background image

9

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in damage to the unit

being installed.

1. Make all electrical connections in accordance with NEC

ANSI/NFPA (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical

connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable local
codes. Refer to unit wiring diagram.

2. Use only copper conductor for connections between

field--supplied electrical disconnect switch and unit. DO

NOT USE ALUMINUM WIRE.

3. Be sure that high--voltage power to unit is within operating

voltage range indicated on unit rating plate. On 3--phase

units, ensure phases are balanced within 2 percent. Consult
local power company for correction of improper voltage

and/or phase imbalance.

4. Do not damage internal components when drilling through

any panel to mount electrical hardware, conduit, etc.

!

CAUTION

HIGH--VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a

field--supplied, waterproof disconnect switch mounted at, or within
sight from the unit. Refer to the unit rating plate, NEC and local

codes for maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing (See Table 3 for electrical data).
The field--supplied disconnect may be mounted on the unit over the

high--voltage inlet hole when the standard power and low--voltage
entry points are used. See Fig. 2 and 3 for acceptable location.
See unit wiring label and Fig. 11 for reference when making high
voltage connections. Proceed as follows to complete the

high--voltage connections to the unit.
Single phase units:

1. Run the high--voltage (L1, L2) and ground lead into the

control box.

2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side

of the contactor.

4. Connect field L1 to black wire on connection 11 of the

compressor contactor.

5. Connect field wire L2 to yellow wire on connection 23 of the

compressor contactor.

Three--phase units:

1. Run the high--voltage (L1, L2, L3) and ground lead into the

control box.

2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side

of the contactor.

4. Connect field L1 to black wire on connection 11 of the

compressor contactor.

5. Connect field wire L2 to yellow wire on connection 13 of the

compressor contactor.

6. Connect field wire L3 to blue wire from compressor.

SPECIAL PROCEDURES FOR 208--V OPERATION

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Make sure that the power supply to the unit is switched OFF

and lockout tag installed before making any wiring changes.

!

WARNING

CONTROL VOLTAGE CONNECTIONS

NOTE

:Do not use any type of power--stealing thermostat. Unit

control problems may result.

Use no. 18 American Wire Gage (AWG) color--coded, insulated

(35

°

C minimum) wires to make the control voltage connections

between the thermostat and the unit. If the thermostat is located more

than 100 ft from the unit (as measured along the control voltage

wires), use no. 16 AWG color--coded, insulated (35

°

C minimum)

wires.
STANDARD CONNECTION
Remove knockout hole located in the electric heat panel adjacent to

the control access panel. See Fig. 2 & 3. Remove the rubber

grommet from the installer’s packet (included with unit) and install
grommet in the knockout opening. Provide a drip loop before

running wire through panel.
Run the low--voltage leads from the thermostat, through the inlet

hole, and into unit low--voltage splice box.
Locate five 18--gage wires leaving control box. These low--voltage
connection leads can be identified by the colors red, green, yellow,

brown (See Fig. 11). Ensure the leads are long enough to be routed
into the low--voltage splice box (located below right side of control

box). Stripped yellow wire is located in connection box. Route leads
through hole in bottom of control box and make low--voltage

connections (See Fig. 11). Secure all cut wires, so that they do not

interfere with operation of unit.
TRANSFORMER PROTECTION

The transformer is of the energy--limiting type. It is set to withstand

a 30--second overload or shorted secondary condition.

POWER

SUPPLY

FIELD-SUPPLIED

FUSED DISCONNECT

HIGH VOLTAGE

POWER LEADS

(SEE UNIT WIRING

LABEL)

GND

CONTROL BOX

SPLICE BOX

LOW-VOLTAGE

POWER LEADS

(SEE UNIT

WIRING LABEL)

Y

G

R

C

YEL(Y)

GRN(G)

RED(R)

BRN(C)

THERMOSTAT

(TYPICAL)

LEGEND

Field Control-Voltage Wiring

Field High-Voltage Wiring

NOTE: Use blue wire for 3-phase units only.

C99010

Fig. 11 -- High-- and Control--Voltage Connections

50SD

Summary of Contents for 50SD024

Page 1: ...Rater Piston 19 TROUBLESHOOTING 19 START UP CHECKLIST 19 C99001 Fig 1 Unit 50SD SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical com...

Page 2: ...re that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a n...

Page 3: ...UNIT 2 00 50 8 SIDE OPPOSITE DUCTS 14 00 355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36...

Page 4: ...m BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 1066 8 Refer...

Page 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 50SD024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Page 6: ...follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is engineered and designed to be ins...

Page 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Page 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Page 9: ...res connected to the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor cont...

Page 10: ...erminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component System contains oil and refrigerant under pressure 5 To rem...

Page 11: ...83 3 80 90 208 230 3 60 187 253 11 7 88 0 0 9 4 1 19 6 19 6 25 25 3 8 5 0 10 4 12 0 19 6 20 2 25 25 7 2 10 0 20 8 24 1 31 2 35 2 35 40 11 3 15 0 31 3 36 1 44 2 50 2 15 0 20 0 41 7 48 1 57 2 65 3 60 7...

Page 12: ...n time delay expires when FAN switch is placed in AUTO position 2 Place SYSTEM switch in COOL position and FAN switch in AUTO position Set cooling control below room temperature Observe that compresso...

Page 13: ...604 1538 1457 1362 1271 High Watts 798 772 738 700 CFM 1720 1648 1540 1414 048 Low Watts 627 617 607 584 567 548 528 503 CFM 1550 1530 1493 1461 1414 1361 1320 1250 Med Watts 771 755 734 711 690 665 6...

Page 14: ...14 A05112 Fig 13 Wiring Diagram 208 230 1 60 50SD...

Page 15: ...15 A06307 Fig 14 Wiring Diagram 208 230 3 60 50SD...

Page 16: ...16 A06485 Fig 15 Wiring Diagram 460 3 60 50SD...

Page 17: ...o change the speed of the indoor fan motor IFM remove the fan motor speed leg lead from the time delay relay TDR This wire is attached to terminal 3 of TDR for 3 phase units To change the speed remove...

Page 18: ...g season Clean when necessary 4 Check electrical connections for tightness and controls for proper operation each cooling season Service when necessary 5 Ensure electric wires are not in contact with...

Page 19: ...e grille ELECTRICAL CONTROLS AND WIRING Inspect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panel to locate all the electri...

Page 20: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Page 21: ...AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE ____...

Page 22: ...t 2006 Carrier Corporation Printed in the U S A Edition Date 09 06 Catalog No 50SD 4SI Replaces 50SD 3SI Manufacturer reserves the right to change at any time specifications and design without notice...

Reviews: