background image

2

TO SHUT UNIT OFF

Refer to Fig. 3 while proceeding with the following steps.

Step 1 — 

Set room thermostat to lowest temperature setting

and set SYSTEM switch to OFF.

Step 2 — 

 Close the external manual gas valve.

Step 3 — 

 Turn off the electrical power supply to unit;

install lockout tag.

Step 4 — 

 Remove the compressor access panel.

Step 5 — 

Move the gas valve switch to the OFF position.

Step 6 — 

 Replace compressor access panel.

Step 7 — 

If unit is being shut down because of a malfunc-

tion, call your dealer as soon as possible.

If unit is being shut down because the heating season has

ended, restore electrical power to the unit and set thermostat to
the COOL position to ensure operation of the cooling system
during the cooling season.

Should overheating occur, or the gas supply fail to shut off,

shut off the manual gas valve to the unit before shutting off the
electrical supply.

Do not use this unit if any part has been under water. Imme-

diately call a qualified service technician to inspect the unit and
to replace any part of the control system and gas control that
has been under water.

MAINTAINING YOUR UNIT

All maintenance should be handled by skilled, experienced

personnel. Your Carrier service technician can help you set up
a maintenance schedule.

For your safety, keep the area around the unit clear and free

of combustible materials, gasoline, and other flammable liq-
uids and vapors.

To ensure proper functioning of the unit, flow of combus-

tion and ventilating air must not be obstructed from reaching
the unit. Clearance of at least 3 ft on flue and condenser sides
and 6 in. on all other sides is required.

1. Do not turn off the electrical power to unit without

first turning off the gas supply.

2. Never attempt to manually light the main burners on

unit with a match, lighter, or any other flame. If the
electric sparking device fails to light the main burners,
refer to the following shutdown procedures. Call your
dealer as soon as possible.

Failure to follow these procedures can result in fire, seri-

ous  injury or death.

GAS VALVE

FLUE OPENING

COMPRESSOR ACCESS PANEL

INTAKE LOUVERS

Fig. 1A — Gas Valve Location

(48HJ004-007)

Fig. 1B — Gas Valve Location

(48HJ008-014)

Summary of Contents for 48HJ004

Page 1: ...ll for service Step 11 Set the temperature selector on room thermostat to desired setting WARNING If the information in this manual is not followed exactly a fire or explosion may result causing prope...

Page 2: ...pect the unit and to replace any part of the control system and gas control that has been under water MAINTAINING YOUR UNIT All maintenance should be handled by skilled experienced personnel Your Carr...

Page 3: ...005 006 48HJE004 006 48HJF004 006 48HJD007 014 48HJE007 014 48HJF007 014 48HJD005 006 48HJE004 006 48HJF004 006 48HJG005 006 48HJH004 006 48HJK004 006 48HJL005 006 48HJM004 006 48HJN004 006 STEP 7 STE...

Page 4: ...C HI M R E P L A C E S C R EW L O 3 phase units only Single phase units only STEP 5 48HJD005 006 48HJE004 006 48HJF004 006 48HJD007 014 48HJE007 014 48HJF007 014 48HJD005 006 48HJE004 006 48HJF004 00...

Page 5: ...gent Do not use throwaway filters in place of cleanable filters Table 1 Indoor Air Filter Data for 48HJ NOTE Replacement filters should be UL Underwriters Laborato ries certified or equivalent 1 TURN...

Page 6: ...your qualified local dealer for service Combustion Area and Vent System The com bustion area and vent system should be visually inspected be fore each heating season The normal accumulation of dirt so...

Page 7: ...Inspection of all supply and return air ducts for leaks obstructions and insulation integrity Any problems found should be resolved at the time of inspection 8 Inspection of the unit base for cracks g...

Page 8: ...llel with the pipe indicating that the valve is open Or is the lever at the right angle indicating that the valve is closed If closed has the gas been shut off for safety reasons Otherwise you may ope...

Reviews: