5. Align hole in flange of economizer panel with left edge of

hood. Hang economizer hood on the top flange of the

economizer panel by rotating hood until top flange of the
economizer hood engages the bent flange on the
economizer panel. Rotate hood until hood is flush with the

economizer panel. Hood will support itself from flange.
Align holes in hood with holes in panel and secure hood to

panel with screws saved from Step 2. (See Fig. 17 and 19.)
Repeat for second hood.
Loosen screws securing the clip on top of the flange of each

opening. Rotate clip 180

_

and tighten screw. Install 1--in.

filter provided by inserting under the clip on the flange and

letting filter drop behind bracket holding barometric relief
hoods. Repeat for second hood. Install baffle between the
outdoor air hoods with the screws saved from item 1. (See

Fig. 17.)

Step 8 — Install All Accessories

After all of the factory-installed options have been adjusted, install

all field- installed accessories. Refer to the accessory installation

instructions included with each accessory.

Step 9 — Configure Controls

Refer to unit Controls and Troubleshooting literature for all

controls information.

BAROMETRIC
RELIEF HOOD

MOUNTING
FLANGE

POWER EXHAUST/

C06262

Fig. 18 -- Barometric Relief/Power Exhaust Hood Flange

MOUNTING 

FLANGE 

ECONOMIZER 

HOOD 

C06263

Fig. 19 -- Economizer Flange

Copyright 2007 Carrier Corp.

S

7310 W. Morris St.

S

Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 10/07

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No:50PG---38SI

Replaces: 50PG--- 18SI

50PG16

Summary of Contents for 50PG16 series

Page 1: ...tions Have fire extinguishers available for all brazing operations ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before performing service or maintena...

Page 2: ...2 C06310 Fig 1 Base Unit Dimensions 50PG16...

Page 3: ...d and above unit to provide minimum distance from combustible materials proper airflow and service access Do not install unit in an indoor location Do not locate air inlets near exhaust vents or other...

Page 4: ...Aluminum Lanced Fins Face Split Condenser A Outer Rows Fins in 2 17 Face Area sq ft 26 6 Condenser B Inner Rows Fins in 2 17 Face Area sq ft 30 2 Humidi MiZer Coil Enhanced Copper Tubes Aluminum Lanc...

Page 5: ...47 8 High 43 8 Belt Type Low AX Mid Low BX High BX Pulley Center Line Distance Min in Low 14 2 Mid Low 10 8 High 8 6 Pulley Center Line Distance Max in Low 10 8 Mid Low 14 2 High 12 Speed Change rpm L...

Page 6: ...6 C06306 Fig 3 Roof Curb Details 50PG16...

Page 7: ...turn AIR OUT AIR IN AIR OUT ECONOMIZER C06308 Fig 5 Air Distribution Concentric Duct Horizontal Applications Horizontal units are shipped with an outer panel that allows for side by side horizontal du...

Page 8: ...TRICAL OPTIONS PANEL BASEPAN CONNECTIONS ACCESS PANEL CONTROL BOX AND COMPRESSOR ACCESS DOOR FILTER ACCESS DOOR ELECTRIC HEAT ACCESS PANEL CONDENSER COIL ACCESS PANEL C06309 Fig 6 Panel and Filter Loc...

Page 9: ...tails refer to the Controls Start up Operation and Troubleshooting manual All 208 230 v units are factory wired for 230 v power supply If the 208 230 v unit is to be connected to a 208 v power supply...

Page 10: ...4 95 533 533 20 256A00 104 2 120 3 37 6 50 0 158 3 148 3 175 175 034 146 164 533 533 20 257A00 156 3 180 4 56 3 75 0 184 3 208 4 200 250 034 206 233 533 533 20 460 3 60 414 506 9 0 62 9 0 62 7 7 50 1...

Page 11: ...538 20 256A00 104 2 120 3 37 6 50 0 164 3 153 7 175 175 034 151 170 538 538 20 257A00 156 3 180 4 56 3 75 0 190 4 213 9 200 250 034 211 239 538 538 20 460 3 60 414 506 9 0 62 9 0 62 7 7 50 1 0 Low 4...

Page 12: ...e unit shall be fuse or HACR breaker 2 Unbalanced 3 Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2 Use the following formula to determine the pe...

Page 13: ...or wall in the conditioned space to sense average temperature Route thermostat or space temperature sensor cable or equivalent single leads of colored wire from subbase terminals through conduit into...

Page 14: ...g 11 13 NOTE For wire runs up to 50 ft use no 18 AWG American Wire Gauge insulated wire 35 C minimum For 50 to 75 ft use no 16 AWG insulated wire 35 C minimum For over 75 ft use no 14 AWG insulated wi...

Page 15: ...must be configured correctly refer to the Controls Start up Operation and Troubleshooting manual for details If the customer also wishes to install a smoke detector into a Humidi MiZer equipped 50PG...

Page 16: ...ic relief hoods Repeat for second hood Install baffle between the outdoor air hoods with the screws saved from item 1 See Fig 17 Step 8 Install All Accessories After all of the factory installed optio...

Reviews: