background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

PC 111

Catalog No. 535-00025

Printed in U.S.A.

Form 50HJ-19SI

Pg 1

3-01

Replaces: 50HJ-16SI

Book 1

4

Tab

1b 6b

Installation, Start-Up and

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1-17

Step 1 — Provide Unit Support

. . . . . . . . . . . . . . . . . . . 1

• ROOF  CURB
• ALTERNATE UNIT SUPPORT

Step 2 — Rig and Place Unit

 . . . . . . . . . . . . . . . . . . . . . 1

• POSITIONING
• ROOF MOUNT

Step 3 — Field Fabricate Ductwork

. . . . . . . . . . . . . . . 7

Step 4 — Make Unit Duct Connections

 . . . . . . . . . . . 7

Step 5 — Trap Condensate Drain

. . . . . . . . . . . . . . . . . 7

Step 6 — Make Electrical Connections

 . . . . . . . . . . . 8

• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• OPTIONAL NON-FUSED DISCONNECT
• OPTIONAL CONVENIENCE OUTLET

Step 7 — Make Outdoor-Air Inlet
Adjustments

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

•  MANUAL OUTDOOR-AIR DAMPER
• OPTIONAL ECONOMI$ER

Step 8 — Install Outdoor-Air Hood

 . . . . . . . . . . . . . . 12

Step 9 — Install All Accessories

. . . . . . . . . . . . . . . . . 15

• MOTORMASTER® I CONTROL INSTALLATION
• MOTORMASTER III CONTROL INSTALLATION

Step 10 — Install Humidistat for Optional
MositureMiser Dehumidification Package

 . . . . . . . 16

START-UP

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  18-26

SERVICE

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  27-33

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . .34,35

START-UP CHECKLIST

 . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can

be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should in-
stall, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func-

tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.     

INSTALLATION

Step 1 — Provide Unit Support

ROOF CURB — Assemble and install accessory roof curb or
horizontal supply roof curb in accordance with instructions
shipped with the accessory. Accessory roof curb and horizontal
supply roof curb and information required to field fabricate a
roof curb or horizontal supply roof curb are shown in Fig. 1
and 2. Install insulation, cant strips, roofing, and counter flash-
ing as shown. Ductwork can be secured to roof curb before unit
is set in place.

Roof curb must be level. This is necessary to permit unit

drain to function properly. Unit leveling tolerance is 

±

 

1

/

16

 in.

per linear ft in any direction. Refer to Accessory Roof Curb or
Horizontal Supply Roof Curb Installation Instructions for addi-
tional information as required.
ALTERNATE UNIT SUPPORT — When the curb or adapter
cannot be used, support unit with sleepers using unit curb or
adapter support area. If sleepers cannot be used, support long
sides of unit with a minimum of 3 equally spaced 4-in. x 4-in.
pads on each side.

Step 2 — Rig and Place Unit — 

Inspect unit for

transportation damage. File any claim with transportation
agency. Keep unit upright, and do not drop. Use spreader bars
over unit to prevent sling or cable damage. Rollers may be used
to move unit across a roof. Level by using unit frame as a refer-
ence; leveling tolerance is ± 

1

/

16

 in. per linear ft in any direc-

tion. See Fig. 3 for additional information. Unit weight is
shown in Table 1.

Four lifting holes are provided in ends of unit base rails as

shown in Fig. 3. Refer to rigging instructions on unit.
POSITIONING — Provide clearance around and above unit
for airflow, safety, and service access (Fig. 4 and 5).

Do not install unit in an indoor location. Do not locate air in-

lets near exhaust vents or other sources of contaminated air.

Although unit is weatherproof, guard against water from

higher level runoff and overhangs.
ROOF MOUNT — Check building codes for weight distribu-
tion requirements.

Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.

IMPORTANT: Units have high ambient operating lim-
its. If limits are exceeded, the unit will automatically
lock the compressor out of operation. Manual reset will
be required to restart the compressor.

IMPORTANT: The gasketing of the unit to the roof curb
or horizontal supply roof curb is critical for a leakproof
seal. Install gasket supplied with the roof curb or hori-
zontal supply roof curb as shown in Fig. 1. Improperly
applied gasket can result in air leaks and poor unit
performance.

