background image

7

REGULAR DEALER MAINTENANCE

In addition to the type of routine maintenance you might be

willing to perform, your unit should be inspected regularly by a
properly trained and qualified Carrier service technician. An
inspection (preferably each heating/cooling season, but at least
every year) should include the following:

1. Inspection of all flue product passages — including the

burners, heat exchanger, and flue collector box.

2. Inspection of all combustion- and ventilation-air passages

and openings.

3. Close inspection of all gas pipes leading to and inside

your unit.

4. Inspection and if required, cleaning of the condenser and

evaporator coils.

5. Inspection, and if required, cleaning of the condensate

drain pan.

6. Inspection and cleaning of blower wheel housing and

motor.

7. Inspection of all supply- and return-air ducts for leaks,

obstructions, and insulation integrity. Any problems
found should be resolved at the time of inspection.

8. Inspection of the unit base for cracks, gaps, etc., which

may cause a hazardous condition.

9. Inspection of the unit casing for signs of deterioration.

10. Inspection of all electrical wiring and components to

ensure proper connection.

11. Inspection for leaks in the refrigerant circuit. Pressure-

check to determine appropriate refrigerant charge

12. Inspection of fan wheels and housings, belt tension, and

fan motor shaft bearings.

13. Operational check of the unit to determine working con-

ditions. Repair or adjustment should be made at the time
of inspection.
Your servicing dealer may offer an economical service
contract that covers seasonal inspections. Ask for further
details.

Complete service instructions can be found in the unit

Installation, Start-Up and Service Instructions.

Fig. 5 — Typical Heat Section Detail

Summary of Contents for 48HJ004

Page 1: ...ll for service Step 11 Set the temperature selector on room thermostat to desired setting WARNING If the information in this manual is not followed exactly a fire or explosion may result causing prope...

Page 2: ...pect the unit and to replace any part of the control system and gas control that has been under water MAINTAINING YOUR UNIT All maintenance should be handled by skilled experienced personnel Your Carr...

Page 3: ...005 006 48HJE004 006 48HJF004 006 48HJD007 014 48HJE007 014 48HJF007 014 48HJD005 006 48HJE004 006 48HJF004 006 48HJG005 006 48HJH004 006 48HJK004 006 48HJL005 006 48HJM004 006 48HJN004 006 STEP 7 STE...

Page 4: ...C HI M R E P L A C E S C R EW L O 3 phase units only Single phase units only STEP 5 48HJD005 006 48HJE004 006 48HJF004 006 48HJD007 014 48HJE007 014 48HJF007 014 48HJD005 006 48HJE004 006 48HJF004 00...

Page 5: ...gent Do not use throwaway filters in place of cleanable filters Table 1 Indoor Air Filter Data for 48HJ NOTE Replacement filters should be UL Underwriters Laborato ries certified or equivalent 1 TURN...

Page 6: ...your qualified local dealer for service Combustion Area and Vent System The com bustion area and vent system should be visually inspected be fore each heating season The normal accumulation of dirt so...

Page 7: ...Inspection of all supply and return air ducts for leaks obstructions and insulation integrity Any problems found should be resolved at the time of inspection 8 Inspection of the unit base for cracks g...

Page 8: ...llel with the pipe indicating that the valve is open Or is the lever at the right angle indicating that the valve is closed If closed has the gas been shut off for safety reasons Otherwise you may ope...

Reviews: