background image

18

START-UP

Use the following information and Start-Up Checklist on

page CL-1 to check out unit PRIOR to start-up.

Unit Preparation — 

Check that unit has been installed in

accordance with these installation instructions and all applica-
ble codes.

Compressor Mounting — 

Compressors are internally

spring mounted. Do not loosen or remove compressor hold-
down bolts.

Refrigerant Service Ports — 

Each refrigerant sys-

tem has a total of 3 Schrader-type service gage ports. One port
is located on the suction line, one on the compressor discharge
line, and one on the liquid line. In addition Schrader-type
valves are located underneath the low-pressure switches. Be
sure that caps on the ports are tight.

Compressor Rotation — 

It is important to be certain

the compressors are rotating in the proper direction. To deter-
mine whether or not compressors are rotating in the proper
direction:

1. Connect service gages to suction and discharge pressure

fittings.

2. Energize the compressor.
3. The suction pressure should drop and the discharge pres-

sure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pres-

sure does not rise to normal levels: 

1. Note that the evaporator fan is probably also rotating in

the wrong direction.

2. Turn off power to the unit.
3. Reverse any two of the incoming power leads.
4. Turn on power to the compressor.

The suction and discharge pressure levels should now move

to their normal start-up levels.
NOTE: When compressors are rotating in the wrong direction,
the unit will have increased noise levels and will not provide
heating and cooling.

After a few minutes of reverse operation, the scroll com-

pressor internal overload protection will open, which will acti-
vate the unit’s lockout and requires a manual reset. Reset is ac-
complished by turning the thermostat on and off.

Internal Wiring — 

Check all electrical connections in

unit control boxes; tighten as required.

Crankcase Heater(s) — 

Heater(s) is energized as long

as there is power to unit and compressor is not operating.

Evaporator Fan — 

Fan belt and variable pulleys are fac-

tory installed. Remove tape from the fan pulley. See Table 8 for
Air Quantity Limits. See Tables 9-12 for Fan Performance
data. Be sure that fans rotate in the proper direction. See
Tables 13 and 14 for Static Pressure information for accesso-
ries and options. See Table 15 for fan rpm at various fan motor
pulley settings. See Table 16 for Evaporator-Fan Motor Speci-
fications. To alter fan performance, see Evaporator-Fan Perfor-
mance Adjustment section, page 27.

Table 8 — Air Quantity Limits

Condenser Fans and Motors — 

Condenser fans and

motors are factory set. Refer to Condenser-Fan Adjustment
section (page 29) as required. Be sure that fans rotate in the
correct direction.

Return-Air Filters — 

Check that correct filters are in-

stalled in filter tracks. See Table 1. Do not operate unit without
return-air filters.

Outdoor-Air Inlet Screens — 

Outdoor-air inlet screens

must be in place before operating unit.

Accessory EconoMi$er Adjustment — 

Remove

filter access panel. Check that outdoor-air damper blades are
closed and return-air damper blades are open.

EconoMi$er operation and adjustment is described in Base

Unit Operation and EconoMi$er Adjustment sections (this
page and page 29), respectively.

Base Unit Operation

COOLING, UNITS WITHOUT ECONOMI$ER — When
thermostat calls for cooling, terminals G and Y1 are energized.
The indoor (evaporator) fan contactor (IFC), and compressor
contactor no. 1 (C1) are energized and evaporator-fan motor,
compressor no. 1 and condenser fans start. The condenser-fan
motors run continuously while unit is cooling. If the thermostat
calls for a second stage of cooling by energizing Y2, compres-
sor contactor no. 2 (C2) is energized and compressor no. 2
starts.
HEATING, UNITS WITHOUT ECONOMI$ER (If Acces-
sory or Optional Heater is Installed) — Upon a call for heat-
ing through terminal W1, IFC and heater contactor no. 1 (HC1)
are energized. On units equipped for 2 stages of heat, when ad-
ditional heat is needed, HC2 is energized through W2.
COOLING UNITS WITH ECONOMI$ER  — When  the
OAT is above the ECON SP set point and the room thermostat
calls for Stage 1 cooling (R to G + Y1), the indoor-fan motors
(IFM) is energized and the EconoMi$er damper modulates to
minimum position. The compressor contactor and OFC are
energized to start the compressor and outdoor-fan motor
(OFM). After the thermostat is satisfied, the damper modulates
to the fully closed position when the IFM is deenergized.

When the OAT is below the ECON SP setting and the room

thermostat calls for Stage 1 cooling (R to G + Y1), the
EconoMi$er modulates to the minimum position when the
IFM is energized. The EconoMi$er provides Stage 1 of cooling
by modulating the return and outdoor air dampers to maintain a
55 F supply air set point. If the supply-air temperature (SAT) is
greater than 57 F, the EconoMi$er modulates open, allowing a
greater amount of outdoor air to enter the unit. If the SAT drops
below 53 F, the outdoor air damper modulates closed to reduce
the amount of outdoor air. When the SAT is between 53 and
57 F, the EconoMi$er maintains its position.

