Carrier 42VMC Console night & day Installation Manual Download Page 15

42VMC

GB - 14

Air delivery and fresh air renewal

Ceiling installation, cooling

Ceiling installation, heating

Fresh air renewal

Units are prearranged for introduction of renewal air through a
prepunched hole located on back side.
Back knockout allows connection of fresh air inlet duct.

Model 009 - 012

 Model 014 - 018 - 024

• Use locally purchased material, suitable for operating

temperatures of 60 °C (continuous).
Conduits can be of flexible polyester (with spiral core) or
corrugated aluminium, externally covered with anti-condensate
material (fibre glass from 12 to 25 mm thickness).

• To complete the installation, all non-insulated ducts must be

covered with anti-condensate insulation (ex. expanded neoprene,
6 mm thickness).

Not observing of these instructions may cause condensate
dripping; the manufacturer will not be held responsible for any
damage caused.

• The supplementary fan motor for outside air intake has to be

supplied separately and controlled by a bipolar ON-OFF switch
with safety fuses (field-installed).

  To adjust the fan motor air flow to the required values it is

advisable to install a speed controller.

  Fresh air flow must be less than 10% of the total air flow, to

avoid operating problems.

  For fresh air ventilation rates higher than 10%, a primary air

treatment system with separate deflectors is recommended.

• Install an air inlet grille with filter inspection port to prevent

dust and dirt from entering and fouling the indoor unit heat
exchanger.
Filter installation also makes the installation of a duct closing
damper during shutdown periods unnecessary.

Air delivery direction

Wall installation, heating

Wall installation, cooling

IMPORTANT:
Air is supplied into the room through the grilles located on top
of the cabinet; air from the room is drawn into the unit through
the grilles and filter at the bottom of the unit.

“No draught”
(guide vane fully open)
(position recommended for ceiling installation in
cooling mode, to avoid draughts)

Make absolutely sure that the above parts are not obstructed
(even partially).

Summary of Contents for 42VMC Console night & day

Page 1: ...42VMC Console T h e S t andards Institutiono f I s r a e l Q u ality Assured Fi r m SI ISO 9001 INSTALLATION MANUAL...

Page 2: ...ge Dimensions and weight 2 Nominal data 2 Minimum clearances 2 Connections 3 Material supplied 3 Operating limits 3 General information 4 Warnings avoid 5 Installation 6 7 Refrigerant connections 8 El...

Page 3: ...m 540 540 600 600 600 kg kg 15 16 18 18 20 Table I Nominal data Unit is not suitable for operation in laundry premises For sizing of power supply wires and delay type fuses refer to the outdoor unit i...

Page 4: ...g limits Cooling Heating Refer to outdoor unit installation manual Mains power supply Nominal single phase voltage 230V 50Hz Operating voltage limits min 198V max 264V Photocatalytic filter Acrylic fi...

Page 5: ...its which have different control systems may cause irreversible damage and void the warranty protection The manufacturer declines any liability for system malfunction resulting from unapproved couplin...

Page 6: ...lose to heating sources which may damage the unit connecting condensate piping to sewage system drain without appropriate trap Trap height must be calculated according to the unit discharge head in or...

Page 7: ...grille To remove suction grille remove the central lock using a pliers then with a screwdriver remove the two side screws fixing the fasteners Locate the mounting template supplied with the unit Insta...

Page 8: ...ections see illustra tion For exit to the rear the wall hole must be made in the position shown in the illustration Drill a 70 or 80 mm diameter hole The hole must have a 5 10 mm downward slope toward...

Page 9: ...s Liquid Model Suction Discharge mm inches mm inches 009 9 52 3 8 6 35 1 4 012 12 70 1 2 6 35 1 4 014 12 70 1 2 6 35 1 4 018 12 70 1 2 6 35 1 4 024 12 70 1 2 6 35 1 4 For refrigerant tubes use seamles...

Page 10: ...gap of a least 3 mm The indoor outdoor unit connecting wires must be A07 RN F type or higher with synthetic rubber insulation with Neoprene coating according to EN 60335 2 40 and HD277 S1 codes The m...

Page 11: ...ng contact Mains supply connecting cable field wiring Connecting cable indoor outdoor units field wiring Indoor unit Outdoor unit Main switch Time delay fuse or circuit breaker see outdoor unit instal...

Page 12: ...ction indoor outdoor unit R Live connection indoor outdoor unit C Neutral connection indoor outdoor unit Y Compressor interlocking contact O Reversing valve control W2 Outdoor fan signal S Defrost end...

Page 13: ...ng temperature range F min and max CL 12 12 12 hour clock AM PM Time format AM morning PM afternoon 24 24 24 hour clock Default is 12 12 Table IV Item Shown on Explanation Description display A remote...

Page 14: ...ol and hold them pressed for more than 5 seconds The display will be cleared the temperature segments will display the first configuration item CH remote address and the time segments will display the...

Page 15: ...pplied separately and controlled by a bipolar ON OFF switch with safety fuses field installed To adjust the fan motor air flow to the required values it is advisable to install a speed controller Fres...

Page 16: ...nzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice Order No 14489 74 April 2002 Supersedes Order No 14489 74 Januar...

Reviews: