheel
and housing with vacuum cleaner, using soft brush
attachment. Remove grease and oil with mild solvent.

d. Reassemble wheel into housing.

e. Reassemble motor into housing. Be sure setscrews are

tightened on motor shaft flats and not on round part of
shaft.

f. Reinstall unit access panel.

3. Restore electrical power to unit. Start unit and check for

proper blower rotation and motor speeds during cooling

cycles.

50SD

Summary of Contents for 50SD024

Page 1: ...Rater Piston 19 TROUBLESHOOTING 19 START UP CHECKLIST 19 C99001 Fig 1 Unit 50SD SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical com...

Page 2: ...re that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a n...

Page 3: ...UNIT 2 00 50 8 SIDE OPPOSITE DUCTS 14 00 355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36...

Page 4: ...m BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 1066 8 Refer...

Page 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 50SD024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Page 6: ...follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is engineered and designed to be ins...

Page 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Page 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Page 9: ...res connected to the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor cont...

Page 10: ...erminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component System contains oil and refrigerant under pressure 5 To rem...

Page 11: ...83 3 80 90 208 230 3 60 187 253 11 7 88 0 0 9 4 1 19 6 19 6 25 25 3 8 5 0 10 4 12 0 19 6 20 2 25 25 7 2 10 0 20 8 24 1 31 2 35 2 35 40 11 3 15 0 31 3 36 1 44 2 50 2 15 0 20 0 41 7 48 1 57 2 65 3 60 7...

Page 12: ...n time delay expires when FAN switch is placed in AUTO position 2 Place SYSTEM switch in COOL position and FAN switch in AUTO position Set cooling control below room temperature Observe that compresso...

Page 13: ...604 1538 1457 1362 1271 High Watts 798 772 738 700 CFM 1720 1648 1540 1414 048 Low Watts 627 617 607 584 567 548 528 503 CFM 1550 1530 1493 1461 1414 1361 1320 1250 Med Watts 771 755 734 711 690 665 6...

Page 14: ...14 A05112 Fig 13 Wiring Diagram 208 230 1 60 50SD...

Page 15: ...15 A06307 Fig 14 Wiring Diagram 208 230 3 60 50SD...

Page 16: ...16 A06485 Fig 15 Wiring Diagram 460 3 60 50SD...

Page 17: ...o change the speed of the indoor fan motor IFM remove the fan motor speed leg lead from the time delay relay TDR This wire is attached to terminal 3 of TDR for 3 phase units To change the speed remove...

Page 18: ...g season Clean when necessary 4 Check electrical connections for tightness and controls for proper operation each cooling season Service when necessary 5 Ensure electric wires are not in contact with...

Page 19: ...e grille ELECTRICAL CONTROLS AND WIRING Inspect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panel to locate all the electri...

Page 20: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Page 21: ...AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE ____...

Page 22: ...t 2006 Carrier Corporation Printed in the U S A Edition Date 09 06 Catalog No 50SD 4SI Replaces 50SD 3SI Manufacturer reserves the right to change at any time specifications and design without notice...

Reviews: