ECONOMI$ER IV CONTROL MODES
Determine the EconoMi$er IV control mode before set up of
the control. Some modes of operation may require different
sensors. The EconoMi$er IV is supplied from the factory with
a supply-air temperature sensor and an outdoor-air temperature
sensor. This allows for operation of the EconoMi$er IV with
outdoor air dry bulb changeover control. Additional accesso-
ries can be added to allow for different types of changeover
control and operation of the EconoMi$er IV and unit.
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory configured
for outdoor dry bulb changeover control. For this control
mode, the outdoor temperature is compared to a selectable set
point on the OAT sensor. If the outdoor air temperature is
above the set point, the EconoMi$er IV will adjust the outdoor
air dampers to minimum position. If the outdoor air tempera-
ture is below the set point, the position of the outdoor air
dampers will be controlled to provide free cooling using out-
door air. When in this mode, the Free Cool LED next to the
outdoor enthalpy set point (ABCD) potentiometer will be on.
The changeover temperature set point is controlled by the dip
switches on the sensor. See Fig. 69 for the switch positions cor-
responding to the temperature changeover values. The ABCD
potentiometer on the controller should be turned fully clock-
wise (CW) to the “D” position. See Fig. 70 for damper leakage.
Fig. 69 — Outdoor Air Temperature
Changeover Set Points
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor
(P/N: HH57AC078) is required. Replace the standard outdoor
dry bulb temperature sensor with the accessory enthalpy sensor
in the same mounting location. See Fig. 71. When the outdoor
air enthalpy rises above the outdoor enthalpy changeover set
point, the outdoor-air damper moves to its minimum position.
The outdoor enthalpy changeover set point is set with the out-
door enthalpy set point potentiometer on the EconoMi$er
®
IV
controller. The set points are A, B, C, and D. See Fig. 72 and
73. The factory-installed 620-ohm jumper must be in place
across terminals S
R
and SR+ on the EconoMi$er IV controller.
Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV controller
uses two enthalpy sensors (HH57AC078 and CRENT-
DIF004A00), one in the outside air and one in the return air
duct. The EconoMi$er IV controller compares the outdoor air
enthalpy to the return air enthalpy to determine EconoMi$er IV
use. The controller selects the lower enthalpy air (return or out-
door) for cooling. For example, when the outdoor air has a
lower enthalpy than the return air, the EconoMi$er IV opens to
bring in outdoor air for free cooling.
Replace the standard outside air dry bulb temperature sensor
with the accessory enthalpy sensor in the same mounting loca-
tion. See Fig. 62 on page 38. Mount the return air enthalpy sen-
sor in the return air duct. See Fig. 71. Wiring is provided in the
EconoMi$er IV wiring harness. See Fig. 66 on page 40. The
outdoor enthalpy changeover set point is set with the outdoor
enthalpy set point potentiometer on the EconoMi$er IV con-
troller. When using this mode of changeover control, turn the
enthalpy set point potentiometer fully clockwise to the D
Table 15 — Supply Air Sensor
Temperature/Resistance Values
TEMPERATURE (F)
RESISTANCE (ohms)
-58
220,250
-40
100,000
-22
53,010
-4
29,091
14
16,500
32
9,795
50
5,970
68
3,747
77
3,000
86
2,416
104
1,597
122
1,080
140
746
158
525
176
376
185
321
194
274
212
203
230
153
248
116
257
102
266
89
284
70
302
55
1 2 3
ON
OFF
1 2 3
ON
OFF
1 2 3
ON
OFF
1 2 3
ON
OFF
1 2 3
ON
OFF
1 2 3
ON
OFF
1 2 3
ON
OFF
1 2 3
ON
OFF
48°F
53°F
55°F
58°F
63°F
68°F
73°F
78°F
DIP SWITCH
POSITION
CHANGEOVER
TEMPERATURE
Summary of Contents for 48GC04
Page 18: ...18 Fig 31 Condenser Fan Assembly Screw Pattern Sequence 1 2 3 4 5 NO SCREW Blank Tab...
Page 33: ...33 Fig 57 Integrated Gas Control IGC Board RED LED STATUS...
Page 96: ...96 APPENDIX D WIRING DIAGRAMS Fig E 48GC 04 06 208 230 1 60 Unit with RTU Open Controller...
Page 97: ...97 APPENDIX D WIRING DIAGRAMS Fig F 48GC 04 06 208 230 3 60 Unit with RTU Open Controller...
Page 98: ...98 APPENDIX D WIRING DIAGRAMS Fig G 48GC 04 06 460 575 3 60 Unit with RTU Open Controller...
Page 99: ...99 APPENDIX D WIRING DIAGRAMS Fig H 48GC 04 06 Power Wiring Diagram 208 230 1 60...
Page 100: ...100 APPENDIX D WIRING DIAGRAMS Fig I 48GC 04 06 Power Wiring Diagram 208 230 3 60...
Page 101: ...101 APPENDIX D WIRING DIAGRAMS Fig J 48GC 04 06 Power Wiring Diagram 460 575 3 60...
Page 102: ...102 APPENDIX D WIRING DIAGRAMS Fig K 48GC 04 06 SystemVu Control Wiring Diagram All Voltages...
Page 103: ...103 APPENDIX D WIRING DIAGRAMS Fig L 48GC 04 06 SystemVu Power Wiring Diagram 208 230 1 60...
Page 104: ...104 APPENDIX D WIRING DIAGRAMS Fig M 48GC 04 06 SystemVu Power Wiring Diagram 208 230 3 60...
Page 105: ...105 APPENDIX D WIRING DIAGRAMS Fig N 48GC 04 06 SystemVu Power Wiring Diagram 460 575 3 60...