7 - POSITIONING AND INSTALLATION
7.6 - Recommended service clearance
Important: This is the
minimum
space required for maintenance operations and access inside the unit. Depending on the assembly
selected for the unit and the characteristics of the installation site, a larger space around it may be required to ensure proper air
circulation and therefore the correct operation of the unit.
A
B
C
D
A
B
C
D
NOTE:
-
Unit not designed to have overhead obstruction.
A
B
C
D
A
B
C
D
50FF/FC 052-058-062-070-074-086-093-099: B1, B2 and BF assemblies
50FF/FC 052-058-062-070-074-086-093-099: BW assembly
50FF/FC 052-058-062-070-074-086-093-099: B3, BX, BP and BA assemblies
50FF/FC 052-058-062-070-074-086-093-099: BT and BB assemblies
50FF/FC
Overall dimension (mm)
Service clearance (mm)
Length Width Height
A
B
C
D
052 to 062
3.000
2.200
1.230 1.600 1.000 1.000 1.000
070 to 099
3.650
2.200
1.230 2.000 1.000 1.000 1.000
50FF/FC
Overall dimension (mm)
Service clearance (mm)
Length Width Height
A
B
C
D
052 to 062
3.000
2.205
1.905 1.600 1.000 1.000 1.000
070 to 099
3.655
2.205
1.905 2.000 1.000 1.000 1.000
50FF/FC
Overall dimension (mm)
Service clearance (mm)
Length Width Height
A
B
C
D
052 to 062
3.000
2.210
1.995 1.600 1.000 1.000 1.000
070 to 099
3.655
2.210
1.995 2.000 1.000 1.000 1.000
50FF/FC
Overall dimension (mm)
Service clearance (mm)
Length Width Height
A
B
C
D
052 to 062
3.000
3.015
1.905 1.600 1.000 1.000 1.000
070 to 099
3.655
3.015
1.905 2.000 1.000 1.000 1000