If outdoor air alone cannot satisfy the cooling requirements

of the conditioned space, and the OAT is above the MECH
CLG LOCKOUT set point, the EconoMi$er integrates free
cooling with mechanical cooling. This is accomplished by the
strategies below.
NOTE: Compressors have a two-minute Minimum On and
Minimum Off, which are accomplished by the strategies
below.

1. If Y1 is energized, and the room thermostat calls for Y2

(2-stage thermostat), the compressor and OFC are ener-
gized. The position of the EconoMi$er damper is main-
tained at its current value.

2. If Y1 is energized for more than 20 minutes, and Y2 is

not energized (whether or not a 2-stage thermostat is
used), the compressor and OFC are energized. The posi-
tion of the EconoMi$er damper is maintained at its cur-
rent value.

IMPORTANT: Unit power must be on for 24 hours prior
to start-up. Otherwise, damage to compressor may result.

UNIT
50HJ

MINIMUM CFM

MAXIMUM CFM

015

3600

6,000

017

4500

7,500

025

6000

10,000

Summary of Contents for 50HJ015-025

Page 1: ...b or horizontal supply roof curb are shown in Fig 1 and 2 Install insulation cant strips roofing and counter flash ing as shown Ductwork can be secured to roof curb before unit is set in place Roof cu...

Page 2: ...oof curb accessory is shipped disassembled 2 Insulated panels 1 thick neoprene coated 1 1 2 lb density 3 Dimensions in are in millimeters 4 Direction of airflow 5 Roof curb 16 ga VA03 56 stl 6 A 90 de...

Page 3: ...orner post from packaging to protect coil from damage Use bumper boards for spreader bars 5 Weights do not include optional EconoMi er Add 80 lb 36 kg for EconoMi er weight 6 Weights given are for alu...

Page 4: ...moval This dimension can be reduced to 4 0 1219 if conditions permit coil removal from the top Left side 4 0 1219 for proper condenser coil airflow Front 4 0 1219 for control box access Right side 4 0...

Page 5: ...19 if conditions permit coil removal from the top Left side 4 0 1219 for proper condenser coil airflow Front 4 0 1219 for control box access Right side 4 0 1219 for proper operation of damper and powe...

Page 6: ...FAN Centrifugal Type Quantity Size in 2 10 x 10 2 12 x 12 2 12 x 12 Type Drive Belt Belt Belt Nominal Cfm 5200 6000 8000 Std Motor Hp 2 9 3 0 5 7 5 Opt Motor Hp 3 7 N A Motor Nominal Rpm 1725 1745 17...

Page 7: ...inside unit evaporator section for conden sate drain connection An 81 2 in x 3 4 in diameter nipple and a 2 in x 3 4 in diameter pipe nipple are coupled to standard 3 4 in diameter elbows to provide a...

Page 8: ...ure Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit in unit to low voltage connections as shown on unit label wiring diagram and in Fig 12 NOTE...

Page 9: ...8 8 42 56 117 135 165 155 175 175 460 414 508 10 70 10 62 3 0 5 0 8 3 7 4 8 30 35 2 3 6 0 32 40 15 18 30 35 2 3 6 0 15 18 32 40 32 39 55 60 2 3 6 0 32 39 58 60 55 66 72 80 2 3 6 0 55 66 75 80 017 208...

Page 10: ...FLA Table 3 Electric Resistance Heater Data Maximum number of stages using accessory low ambient kit or head pressure control device and low ambient kit NOTE Heaters are rated at 240 480 and 575 v FLA...

Page 11: ...FF position and close the door The handle should fit over the end of the shaft when the door is closed 8 The handle must be in the OFF position to open the con trol box door OPTIONAL CONVENIENCE OUTLE...

Page 12: ...SENSOR INSTALLA TION Perform the following procedure to install the out door air enthalpy sensor part no CROUTENT001A00 1 Remove the outdoor air temperature sensor cover See Fig 21 Save cover and scr...

Page 13: ...section of the unit The DAT is factory wired to the EconoMi er Control Module CO2 CONTROL SETUP If a CO2 sensor is not being used proceed to the next section If a CO2 sensor is being used perform the...

Page 14: ...conoMi er Switchover Control Strategy Must be selected manually Table 6 Changeover Set Points Field installed accessory Table 7 Default Potentiometer Settings ECONOMI ER SWITCHOVER STRATEGY SENSORS RE...

Page 15: ...nd Baffles Wind baffles must be field fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures See Fig 25 for baffle details Use 20 gage galvanized sheet metal or...

Page 16: ...tdoor fan motor no 1 with motor included in accessory kit Existing motor is not Motormaster III compatible Install Motormaster III Controls Only one Motormaster III control is required per unit Sensor...

Page 17: ...V Unit Shown LEGEND CB Circuit Breaker LLSV Liquid Line Solenoid Valve LPS Low Pressure Switch TB Terminal Block TRAN Transformer NOTES 1 All sensors are located on the eighth hairpin up from the bott...

Page 18: ...creens must be in place before operating unit Accessory EconoMi er Adjustment Remove filter access panel Check that outdoor air damper blades are closed and return air damper blades are open EconoMi e...

Page 19: ...coming off the evaporator coils and the liquid is further cooled to a temperature approach ing the evaporator coil leaving air temperature The state of the refrigerant leaving the subcooler coils is...

Page 20: ...20 Fig 29 MoistureMiser Operation Diagram...

Page 21: ...field supplied motor may affect wiring size Contact your Carrier representative for details 50HJ015 12 TONS Cfm Available External Static Pressure in wg 0 2 0 4 0 6 0 8 1 0 Rpm Watts Bhp Rpm Watts Bh...

Page 22: ...3 835 1248 1 44 932 1448 1 67 1024 1657 1 91 1111 1872 2 15 4500 761 1191 1 37 861 1389 1 60 954 1593 1 83 1043 1804 2 07 1127 2022 2 33 4750 792 1339 1 54 887 1541 1 77 977 1749 2 01 1063 1963 2 26 1...

Page 23: ...790 2088 2 45 860 2360 2 77 926 2638 3 09 988 2920 3 43 1048 3208 3 76 6600 821 2340 2 74 888 2621 3 07 952 2906 3 41 1013 3196 3 75 1070 3491 4 10 6900 852 2611 3 06 917 2900 3 40 979 3194 3 75 1038...

Page 24: ...36 1111 4747 5 63 1162 4978 5 91 8 500 999 4583 5 44 1053 4803 5 70 1105 5027 5 96 1155 5255 6 23 1204 5485 6 51 9 000 1052 5125 6 08 1103 5345 6 34 1152 5569 6 61 1200 5796 6 88 1247 6025 7 15 9 500...

Page 25: ...16 42 56 0 20 56 75 0 09 7 500 0 12 14 19 26 34 0 17 42 56 0 21 56 75 0 10 480 3 60 3 750 0 05 15 32 0 06 55 0 07 80 0 03 4 000 0 05 15 32 0 06 55 0 07 80 0 04 5 000 0 07 15 32 0 08 55 0 10 80 0 05 6...

Page 26: ...178 1156 1134 1112 1091 1069 1047 1025 025 1151 1132 1114 1095 1077 1058 1040 1021 1002 025 1369 1347 1325 1303 1281 1259 1237 1215 1193 UNIT 50HJ NOMINAL HP VOLTAGE MAX WATTS EFF MAX BHP MAX BkW MAX...

Page 27: ...nt Fig 30 32 Fan motor pulleys are factory set for speed shown in Table 1 To change fan speeds 1 Shut off unit power supply 2 a Size 015 Only Loosen belt by loosening fan motor mounting plate nuts b S...

Page 28: ...st belt tension 1 Loosen fan motor bolts 2 Adjust belt tension a Size 015 Units Move motor mounting plate up or down for proper belt tension 1 2 in deflection with one finger a Size 017 025 Units Turn...

Page 29: ...ancels the automatic test procedure If the EconoMi er controller recognized a non critical sensor fault and flashed a code i e FLASH 6 outdoor air humidity sensor fault the FLASH CODE will be cleared...

Page 30: ...d on the unit to measure liquid pressure entering the subcooler leaving the condenser Filter Drier Replace whenever refrigerant system is ex posed to atmosphere Protective Devices COMPRESSOR PROTECTIO...

Page 31: ...ckout COMP Compressor Motor CR Control Relay DAT Discharge Air Thermistor DM Damper Motor DU Dummy Terminal EC Enthalpy Control EQUIP Equipment FL Fuse Link FPT Freeze Protection Thermostat FU Fuse GN...

Page 32: ...32 Fig 36 Typical Wiring Schematic 50HJ017 460v Shown...

Page 33: ...33 Fig 36 Typical Wiring Schematic 50HJ017 460v Shown cont Fig 37 Typical Component Arrangement 50HJ017 Shown...

Page 34: ...place Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Ther...

Page 35: ...MIN POS to 100 to verify operation and then set to correct setting EconoMi er Changeover Set Point Set Too High or Too Low Set at correct value See Table 6 Discharge Air Thermistor Faulty If STATUS li...

Page 36: ......

Page 37: ......

Page 38: ...ue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 535 00025 Printed in U S A Form 50HJ 19SI Pg 38 3 01 Replaces 50HJ 16SI Book 1 4 T...

Page 39: ......

Page 40: ...HECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND VERIFY SET SCREW IS TIGHT VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED VERIFY THAT SCROLL COMPRESSORS ARE ROTAT...

Reviews: