Controls Configuration and Calibration —

Be-

fore installing the transducers into the compressors, the con-
trols must be reconfigured and the transducers calibrated.
Proceed as follows:
1. Reconnect power to the rooftop unit.
2. Turn on the unit control circuit breaker (CCB).
3. Turn the ON/OFF switch located on the fuse/circuit breaker

bracket to the ON position.

4. Use the accessory HSIO keypad and display module (see

Fig. 9) to perform the following:

HSIO ENTRY

KEYPAD

DISPLAY

ACTION BEING

TAKEN

LOG ON

Enter login function

LOGGEDON Logging in

FACT CFG

Enter factory configuration
function

TYPE X

None at this time

AWTP 0

None at this time

SIZE X

None at this time

ULOP X

None at this time

HPSP 113

None at this time

HEAT X

None at this time

HTSG 2

None at this time

TRNS NO

None at this time

TRNS YES

Configure unit

USER CFG

Enter user configuration
function

HUSN X

None at this time

SUSN NO

None at this time

SUSN YES

Configure unit

FACT CFG

Enter factory configuration
function

SPB CALB

None at this time

SPA CALB

None at this time

DPB CALB

None at this time

DPA CALB

None at this time

DTRS NO

None at this time

DTRS YES

Reset processor

LEGEND

AWTP — Air/Water Type

HTSG — Number of Heat

DP

— Discharge Pressure

Stages

Sensor

SIZE

— Unit Size

DTRS — Data Reset

SP

— Suction Pressure

HEAT

— Heat Type

Sensor

HPSP — Head Pressure

SUSN — Suction Sensors

Set Point

TRNS — Transducers

HUSN — Humidity Sensors

ULOP — Number of Unloaders

After approximately 20 seconds, the HSIO keypad and dis-

play module will resume its normal rotating display indi-
cating that the reconfiguration is complete. After the HSIO
resumes its normal rotating display, perform the following:

HSIO ENTRY

KEYPAD

DISPLAY

ACTION BEING

TAKEN

LOG ON

Enter login function

LOGGEDON Logging in

FACT CFG

Enter factory configuration
function

SPB CALB

SPB CALB

Calibrate SPB transducer

SPA CALB

SPA CALB

Calibrate SPA transducer

DPB CALB

DPB CALB

Calibrate DPB transducer

DPA CALB

DPA CALB

Calibrate DPA transducer

DP — Discharge Pressure
SP — Suction Pressure

At this point, the unit configuration and transducer cali-

bration is complete. To ensure that the calibration was per-
formed properly and that the suction thermistors are reading
correctly, proceed to the following system temperature check:

HSIO ENTRY

KEYPAD

DISPLAY

READING NAME

(EXPECTED DISPLAY)

TEMPS

System temperatures

SCTA X

Saturated condensing temperature,
circuit A (−41 F)

STA X

Suction temperature, circuit A
(−41 F)

SSTA X

Saturated suction temperature, circuit
A (−41 F)

SHA X

Superheat, circuit A (STA-SSTA)

SCTB X

Saturated condensing temperature,
circuit B (−41 F)

STB X

Suction temperature, circuit B
(−41 F)

SSTB X

Saturated suction temperature, circuit
B (−41 F)

SHB X

Superheat, circuit B (STB-SSTB)

Fig. 9 — HSIO Display Module

9

Summary of Contents for 48NP

Page 1: ...oring PACKAGE CONTENTS ITEM QUANTITY Thermistor 2 Transducer 4 Compression Fitting 2 Wire Nuts 2 types 13 PSIO1 Plug Assembly 1 Transducer Plug Harness 4 Connection Box 2 Connection Box Cover 2 Connec...

Page 2: ...reference there will already be a violet wire attached to TB2 terminal 4 and an orange wire attached to TB2 terminal 3 ALL UNITS Locate the PSIO1 plug assembly in the accessory kit see Fig 1 This wil...

Page 3: ...LEGEND PL Plug Assembly PSIO Processor Module TB Terminal Block NOTE The PSIO1 module is located underneath the PSIO2 module Fig 3 Control Box 034 044 3...

Page 4: ...or Evaporator Fan Contactor MMC Head Pressure Control Device OAT Outdoor Air Thermostat OFC Outdoor Condenser Fan Contactor PSIO Processor Module RAT Return Air Thermistor SAT Supply Air Thermistor SC...

Page 5: ...ermistors probe ends un derneath the baffle in the condenser section over to the compressors with the marked thermistor going to com pressor no 1 See Fig 6 and 7 034 044 UNITS Connect the thermistors...

Page 6: ...Thermistor Probe End Routing Fig 6 Control Box Location and Thermistor Routing 024 030 Thermistor Probe End Routing Fig 7 Thermistor Probe End Routing 024 030 Units 6...

Page 7: ...section with the marked cable and ther mistor going to compressor no 1 Compressor Section Wiring This section will de tail the accessory kit wiring in the compressor section When instructed to plug ea...

Page 8: ...ng varnish cloth 6 Locate the 4 transducer plug harness assemblies in the accessory package 7 Plug one of these into the discharge and suction trans ducers for each compressor Mark the white wire in t...

Page 9: ...uction Pressure HEAT Heat Type Sensor HPSP Head Pressure SUSN Suction Sensors Set Point TRNS Transducers HUSN Humidity Sensors ULOP Number of Unloaders After approximately 20 seconds the HSIO keypad a...

Page 10: ...itting threaded into the discharge valve body 3 Unplug the harness from the proper transducer 4 Thread the transducer onto the flare fitting and tighten See Fig 13 16 5 Reconnect the transducer harnes...

Page 11: ...and Discharge Valve Stem Cap Locations 044 Units Compressors 1 and 2 054 Units Compressor 2 DANGER DISCHARGE VALVE STEM CAP LOW PRESSURE SWITCH Fig 12 Low Pressure Switch and Discharge Valve Stem Cap...

Page 12: ...SSURE SWITCH WIRE TIE SUCTION GAS THERMISTOR INSTALLED SUCTION LINE Fig 13 Transducers and Thermistor Installed 024 030 Units SUCTION PRESSURE TRANSDUCER DISCHARGE PRESSURE TRANSDUCER COMPRESSION FITT...

Page 13: ...15 Transducers and Thermistor Installed 044 Units Compressors 1 and 2 054 Units Compressor 2 DANGER DISCHARGE PRESSURE TRANSDUCER COMPRESSION FITTING SUCTION GAS THERMISTOR SUCTION PRESSURE TRANSDUCER...

Page 14: ...and tighten 3 4 to 1 full turn with a wrench to ensure a tight seal DO NOT OVERTIGHTEN 7 Turn the valve stem 1 to 11 2 full turns clockwise Check compression fitting seal for leaks and tighten nut if...

Page 15: ...supplied to transducer 5 Transducer failure 0 0 psig Transducer is not sensing any pressure 1 Service valve is not opened 2 Valve core is not being depressed 205 psig Open circuit at PSIO1 PSIO1 J7 p...

Page 16: ...cturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 1 Tab 1a 1b PC 111 Catalog No 564 923 Printed in U S A...

Reviews: