![Carrier 50HB Manual Download Page 3](http://html.mh-extra.com/html/carrier/50hb/50hb_manual_2561577003.webp)
3
Horizontal package air conditionners
1. I
NTRODUCTION
The
50HF/HB
heat pumps and cooling unit are packages air to air
units, of horizontal compact construction, made for operation indoors.
They are equipped with centrifugal fans, air coils, scroll compressor
and electronic control with microprocessor, optimized components for
the R-410A refrigerant.
Are appropriate for air conditioning applications in medium power in
of
fi
ces, commercial and industrial spaces where the facade aesthetics
must be preserved.
•
50HF Series:
Air to air
cooling
autonomous units.
•
50HB Series: Reversible
air to air
heat pump
autonomous units.
The units comply with European Directives: Machinery 2006/42/EC -
EMC 2014/30/EU - LVD 2014/35/EU - PED 2014/68/EC (Category 2)
- RoHS 2011/65/EU - Eco-design 2009/125/CE - Eco-labelling 2010/30/
EU; and with Harmonised Standard: EN 378-2:2012.
After manufacturing, all units are charged with refrigerant and
are tested at the factory, verifying the correct operation of all their
components within the operating range for which they are intended.
Those in charge of the installation, commissioning, operation and
maintenance of the unit must know the instructions contained in this
brochure and the speci
fi
c technical characteristics of the installation site.
2. O
PERATION LIMITS
With control of operation condensation pressure up to -10ºC.
When the outdoor temperature usually reaches less than 5ºC WB
it is recommended installing a support element.
Conditions
air inlet
Cooling
Heating
Indoor coil
Minimum
14 ºC WB
10 ºC
Maximum
22 ºC WB
27 ºC
Outdoor
coil
Minimum
12 ºC
-6 ºC BH
Maximum
48 ºC
15 ºC WB
Summary of Contents for 50HB