50HJ015-025

Single-Package Rooftop Units

Electric Cooling with Electric Heat Option

Summary of Contents for 50HJ015-025

Page 1: ...b or horizontal supply roof curb are shown in Fig 1 and 2 Install insulation cant strips roofing and counter flash ing as shown Ductwork can be secured to roof curb before unit is set in place Roof cu...

Page 2: ...oof curb accessory is shipped disassembled 2 Insulated panels 1 thick neoprene coated 1 1 2 lb density 3 Dimensions in are in millimeters 4 Direction of airflow 5 Roof curb 16 ga VA03 56 stl 6 A 90 de...

Page 3: ...orner post from packaging to protect coil from damage Use bumper boards for spreader bars 5 Weights do not include optional EconoMi er Add 80 lb 36 kg for EconoMi er weight 6 Weights given are for alu...

Page 4: ...moval This dimension can be reduced to 4 0 1219 if conditions permit coil removal from the top Left side 4 0 1219 for proper condenser coil airflow Front 4 0 1219 for control box access Right side 4 0...

Page 5: ...19 if conditions permit coil removal from the top Left side 4 0 1219 for proper condenser coil airflow Front 4 0 1219 for control box access Right side 4 0 1219 for proper operation of damper and powe...

Page 6: ...FAN Centrifugal Type Quantity Size in 2 10 x 10 2 12 x 12 2 12 x 12 Type Drive Belt Belt Belt Nominal Cfm 5200 6000 8000 Std Motor Hp 2 9 3 0 5 7 5 Opt Motor Hp 3 7 N A Motor Nominal Rpm 1725 1745 17...

Page 7: ...inside unit evaporator section for conden sate drain connection An 81 2 in x 3 4 in diameter nipple and a 2 in x 3 4 in diameter pipe nipple are coupled to standard 3 4 in diameter elbows to provide a...

Page 8: ...ure Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit in unit to low voltage connections as shown on unit label wiring diagram and in Fig 12 NOTE...

Page 9: ...8 8 42 56 117 135 165 155 175 175 460 414 508 10 70 10 62 3 0 5 0 8 3 7 4 8 30 35 2 3 6 0 32 40 15 18 30 35 2 3 6 0 15 18 32 40 32 39 55 60 2 3 6 0 32 39 58 60 55 66 72 80 2 3 6 0 55 66 75 80 017 208...

Page 10: ...FLA Table 3 Electric Resistance Heater Data Maximum number of stages using accessory low ambient kit or head pressure control device and low ambient kit NOTE Heaters are rated at 240 480 and 575 v FLA...

Page 11: ...FF position and close the door The handle should fit over the end of the shaft when the door is closed 8 The handle must be in the OFF position to open the con trol box door OPTIONAL CONVENIENCE OUTLE...

Page 12: ...SENSOR INSTALLA TION Perform the following procedure to install the out door air enthalpy sensor part no CROUTENT001A00 1 Remove the outdoor air temperature sensor cover See Fig 21 Save cover and scr...

Page 13: ...section of the unit The DAT is factory wired to the EconoMi er Control Module CO2 CONTROL SETUP If a CO2 sensor is not being used proceed to the next section If a CO2 sensor is being used perform the...

Page 14: ...conoMi er Switchover Control Strategy Must be selected manually Table 6 Changeover Set Points Field installed accessory Table 7 Default Potentiometer Settings ECONOMI ER SWITCHOVER STRATEGY SENSORS RE...

Page 15: ...nd Baffles Wind baffles must be field fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures See Fig 25 for baffle details Use 20 gage galvanized sheet metal or...

Page 16: ...tdoor fan motor no 1 with motor included in accessory kit Existing motor is not Motormaster III compatible Install Motormaster III Controls Only one Motormaster III control is required per unit Sensor...

Page 17: ...V Unit Shown LEGEND CB Circuit Breaker LLSV Liquid Line Solenoid Valve LPS Low Pressure Switch TB Terminal Block TRAN Transformer NOTES 1 All sensors are located on the eighth hairpin up from the bott...

Page 18: ...creens must be in place before operating unit Accessory EconoMi er Adjustment Remove filter access panel Check that outdoor air damper blades are closed and return air damper blades are open EconoMi e...

Page 19: ...coming off the evaporator coils and the liquid is further cooled to a temperature approach ing the evaporator coil leaving air temperature The state of the refrigerant leaving the subcooler coils is...

Page 20: ...20 Fig 29 MoistureMiser Operation Diagram...

Page 21: ...field supplied motor may affect wiring size Contact your Carrier representative for details 50HJ015 12 TONS Cfm Available External Static Pressure in wg 0 2 0 4 0 6 0 8 1 0 Rpm Watts Bhp Rpm Watts Bh...

Page 22: ...3 835 1248 1 44 932 1448 1 67 1024 1657 1 91 1111 1872 2 15 4500 761 1191 1 37 861 1389 1 60 954 1593 1 83 1043 1804 2 07 1127 2022 2 33 4750 792 1339 1 54 887 1541 1 77 977 1749 2 01 1063 1963 2 26 1...

Page 23: ...790 2088 2 45 860 2360 2 77 926 2638 3 09 988 2920 3 43 1048 3208 3 76 6600 821 2340 2 74 888 2621 3 07 952 2906 3 41 1013 3196 3 75 1070 3491 4 10 6900 852 2611 3 06 917 2900 3 40 979 3194 3 75 1038...

Page 24: ...36 1111 4747 5 63 1162 4978 5 91 8 500 999 4583 5 44 1053 4803 5 70 1105 5027 5 96 1155 5255 6 23 1204 5485 6 51 9 000 1052 5125 6 08 1103 5345 6 34 1152 5569 6 61 1200 5796 6 88 1247 6025 7 15 9 500...

Page 25: ...16 42 56 0 20 56 75 0 09 7 500 0 12 14 19 26 34 0 17 42 56 0 21 56 75 0 10 480 3 60 3 750 0 05 15 32 0 06 55 0 07 80 0 03 4 000 0 05 15 32 0 06 55 0 07 80 0 04 5 000 0 07 15 32 0 08 55 0 10 80 0 05 6...

Page 26: ...178 1156 1134 1112 1091 1069 1047 1025 025 1151 1132 1114 1095 1077 1058 1040 1021 1002 025 1369 1347 1325 1303 1281 1259 1237 1215 1193 UNIT 50HJ NOMINAL HP VOLTAGE MAX WATTS EFF MAX BHP MAX BkW MAX...

Page 27: ...nt Fig 30 32 Fan motor pulleys are factory set for speed shown in Table 1 To change fan speeds 1 Shut off unit power supply 2 a Size 015 Only Loosen belt by loosening fan motor mounting plate nuts b S...

Page 28: ...st belt tension 1 Loosen fan motor bolts 2 Adjust belt tension a Size 015 Units Move motor mounting plate up or down for proper belt tension 1 2 in deflection with one finger a Size 017 025 Units Turn...

Page 29: ...ancels the automatic test procedure If the EconoMi er controller recognized a non critical sensor fault and flashed a code i e FLASH 6 outdoor air humidity sensor fault the FLASH CODE will be cleared...

Page 30: ...d on the unit to measure liquid pressure entering the subcooler leaving the condenser Filter Drier Replace whenever refrigerant system is ex posed to atmosphere Protective Devices COMPRESSOR PROTECTIO...

Page 31: ...ckout COMP Compressor Motor CR Control Relay DAT Discharge Air Thermistor DM Damper Motor DU Dummy Terminal EC Enthalpy Control EQUIP Equipment FL Fuse Link FPT Freeze Protection Thermostat FU Fuse GN...

Page 32: ...32 Fig 36 Typical Wiring Schematic 50HJ017 460v Shown...

Page 33: ...33 Fig 36 Typical Wiring Schematic 50HJ017 460v Shown cont Fig 37 Typical Component Arrangement 50HJ017 Shown...

Page 34: ...place Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Ther...

Page 35: ...MIN POS to 100 to verify operation and then set to correct setting EconoMi er Changeover Set Point Set Too High or Too Low Set at correct value See Table 6 Discharge Air Thermistor Faulty If STATUS li...

Page 36: ......

Page 37: ......

Page 38: ...ue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 535 00025 Printed in U S A Form 50HJ 19SI Pg 38 3 01 Replaces 50HJ 16SI Book 1 4 T...

Page 39: ......

Page 40: ...HECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND VERIFY SET SCREW IS TIGHT VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED VERIFY THAT SCROLL COMPRESSORS ARE ROTAT...

Reviews: