Fig. 14 -- Humidi--MiZer
t
Low--Voltage Terminal Strip -- Humidity Sensor/Humidistat Wiring
C07191
Fig. 15 -- Third Party Smoke Detector on Humidi--MiZer
Route thermostat or space temperature sensor cable or equivalent
single leads of colored wire from subbase terminals through
conduit into unit to low-voltage connections as shown on unit label
wiring diagram and in Fig. 11-13.
NOTE
: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gauge) insulated wire (35 C minimum). For 50 to 75 ft, use
no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use
no. 14 AWG insulated wire (35 C minimum). All wire larger than
no. 18 AWG cannot be directly connected at the thermostat and
will require a junction box and splice at the thermostat.
Set heat anticipator settings as follows:
VOLTAGE
STAGE 1
(W1) ON
STAGE 1 AND 2
(W1 AND W2) ON
All
0.2
0.4
Settings may be changed slightly to provide a greater degree of
comfort for a particular installation.
50PG16