CL-2
INPUT CONFIGURATION (cont)
Input 5 Function
1 = No Function
2 = Fire Shutdown
3 = Fan Status
4 = Filter Status
5 = Remote Occupancy
2
6 = Door Contact
2
Fire Shutdown
Input 5 Switch Configuration
1 = NO (Normally Open)
2 = NC (Normally Closed)
NO
Input 8 Function
3
1 = No Function
2 = Enthalpy Switch
3 = Fan Status
4 = Filter Status
5 = Remote Occupancy
2
6 = Door Contact
2
No Function
Input 8 Switch Configuration
3
1 = NO (Normally Open)
2 = NC (Normally Closed)
NO
Input 9 Function
4
1 = No Function
2 = Humidistat
7
3 = Fan Status
4 = Filter Status
5 = Remote Occupancy
2
6 = Door Contact
2
7 = IGC Override
No Function
Input 9 Switch Configuration
3 4
NO (Normally Open)
NC (Normally Closed)
NO
ZS Sensor Binder Alarm
ALARM/Normal
ZS Space Temp
°F
ZS Space Humidity
%rh
ZS Space CO2
ppm
SENSOR CALIBRATION
Space Temp
°F
Space RH
5
%rh
Space AQ
6
ppm
Outdoor AQ
7
ppm
Static Pressure
0.00 - 2.50 "wc
Static Pressure Calibration
-0.2 - 0.20 "wc
0
Supply Air Temperature
-56 - 245°F
Supply Air Temp Calibration
-9.9 - 10∆°F
0∆
Return Air Temperature
-56 - 245°F
Return Air Temp Calibration
-9.9 - 10∆°F
0∆
Outdoor Air Temperature
-56 - 245°F
Outdoor Air Temp Calibration
-9.9 - 10∆°F
0∆
SETPOINT
Supply Air Setpoint
45 - 75°F
53
Static Pressure Setpoint
0.25 - 2.25 "wc
0.5
SA Tempering Setpoint
8
40 - 75°F
48
Optimal Start Type
Temp Compensated
Occ Relative Humidity Setpoint
0%RH to Unoccupied RH Control
Setpoint
60
DCV Max Ctrl Setpoint
0 to 9999 ppm
1100
Power Exhaust Setpoint
20 to 90% Open
50
HIGH STATIC PRESSURE ALARM
SP High Limit Trip Setpoint
0 to 2.50 "wc
1.50
SUPPLY AIR TEMPERATURE ALARM
Low SAT Alarm Limit
15-90°F
38
High SAT Alarm Limit
90-175°F
160
RETURN AIR TEMPERATURE ALARM
Low RAT Alarm Limit
15-90°F
55
High RAT Alarm Limit
90-175°F
120
SPACE HUMIDITY ALARM
Occupied High RH Alarm Limit
0-100%RH
70
Alarm Delay (min/%RH)
0-30 min
5
Unoccupied High RH Alarm Limit
0-100%rh
100
Low RH Alarm Limit
0-100%rh
0
POINT NAME
RANGE
DEFAULT
ENTRY
Summary of Contents for 48LCB07
Page 4: ...4 Fig 2 VAV RTU Open Control Module ...
Page 8: ...8 Fig 5 VAV RTU Open Control Wiring Diagram 48LC B07 ...
Page 9: ...9 Fig 6 VAV RTU Open Control Wiring Diagram 48LC B08 12 ...
Page 10: ...10 Fig 7 VAV RTU Open Control Wiring Diagram 48LC B14 26 ...
Page 11: ...11 Fig 8 VAV RTU Open Control Wiring Diagram 50LC B07 ...
Page 12: ...12 Fig 9 VAV RTU Open Control Wiring Diagram 50LC B08 12 ...
Page 13: ...13 Fig 10 VAV RTU Open Control Wiring Diagram 50LC B14 26 ...
Page 55: ......