background image

7

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage.
Do not slide unit to position when it is sitting on the curb.

Curb gasketing material may be damaged and leaks may

result.

CAUTION

!

Step 3 — Field Fabricate Ductwork

On vertical units, secure all ducts to roof curb and building

structure.

Do not connect ductwork to unit.

Insulate and

weatherproof all external ductwork, joints, and roof openings with

counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated

and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be

ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork if electric
heat is not used. Cabinet return-air static pressure (a negative

condition) shall not exceed 0.35--in. wg with economizer or
0.45--in. wg without economizer.

Step 4 — Make Unit Duct Connections

Vertical Supply/Return Configuration

Unit is shipped in vertical supply/return configuration. Ductwork

openings are shown in Fig. 1 and 3. Attach the ductwork to the
roof curb. Do not attach duct directly to the unit.
Duct connections are shown in Fig. 4. Field-fabricated concentric

ductwork may be connected as shown in Fig. 5.

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
For vertical supply and return units, tools or parts could

drop into ductwork and cause an injury. Install a 90

_

turn

in the return ductwork between the unit and the conditioned

space. If a 90

_

elbow cannot be installed, then a grille of

sufficient strength and density should be installed to prevent

objects from falling into the conditioned space.

CAUTION

!

AIR

OUT

AIR

IN

ECONOMIZER

C06307

Fig. 4 -- Air Distribution -- Vertical Supply and Return

AIR OUT

AIR IN

AIR OUT

ECONOMIZER

C06308

Fig. 5 -- Air Distribution -- Concentric Duct

Horizontal Applications

Horizontal units are shipped with an outer panel that allows for
side by side horizontal duct connections. If specified during

ordering, the unit will be shipped with the vertical duct openings
blocked off from the factory, ready for side supply installation. If

the horizontal supply/return option was not specified at time of

ordering the unit, a field--installed accessory kit is required to
convert the vertical unit into a horizontal supply configuration.
Installation of the duct block--off covers should be completed prior
to placing the unit unless sufficient side clearance is available. A

minimum of 66 in. is required between the unit and any

obstruction to install the duct block--off covers. Slide supply duct
dimensions and locations are shown on Fig. 3. Install ductwork to

horizontal duct flange connections on side of unit.
Units with electric heat require a 1-in. clearance for the first 24 in.

of ductwork. Outlet grilles must not lie directly below unit
discharge.

NOTE

: A 90

_

elbow must be provided in the supply ductwork to

comply with UL (Underwriters Laboratories) codes for use with
electric heat.

Step 5 — Install External Trap for Condensate

Drain

The unit’s

3

/

4

-in. condensate drain connections are located on the

bottom and side of the unit. Unit discharge connections do not
determine the use of drain connections; either drain connection can

be used with vertical or horizontal applications. See Fig. 3 for
locations.
When using the standard side drain connection, make sure the plug

(red) in the alternate bottom connection is tight before installing the
unit. (See Fig. 7.)
To use the bottom drain connection for a roof curb installation,
relocate the factory-installed plug (red) from the bottom connection

to the side connection. A

1

/

2

-in. socket extension can be used to

remove the plug. (See Fig. 7.) The piping for the condensate drain
and external trap can be completed after the unit is in place.

50PG16

Summary of Contents for 50PG16 series

Page 1: ...tions Have fire extinguishers available for all brazing operations ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before performing service or maintena...

Page 2: ...2 C06310 Fig 1 Base Unit Dimensions 50PG16...

Page 3: ...d and above unit to provide minimum distance from combustible materials proper airflow and service access Do not install unit in an indoor location Do not locate air inlets near exhaust vents or other...

Page 4: ...Aluminum Lanced Fins Face Split Condenser A Outer Rows Fins in 2 17 Face Area sq ft 26 6 Condenser B Inner Rows Fins in 2 17 Face Area sq ft 30 2 Humidi MiZer Coil Enhanced Copper Tubes Aluminum Lanc...

Page 5: ...47 8 High 43 8 Belt Type Low AX Mid Low BX High BX Pulley Center Line Distance Min in Low 14 2 Mid Low 10 8 High 8 6 Pulley Center Line Distance Max in Low 10 8 Mid Low 14 2 High 12 Speed Change rpm L...

Page 6: ...6 C06306 Fig 3 Roof Curb Details 50PG16...

Page 7: ...turn AIR OUT AIR IN AIR OUT ECONOMIZER C06308 Fig 5 Air Distribution Concentric Duct Horizontal Applications Horizontal units are shipped with an outer panel that allows for side by side horizontal du...

Page 8: ...TRICAL OPTIONS PANEL BASEPAN CONNECTIONS ACCESS PANEL CONTROL BOX AND COMPRESSOR ACCESS DOOR FILTER ACCESS DOOR ELECTRIC HEAT ACCESS PANEL CONDENSER COIL ACCESS PANEL C06309 Fig 6 Panel and Filter Loc...

Page 9: ...tails refer to the Controls Start up Operation and Troubleshooting manual All 208 230 v units are factory wired for 230 v power supply If the 208 230 v unit is to be connected to a 208 v power supply...

Page 10: ...4 95 533 533 20 256A00 104 2 120 3 37 6 50 0 158 3 148 3 175 175 034 146 164 533 533 20 257A00 156 3 180 4 56 3 75 0 184 3 208 4 200 250 034 206 233 533 533 20 460 3 60 414 506 9 0 62 9 0 62 7 7 50 1...

Page 11: ...538 20 256A00 104 2 120 3 37 6 50 0 164 3 153 7 175 175 034 151 170 538 538 20 257A00 156 3 180 4 56 3 75 0 190 4 213 9 200 250 034 211 239 538 538 20 460 3 60 414 506 9 0 62 9 0 62 7 7 50 1 0 Low 4...

Page 12: ...e unit shall be fuse or HACR breaker 2 Unbalanced 3 Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2 Use the following formula to determine the pe...

Page 13: ...or wall in the conditioned space to sense average temperature Route thermostat or space temperature sensor cable or equivalent single leads of colored wire from subbase terminals through conduit into...

Page 14: ...g 11 13 NOTE For wire runs up to 50 ft use no 18 AWG American Wire Gauge insulated wire 35 C minimum For 50 to 75 ft use no 16 AWG insulated wire 35 C minimum For over 75 ft use no 14 AWG insulated wi...

Page 15: ...must be configured correctly refer to the Controls Start up Operation and Troubleshooting manual for details If the customer also wishes to install a smoke detector into a Humidi MiZer equipped 50PG...

Page 16: ...ic relief hoods Repeat for second hood Install baffle between the outdoor air hoods with the screws saved from item 1 See Fig 17 Step 8 Install All Accessories After all of the factory installed optio...

Reviews: