4
Horizontal package air conditionners
3. T
ECHNICAL CHARACTERISTICS
(EN-14511-2013)
50HB/HF
55
65
80
90
120
160
Cooling
capacities
Cooling capacity
(kW)
12,5
15,3
20,1
21,5
27,1
35,9
Power input
(kW)
5,2
6,6
7,4
8,5
11,0
15,4
EER performance
2,38
2,30
2,70
2,53
2,47
2,33
Heating
capacity
Heating capacity
(kW)
14,2
16,9
21,1
23,1
30,5
41,0
Power input
(kW)
4,8
5,7
6,4
7,4
9,3
13,3
COP performance
2,93
2,96
3,29
3,13
3,28
3,10
Outdoor
circuit
fan
Nominal air
fl
ow (m
3
/h)
4.100
4.600
6.500
7.000
10.000
12.200
Available static pressure (mm.w.c)
9
9
10
10
12
12
Type
Centrifugal
Number
1
Motor output (kW)
1,1
1,5
1,5
2,2
2,2
3,0
Power input (kW)
0,77
1,01
1,14
1,33
1,37
2,03
Speed (r.p.m.)
1.125
1.207
828
859
589
630
Indoor
circuit
fan
Nominal air
fl
ow (m
3
/h)
2.500
3.100
4.000
4.600
6.000
7.000
Available static pressure (mm.w.c)
5,0
5,0
6,2
6,2
6,2
7,5
Type
Centrifugal
Number
1
Motor output (kW)
0,55
1,1
1,1
1,5
1,5
3,0
Power input (kW)
0,35
0,63
0,67
0,94
1,20
1,94
Speed (r.p.m.)
1.115
1.340
1.051
1.150
988
1.168
Compressor
Type
Scroll
Compresor number
1
Circuit number
1
Oil type
Copeland 3MAF 32cST, Danfoss POE 160SZ, ICI Emkarate RL 32CF, Mobil EAL Artic 22CC
Voulme of oil (l)
1,6
1,6
1,6
3,0
3,3
3,3
Electrical
characteristics
Electrical power supply
400 V / III ph / 50 Hz (±10%)
Power supply
3 Wires + Ground
Maximum
absorbed
current
Compressor (A)
15,0
19,0
19,0
22,0
29,0
35,0
Outdoor fan (A)
2,7
3,6
3,6
5,0
5,0
6,9
Indoor fan (A)
1,6
2,7
2,7
3,6
3,6
6,9
Control (A)
2,0
2,0
2,0
2,0
2,0
2,0
Total (A)
21,3
27,3
27,3
32,6
39,6
50,8
Refrigerant
Type
R-410A
Global warming potential (GWP)
2.088
Charge (kg)
2,5
3,0
4,5
4,9
5,0
6,2
Environment impact (t CO2e)
5,2
6,3
9,4
10,2
10,4
12,9
Dimensions
Length (mm)
1.420
1.420
1.760
1.760
2.300
2.300
Width (mm)
1.065
1.065
1.414
1.414
1.820
1.820
Height (mm)
576
576
701
701
824
824
Weight
(kg)
245
253
332
375
472
521
Ø Condensate evacuation
3/4”
Cooling capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 27ºC, 50% RH and 35ºC outdoor temperature.
Heating capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 20ºC and 6ºC WB outdoor temperature.
Total power input by compressor and motorised fans under nominal conditions calculated in accordance with the EN-14511-2013.
Climatic warming potential of a kilogram of
fl
uorinated greenhouse gas in relation to a kilogram of carbon dioxide over a period of 100 years.
Summary of Contents for 50HB