Packaged rooftop units 

with integrated gas burner

12

Main door switch

By using a mechanical device, 

it impedes access to the electric 

panel when the unit is with 

voltage.

High pressure pressostat

Connected to the compressor discharge, it will 

stop its operation when the pressure at that point 

reaches the setpoint. It disconnects at 42 bar and 

it is automatically reactivated.

Low pressure pressostat

When connected to the compressor suction, it 

will stop its operation when the pressure at that 

point goes down below the tare value (caused by 

obstructions in the circuit, excessive dirt in the fi lters, fan stop or ice 

formation in the evaporator).

It disconnects at 2 bar and it is automatically reactivated.

Safeties at the compressor

The scroll type compressor that these units as standard have the 

following safeties:

-  Non-return valve built into the compressor.

-  Klixon in the compressor, which stops the operation of the motor 

when there is excessive heating.

Condensation and evaporation pressure control 

This safety element, integrated in the control, enables managing the 

outdoor fans when the units are working in COOLING mode with low 

outdoor temperatures (condensation control) or in HEATING mode with 

high outdoor temperatures (evaporation control).

This aids the unit's operation in all the stations.

Smoke detector (optional)

This smoke detection station uses a LED to indicate the installation 

status and if the probe detects the presence of smoke in the installation 

it stops the operation of the unit. The station is installed in the factory 

in the auxiliary electric panel.

Smoke detecting station

Smoke detecting probe

Clogged fi lter detector (optional)

Differential pressostat for indication of maintenance to fi lters. Automatic 

reactivation. It is installed in the auxiliary electric panel.

Anti-fi re safety device

This safety device, integrated in the control, shuts down the unit if the 

probe located in the return detects an air inlet temperature above 

60ºC.  The unit will not return to operation until this temperature drops 

under 40ºC.

Control of air fl ow

Differential pressostat that measures the fl ow variation in the air outlet. 

This allows the detection of fan belt breakages, since the fan relay only 

detects operating faults that have arisen in the motor. This pressostat 

is installed in the factory in the auxiliary electric panel.

Protection of the electric panel (optional)

Anti-freeze protection for low outdoor temperatures with electric heater. 

This safety device is compulsory when the outdoor conditions guarantee 

an air inlet temperature to the burner which is less than -15ºC.

Air quality probe (optional)

This probe is for installation in the environment or in duct to enable 

measuring CO

2

 and/or volatile compounds.

This probe is to be connected by the client. The clamps on the terminal 

board on the main panel used for the connection are indicated on the 

wiring diagram provided with the unit.

This probe is supplied inside the main electric panel.

Automatic switch in the control circuit

Magnetothermal switch that protects the operation circuit against 

continuous surges as well as against high currents of short duration 

(short circuits).

Defrost control

This safety element is intended to eliminate ice which could accumulate 

in the outdoor coil when the unit is working in the heating CYCLE. 

Defrosting is carried out by the control depending on the value 

measured by the sensors on the outdoor coils and the time set between 

defrosting operations.

Magnetothermals for line protection

They are located at the beginning of the power lines of the compressor 

and motorised fans to protect them. 

Safety devices in the 48EN/EH unit

Summary of Contents for 48EH

Page 1: ...ERATION AND MAINTENANCE INSTRUCTIONS 48EN EH Nominal cooling capacity 58 9 135 5 kW Nominal heating capacity 62 2 143 4 kW 50 Hz Packaged rooftop cooling only heat pumps with integrated gas burner Ori...

Page 2: ...ommissioning and maintenance operations 8 7 Gas Burner 9 Operating principle 9 Control of the gas burner 10 8 Safety elements 11 Safety devices in the gas burner 11 Safety devices in the 48EN EH unit...

Page 3: ...lation and reliable operation Space 48EN Series Autonomous air air cooling units with a compact horizontal rooftop design with a built in gas burner Space 48EH Series Autonomous reversible air air hea...

Page 4: ...5 900 18 000 18 200 20 400 24 000 Available static pressure mm w c 12 12 12 12 12 12 12 12 15 15 Type Centrifugal Number no turbines 2 2 Motor output kW 2 x 1 5 2 x 2 2 2 x 3 2 x 1 1 2 x 2 2 2 x 2 2 2...

Page 5: ...ents during installation commissioning or maintenance it is required to take into consideration the units specifications refrigerated circuits under pressure refrigerant presence voltage presence and...

Page 6: ...said vapours Although the R 410A is not flammable when in contact with a flame or hot spot it can decompose thus producing fluorhydric acid HF and fluophosgene COF2 which are highly toxic and corrosiv...

Page 7: ...re can withstand the weight of the unit Since the unit is designed to work outdoors some specific installation norms must be followed The unit will be located on the roof of the premises If it is fore...

Page 8: ...02 450 404 66 414 368 1805 MA MC0 1845 2095 137 498 438 63 424 364 1925 322 MO 1845 2095 72 432 397 74 433 398 1806 MS 1845 2095 107 471 423 69 434 385 1888 MA MC0 1845 2095 143 520 457 66 443 380 200...

Page 9: ...lectrode nozzle Control device On off signal Burner fan EVP pilot light flame EV1 1st electromagnetic valve gas EV2 2nd electromagnetic valve gas A B C D E F Operation of the air gas premix The air an...

Page 10: ...imit the power supplied by the burner This avoids the stratification of the hot air masses and that the outlet air temperature exceeds a maximum safety level 55 C by default which will cause the burne...

Page 11: ...or the modulation are outside the range Failure in the fan motor F4 F5 F6 Unused F7 No serial communication The remote control is disconnected F8 The flame control device does not work The flame contr...

Page 12: ...utomatic reactivation It is installed in the auxiliary electric panel Anti fire safety device This safety device integrated in the control shuts down the unit if the probe located in the return detect...

Page 13: ...ces etc refer to The information supplied in this document table of technical characteristics Data plate The wiring diagram and the legend supplied with the unit The CARRIERrtc electronic control broc...

Page 14: ...burns Note The gas burner chimney is not supplied with the unit Its design and installation is the responsibility of the engineer and must comply with all the directives and regulations in force in t...

Page 15: ...ibration transmission Air ducts connections Checks in the axial fans Before commissioning check the blade rotation direction and that the axis turns without strokes nor vibrations Once running check t...

Page 16: ...Condensates outlet Before commissioning check the blade rotation direction and that the axis turns without strokes nor vibrations Once running check the operation conditions pressures flows and consum...

Page 17: ...unit and all the components used This will be very helpful for maintenance and repairs to the installation Check that the electrical power supply matches the unit voltage and that its value lies with...

Page 18: ...means this has to be taken into account in the selection of higher pressure fans optional or in the substitution of the standard pulley set with a new set that generates a higher turn speed to the pa...

Page 19: ...ually Depending on the installation conditions the filter aspect must be examined to define the cleaning periodicity Gravimetric filters Cleaning the filtering mesh can be done with a household vacuum...

Page 20: ...f the charge Note Both the oil type as well as the volume needed for each model are stated in the Technical characteristic tables in chapter 3 Caution Before starting any maintenance operations ensure...

Page 21: ...n Burner Safety Devices Open the valve unblock the control and check that the burner is operating correctly 8 The safety thermostat and the air differential pressostat With the burner in operation ope...

Page 22: ...rature of air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise humming a No power b The contacts of a control element are o...

Page 23: ......

Page 24: ...Order No 10051 03 2015 Supersedes order No New Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...