25
Table 13 — Accessory/FIOP Static Pressure (in. wg)
LEGEND
*There are no electric heaters available for 017 and 025 575-v units.
NOTES:
1. Heaters are rated at 240 v, 480 v, and 575 v.
2. The factory assembled horizontal adapter substantially
improves fan performance.
3. The static pressure must be added to external static pressure.
The sum and the evaporator entering-air cfm should then be
used in conjunction with the Fan Performance table to deter-
mine blower rpm, bhp, and watts.
Table 14 — MoistureMiser Dehumidification
Package Static Pressure Drop (in. wg)
UNIT
50HJ
HEATER
RATED
VOLTAGE*
CFM
ELECTRIC HEATERS
PRESSURE DROP
(kW)
ECONOMI$ER
PRESSURE
DROP
015, 017
208/240-3-60
3,750
0.05 (14/19, 26/34)
0.06 (42/56)
0.07 (56/75)
0.03
4,000
0.05 (14/19, 26/34)
0.06 (42/56)
0.07 (56/75)
0.04
5,000
0.07 (14/19, 26/34)
0.08 (42/56)
0.10 (56/75)
0.05
6,000
0.09 (14/19, 26/34)
0.12 (42/56)
0.15 (56/75)
0.07
7,200
0.11 (14/19, 26/34)
0.16 (42/56)
0.20 (56/75)
0.09
7,500
0.12 (14/19, 26/34)
0.17 (42/56)
0.21 (56/75)
0.10
480-3-60
3,750
0.05 (15, 32)
0.06
(55)
0.07 (80)
0.03
4,000
0.05 (15, 32)
0.06
(55)
0.07 (80)
0.04
5,000
0.07 (15, 32)
0.08
(55)
0.10 (80)
0.05
6,000
0.09 (15, 32)
0.12
(55)
0.15 (80)
0.07
7,200
0.11 (15, 32)
0.15
(55)
0.20 (80)
0.09
7,500
0.12 (15, 32)
0.17
(55)
0.21 (80)
0.10
575-3-60
3,750
0.06 (37)
0.03
4,000
0.06 (37)
0.03
5,000
0.08 (37)
0.05
6,000
0.12 (37)
0.07
7,200
0.15 (37)
0.09
7,500
0.17 (37)
0.10
025
208/240-3-60
5,000
0.08 (26/34)
0.11 (42/56)
0.14 (56/75)
0.06
6,000
0.09 (26/34)
0.12 (42/56)
0.15 (56/75)
0.07
7,200
0.11 (26/34)
0.16 (42/56)
0.20 (56/75)
0.09
9,000
0.15 (26/34)
0.19 (42/56)
0.24 (56/75)
0.11
10,000
0.17 (26/34)
0.21 (42/56)
0.26 (56/75)
0.12
11,250
0.20 (26/34)
0.24 (42/56)
0.29 (56/75)
0.14
480-3-60
5,000
0.08 (32)
0.11 (55)
0.14 (80)
0.06
6,000
0.09 (32)
0.12 (55)
0.15 (80)
0.07
7,200
0.11 (32)
0.15 (55)
0.20 (80)
0.09
9,000
0.15 (32)
0.19 (55)
0.24 (80)
0.11
10,000
0.17 (32)
0.21 (55)
0.26 (80)
0.12
11,250
0.20 (32)
0.24 (55)
0.29 (80)
0.14
FIOP —
Factory-Installed Option
UNIT SIZE
50HJ
UNIT NOMINAL
TONS
CFM PER TON
300
400
500
015
12
.026
.045
.071
017
15
.040
.071
.111
025
20
.071
.126
.197