42VMC

GB - 9

E N G L I S H

Electrical connections

Jumper positioning:
Units are equipped with a jumper inside the electric control box, to
make them suitable for the two installation typologies:

Wall vertical installation: jumper inserted.

Ceiling horizontal installation: jumper removed.

To reset incorrect jumper positioning, proceed as follows:

• Disconnect the power supply.

• Reposition the jumper correctly.

• Connect the power supply.

IMPORTANT:

• Make refrigerant connections before electrical

connections.
When disconnecting, disconnect electrical connections before
refrigerant connections.

• Make ground connection prior to any other electrical

connections.

The mains supply must be connected as follows:
Models 42VMC 009, 012, 014: to the indoor unit.
Models 42VMC 018, 024: to the outdoor unit.

• Make electrical connections between units prior to proceeding

to mains supply unit connection.

• Before proceeding with the unit connection to the mains supply

locate live L and neutral N, then make connections as shown
in the wiring diagram.

• Ensure that mains supply connection is made through a switch

that disconnects all poles, with contact gap of a least 3 mm.

• The indoor - outdoor unit connecting wires must be A07 RN-F type

(or higher), with synthetic rubber insulation with Neoprene coating,
according to EN 60335-2-40 and HD277.S1 codes.

• The mains supply connecting cable for 42VMC 009, 012, 014

units, must be H07 RN-F type (or higher), with synthetic rubber
insulation with Neoprene coating, according to EN 60335-2-40
and HD277.S1 codes.

• Ground connection between indoor and outdoor unit is made

via the refrigerant pipes.

• With the cable clamp supplied, secure the connecting cable

between the two units.

• Fasten the electric connecting wires with refrigerant tubes together.

Allow an additional length to the electric wires for easy connection
to the unit connectors.

Notes:

• For sizing of power supply wires and delay type fuses, refer

to the outdoor unit installation instructions.

• All field electrical connections are the responsibility of the

installer.

IMPORTANT:
The units are provided with electronic control.
A time-delay device provides a 3 minute starting delay of the
compressor every time the unit is stopped or when it is initially
switched on.

Control and safety devices

The following control and safety devices are built into the indoor
units (see wiring diagrams):

• Room air thermostat adjustable from 18°C to 32°C.

• Motor with overheat/overcurrent protection.

Summary of Contents for 42VMC Console night & day

Page 1: ...42VMC Console T h e S t andards Institutiono f I s r a e l Q u ality Assured Fi r m SI ISO 9001 INSTALLATION MANUAL...

Page 2: ...ge Dimensions and weight 2 Nominal data 2 Minimum clearances 2 Connections 3 Material supplied 3 Operating limits 3 General information 4 Warnings avoid 5 Installation 6 7 Refrigerant connections 8 El...

Page 3: ...m 540 540 600 600 600 kg kg 15 16 18 18 20 Table I Nominal data Unit is not suitable for operation in laundry premises For sizing of power supply wires and delay type fuses refer to the outdoor unit i...

Page 4: ...g limits Cooling Heating Refer to outdoor unit installation manual Mains power supply Nominal single phase voltage 230V 50Hz Operating voltage limits min 198V max 264V Photocatalytic filter Acrylic fi...

Page 5: ...its which have different control systems may cause irreversible damage and void the warranty protection The manufacturer declines any liability for system malfunction resulting from unapproved couplin...

Page 6: ...lose to heating sources which may damage the unit connecting condensate piping to sewage system drain without appropriate trap Trap height must be calculated according to the unit discharge head in or...

Page 7: ...grille To remove suction grille remove the central lock using a pliers then with a screwdriver remove the two side screws fixing the fasteners Locate the mounting template supplied with the unit Insta...

Page 8: ...ections see illustra tion For exit to the rear the wall hole must be made in the position shown in the illustration Drill a 70 or 80 mm diameter hole The hole must have a 5 10 mm downward slope toward...

Page 9: ...s Liquid Model Suction Discharge mm inches mm inches 009 9 52 3 8 6 35 1 4 012 12 70 1 2 6 35 1 4 014 12 70 1 2 6 35 1 4 018 12 70 1 2 6 35 1 4 024 12 70 1 2 6 35 1 4 For refrigerant tubes use seamles...

Page 10: ...gap of a least 3 mm The indoor outdoor unit connecting wires must be A07 RN F type or higher with synthetic rubber insulation with Neoprene coating according to EN 60335 2 40 and HD277 S1 codes The m...

Page 11: ...ng contact Mains supply connecting cable field wiring Connecting cable indoor outdoor units field wiring Indoor unit Outdoor unit Main switch Time delay fuse or circuit breaker see outdoor unit instal...

Page 12: ...ction indoor outdoor unit R Live connection indoor outdoor unit C Neutral connection indoor outdoor unit Y Compressor interlocking contact O Reversing valve control W2 Outdoor fan signal S Defrost end...

Page 13: ...ng temperature range F min and max CL 12 12 12 hour clock AM PM Time format AM morning PM afternoon 24 24 24 hour clock Default is 12 12 Table IV Item Shown on Explanation Description display A remote...

Page 14: ...ol and hold them pressed for more than 5 seconds The display will be cleared the temperature segments will display the first configuration item CH remote address and the time segments will display the...

Page 15: ...pplied separately and controlled by a bipolar ON OFF switch with safety fuses field installed To adjust the fan motor air flow to the required values it is advisable to install a speed controller Fres...

Page 16: ...nzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice Order No 14489 74 April 2002 Supersedes Order No 14489 74 Januar...

Reviews: