Table 12 — Fan Performance — 50HJ025

LEGEND

*Standard low-medium static drive range is 1002 to 1151 rpm. Alter-

nate high-static drive range is 1193 to 1369. Other rpms require a
field-supplied drive.

NOTES:

1. Maximum continuous bhp for the standard motor is 9.47 (for

208 and 575-v units) and 10.33 (for 230 and 460-v units). The
maximum continuous watts is 7915 (for 208 and 575-v units)
and 8640 (for 230 and 460-v units). Do not adjust motor rpm
such that motor maximum bhp and/or watts is exceeded at the
maximum operating cfm.

2. Static pressure losses (i.e., EconoMi$er) must be added to

external static pressure before entering Fan Performance table.

3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and

casing losses. See Table 13 for accessory/FIOP static pressure
information.

5. Extensive motor and drive testing on these units ensures that

the full bhp and watts range of the motor can be utilized with
confidence. Using your fan motors up to the watts or bhp rating
shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected.

6. Use of a field-supplied motor may affect wiring size. Contact

your Carrier representative for details.

50HJ025 (20 TONS)*

Cfm

Available External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6,000

753

2385

2.83

816

2579

3.06

884

2807

3.33

949

3040

3.61

1010

3277

3.89

6,500

793

2738

3.25

861

2959

3.51

925

3186

3.78

987

3418

4.05

1045

3653

4.33

7,000

844

3151

3.74

908

3372

4.00

968

3598

4.27

1026

3828

4.54

1082

4062

4.82

7,500

895

3596

4.27

955

3817

4.53

1013

4042

4.80

1068

4271

5.07

1121

4504

5.34

8,000

947

4073

4.83

1004

4294

5.09

1058

4518

5.36

1111

4747

5.63

1162

4978

5.91

8,500

999

4583

5.44

1053

4803

5.70

1105

5027

5.96

1155

5255

6.23

1204

5485

6.51

9,000

1052

5125

6.08

1103

5345

6.34

1152

5569

6.61

1200

5796

6.88

1247

6025

7.15

9,500

1105

5699

6.76

1153

5919

7.02

1200

6142

7.29

1246

6369

7.56

1291

6598

7.83

10,000

1158

6306

7.48

1204

6526

7.74

1249

6750

8.01

1293

6975

8.27

1336

7203

8.55

50HJ025 (20 TONS) (cont)*

Cfm

Available External Static Pressure (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6,000

1069

3517

4.17

1125

3761

4.46

1180

4006

4.75

1232

4255

5.05

1283

4506

5.35

6,500

1102

3891

4.62

1156

4132

4.90

1208

4377

5.19

1259

4623

5.48

1308

4871

5.78

7,000

1136

4299

5.10

1188

4538

5.38

1239

4780

5.67

1288

5025

5.96

1335

5271

6.25

7,500

1173

4739

5.62

1223

4977

5.90

1272

5217

6.19

1319

5460

6.48

1365

5705

6.77

8,000

1211

5212

6.18

1259

5449

6.46

1306

5688

6.75

1352

5929

7.03

1396

6172

7.32

8,500

1251

5718

6.78

1297

5954

7.06

1342

6192

7.35

1386

6431

7.63

1429

6673

7.92

9,000

1292

6257

7.42

1337

6492

7.70

1380

6729

7.98

1423

6967

8.27

1464

7207

8.55

9,500

1335

6830

8.10

1377

7063

8.38

1419

7299

8.66

1460

7536

8.94

1501

7776

9.22

10,000

1378

7434

8.82

1419

7667

9.10

1460

7902

9.37

1499

8138

9.65

1538

8377

9.94

50HJ025 (20 TONS) (cont)*

Cfm

Available External Static Pressure (in. wg)

2.2

2.4

2.6

2.8

3.0

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6,000

1332

4750

5.65

1380

5015

5.95

1427

5272

6.25

1472

5531

6.56

1517

5793

6.87

6,500

1356

5122

6.08

1402

5375

6.38

1447

5630

6.68

1492

5886

6.98

1535

6144

7.29

7,000

1381

5519

6.55

1427

5770

6.84

1471

6022

7.14

1514

6276

7.45

7,500

1409

5951

7.06

1453

6199

7.35

1496

6449

7.65

1538

6701

7.95

8,000

1440

6417

7.61

1482

6663

7.90

1523

6911

8.20

8,500

1471

6916

8.20

1513

7161

8.49

9,000

1505

7449

8.84

1545

7693

9.13

9,500

1540

8016

9.51

10,000

Bhp

Brake Horsepower

FIOP

Factory-Installed Option

Watts —

Input Watts to Motor

Summary of Contents for 50HJ015-025

Page 1: ...b or horizontal supply roof curb are shown in Fig 1 and 2 Install insulation cant strips roofing and counter flash ing as shown Ductwork can be secured to roof curb before unit is set in place Roof cu...

Page 2: ...oof curb accessory is shipped disassembled 2 Insulated panels 1 thick neoprene coated 1 1 2 lb density 3 Dimensions in are in millimeters 4 Direction of airflow 5 Roof curb 16 ga VA03 56 stl 6 A 90 de...

Page 3: ...orner post from packaging to protect coil from damage Use bumper boards for spreader bars 5 Weights do not include optional EconoMi er Add 80 lb 36 kg for EconoMi er weight 6 Weights given are for alu...

Page 4: ...moval This dimension can be reduced to 4 0 1219 if conditions permit coil removal from the top Left side 4 0 1219 for proper condenser coil airflow Front 4 0 1219 for control box access Right side 4 0...

Page 5: ...19 if conditions permit coil removal from the top Left side 4 0 1219 for proper condenser coil airflow Front 4 0 1219 for control box access Right side 4 0 1219 for proper operation of damper and powe...

Page 6: ...FAN Centrifugal Type Quantity Size in 2 10 x 10 2 12 x 12 2 12 x 12 Type Drive Belt Belt Belt Nominal Cfm 5200 6000 8000 Std Motor Hp 2 9 3 0 5 7 5 Opt Motor Hp 3 7 N A Motor Nominal Rpm 1725 1745 17...

Page 7: ...inside unit evaporator section for conden sate drain connection An 81 2 in x 3 4 in diameter nipple and a 2 in x 3 4 in diameter pipe nipple are coupled to standard 3 4 in diameter elbows to provide a...

Page 8: ...ure Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit in unit to low voltage connections as shown on unit label wiring diagram and in Fig 12 NOTE...

Page 9: ...8 8 42 56 117 135 165 155 175 175 460 414 508 10 70 10 62 3 0 5 0 8 3 7 4 8 30 35 2 3 6 0 32 40 15 18 30 35 2 3 6 0 15 18 32 40 32 39 55 60 2 3 6 0 32 39 58 60 55 66 72 80 2 3 6 0 55 66 75 80 017 208...

Page 10: ...FLA Table 3 Electric Resistance Heater Data Maximum number of stages using accessory low ambient kit or head pressure control device and low ambient kit NOTE Heaters are rated at 240 480 and 575 v FLA...

Page 11: ...FF position and close the door The handle should fit over the end of the shaft when the door is closed 8 The handle must be in the OFF position to open the con trol box door OPTIONAL CONVENIENCE OUTLE...

Page 12: ...SENSOR INSTALLA TION Perform the following procedure to install the out door air enthalpy sensor part no CROUTENT001A00 1 Remove the outdoor air temperature sensor cover See Fig 21 Save cover and scr...

Page 13: ...section of the unit The DAT is factory wired to the EconoMi er Control Module CO2 CONTROL SETUP If a CO2 sensor is not being used proceed to the next section If a CO2 sensor is being used perform the...

Page 14: ...conoMi er Switchover Control Strategy Must be selected manually Table 6 Changeover Set Points Field installed accessory Table 7 Default Potentiometer Settings ECONOMI ER SWITCHOVER STRATEGY SENSORS RE...

Page 15: ...nd Baffles Wind baffles must be field fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures See Fig 25 for baffle details Use 20 gage galvanized sheet metal or...

Page 16: ...tdoor fan motor no 1 with motor included in accessory kit Existing motor is not Motormaster III compatible Install Motormaster III Controls Only one Motormaster III control is required per unit Sensor...

Page 17: ...V Unit Shown LEGEND CB Circuit Breaker LLSV Liquid Line Solenoid Valve LPS Low Pressure Switch TB Terminal Block TRAN Transformer NOTES 1 All sensors are located on the eighth hairpin up from the bott...

Page 18: ...creens must be in place before operating unit Accessory EconoMi er Adjustment Remove filter access panel Check that outdoor air damper blades are closed and return air damper blades are open EconoMi e...

Page 19: ...coming off the evaporator coils and the liquid is further cooled to a temperature approach ing the evaporator coil leaving air temperature The state of the refrigerant leaving the subcooler coils is...

Page 20: ...20 Fig 29 MoistureMiser Operation Diagram...

Page 21: ...field supplied motor may affect wiring size Contact your Carrier representative for details 50HJ015 12 TONS Cfm Available External Static Pressure in wg 0 2 0 4 0 6 0 8 1 0 Rpm Watts Bhp Rpm Watts Bh...

Page 22: ...3 835 1248 1 44 932 1448 1 67 1024 1657 1 91 1111 1872 2 15 4500 761 1191 1 37 861 1389 1 60 954 1593 1 83 1043 1804 2 07 1127 2022 2 33 4750 792 1339 1 54 887 1541 1 77 977 1749 2 01 1063 1963 2 26 1...

Page 23: ...790 2088 2 45 860 2360 2 77 926 2638 3 09 988 2920 3 43 1048 3208 3 76 6600 821 2340 2 74 888 2621 3 07 952 2906 3 41 1013 3196 3 75 1070 3491 4 10 6900 852 2611 3 06 917 2900 3 40 979 3194 3 75 1038...

Page 24: ...36 1111 4747 5 63 1162 4978 5 91 8 500 999 4583 5 44 1053 4803 5 70 1105 5027 5 96 1155 5255 6 23 1204 5485 6 51 9 000 1052 5125 6 08 1103 5345 6 34 1152 5569 6 61 1200 5796 6 88 1247 6025 7 15 9 500...

Page 25: ...16 42 56 0 20 56 75 0 09 7 500 0 12 14 19 26 34 0 17 42 56 0 21 56 75 0 10 480 3 60 3 750 0 05 15 32 0 06 55 0 07 80 0 03 4 000 0 05 15 32 0 06 55 0 07 80 0 04 5 000 0 07 15 32 0 08 55 0 10 80 0 05 6...

Page 26: ...178 1156 1134 1112 1091 1069 1047 1025 025 1151 1132 1114 1095 1077 1058 1040 1021 1002 025 1369 1347 1325 1303 1281 1259 1237 1215 1193 UNIT 50HJ NOMINAL HP VOLTAGE MAX WATTS EFF MAX BHP MAX BkW MAX...

Page 27: ...nt Fig 30 32 Fan motor pulleys are factory set for speed shown in Table 1 To change fan speeds 1 Shut off unit power supply 2 a Size 015 Only Loosen belt by loosening fan motor mounting plate nuts b S...

Page 28: ...st belt tension 1 Loosen fan motor bolts 2 Adjust belt tension a Size 015 Units Move motor mounting plate up or down for proper belt tension 1 2 in deflection with one finger a Size 017 025 Units Turn...

Page 29: ...ancels the automatic test procedure If the EconoMi er controller recognized a non critical sensor fault and flashed a code i e FLASH 6 outdoor air humidity sensor fault the FLASH CODE will be cleared...

Page 30: ...d on the unit to measure liquid pressure entering the subcooler leaving the condenser Filter Drier Replace whenever refrigerant system is ex posed to atmosphere Protective Devices COMPRESSOR PROTECTIO...

Page 31: ...ckout COMP Compressor Motor CR Control Relay DAT Discharge Air Thermistor DM Damper Motor DU Dummy Terminal EC Enthalpy Control EQUIP Equipment FL Fuse Link FPT Freeze Protection Thermostat FU Fuse GN...

Page 32: ...32 Fig 36 Typical Wiring Schematic 50HJ017 460v Shown...

Page 33: ...33 Fig 36 Typical Wiring Schematic 50HJ017 460v Shown cont Fig 37 Typical Component Arrangement 50HJ017 Shown...

Page 34: ...place Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Ther...

Page 35: ...MIN POS to 100 to verify operation and then set to correct setting EconoMi er Changeover Set Point Set Too High or Too Low Set at correct value See Table 6 Discharge Air Thermistor Faulty If STATUS li...

Page 36: ......

Page 37: ......

Page 38: ...ue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 535 00025 Printed in U S A Form 50HJ 19SI Pg 38 3 01 Replaces 50HJ 16SI Book 1 4 T...

Page 39: ......

Page 40: ...HECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND VERIFY SET SCREW IS TIGHT VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED VERIFY THAT SCROLL COMPRESSORS ARE ROTAT...

Reviews: