22
7 - POSITIONING AND INSTALLATION
7.6 - Recommended service clearance
Important: This is the
minimum
space required for maintenance operations and access inside the unit. Depending on the assembly
selected for the unit and the characteristics of the installation site, a larger space around it may be required to ensure proper air
circulation and therefore the correct operation of the unit.
Unit not designed to have overhead obstruction.
50FF/FC - 180 to 280
50FF/FC
Overall dimensions
(mm)
Service clearance
(mm)
Length Width Height
A
B
C
D
180 to 220
5.300 2.257 2.421 2.600 2.500 1.200 1.000
250 to 280
6.350 2.257 2.494 3.000 2.500 1.200 1.000
50FF/FC
Overall dimensions
(mm)
Service clearance
(mm)
Length Width Height
A
B
C
D
180 to 220
5.300 2.257 2.555 2.600 2.500 1.200 1.000
250 to 280
6.350 2.257 2.555 3.000 2.500 1.200 1.000
50FF/FC
Overall dimensions
(mm)
Service clearance
(mm)
Length Width Height
A
B
C
D
180 to 220
5.300 3.112 2.555 2.600 1.700 1.200 1.000
250 to 280
6.350 3.112 2.555 3.000 2.500 1.200 1.000
50FF/FC
Overall dimensions
(mm)
Service clearance
(mm)
Length Width Height
A
B
C
D
180 to 220
5.306 2.268 2.555 2.600 2.500 1.200 1.000
250 to 280
6.356 2.268 2.555 3.000 2.500 1.200 1.000
B1 and B2 assemblies
BW assembly
BP and BA assemblies
BT and BB assemblies
A
B
C
D
A
B
C
D
A
B
C
D
A
B
D
C