39
SERVICE CONFIGURATION (cont)
Property Pages>
Configuration>
Service Configuration
(cont)
3
Indoor CO
2
Sensor Value
@ Max mA
14
0-9999ppm
2000
Properties>
Control Program>
Configuration>
Service Configuration
(cont)
3
Outdoor CO
2
Sensor
Value @ Min mA
15
0-9999ppm
0
3
Outdoor CO
2
Sensor
Value @ Max mA
15
0-9999ppm
2000
3
Static Pressure Sensor
Value @ Min mA
0
3
Static Pressure Sensor
Value @ Max mA
2.5
3
System Space RH
N/A
-999.0
3
System Space AQ
N/A
-999.0
3
System Cool Demand
Level
0-3
0
3
System Heat Demand
Level
0-3
0
3
System Outdoor Air
Temperature
N/A
-999.0
3
System Outdoor AQ
N/A
-999.0
3
System Fire / Smoke
Off/On
Off
3
Network Heat Interlock
Off/On
Off
SERVICE TEST
Property Pages>
Configuration>
Service Configuration
3
Service Test Mode
Disable/Enable
Properties>
Control Program>
Configuration>
Service Configuration>
Service Test
3
Service Test
Disable/Enable
Disable
3
Fan Test
Disable/Enable
Disable
3
Compressor 1 Test
Disable/Enable
Disable
3
Compressor 2 Test
Disable/Enable
Disable
3
Heat 1 Test
Disable/Enable
Disable
3
Heat 2 Test
Disable/Enable
Disable
3
Heat Interlock Relay Test Disable/Enable
Disable
3
Power Exhaust Test
Disable/Enable
Disable
3
Economizer Test
0-100 %Open
0
3
VFD Speed Test
0-100%
0
MAINTENANCE (UNIT)
Property Pages>
Maintenance>
Unit
3
Occupancy Status
Occupied/Unoccupied
Properties>
Control Program>
Maintenance>
Unit
3
Current Static Pressure
Setpoint
"wc
3
Calculated Static
Pressure Reset
"wc
3
HPCO Status
Normal/Shutdown
3
Reset Tripped HPCO
16
Run / Reset
3
Static Pressure Proof
Not Active
Valid SP Proof
Wait SP Proof
SP Proof Timeout
3
Supply Air Setpoint
°F
3
Supply Air Temp Clg.
Setpoint
°F
3
SAT Reset Source
No Reset
SAT Rst by SPT
SAT Rst ovr RH
3
SAT Reset Value
°F
3
RH Reset Override
°F
3
Heating Control Setpoint °F
3
Calculated Max Heat
SAT Limit
°F
3
Reset Calculated Max
Heat Limit
Off/On
Off
3
Pre-Occ Purge
Inactive/Active
Table A — User Interface Menus (cont)
Equipment Touch or
System Touch Menu
Access Level
3 = ADMIN
2 = USER
1 = None
POINT NAME
RANGE
DEFAULT
Field Assistant Menu
APPENDIX A — USER INTERFACE MENUS (CONT)
Summary of Contents for 48LCB07
Page 4: ...4 Fig 2 VAV RTU Open Control Module ...
Page 8: ...8 Fig 5 VAV RTU Open Control Wiring Diagram 48LC B07 ...
Page 9: ...9 Fig 6 VAV RTU Open Control Wiring Diagram 48LC B08 12 ...
Page 10: ...10 Fig 7 VAV RTU Open Control Wiring Diagram 48LC B14 26 ...
Page 11: ...11 Fig 8 VAV RTU Open Control Wiring Diagram 50LC B07 ...
Page 12: ...12 Fig 9 VAV RTU Open Control Wiring Diagram 50LC B08 12 ...
Page 13: ...13 Fig 10 VAV RTU Open Control Wiring Diagram 50LC B14 26 ...
Page 55: ......