Electronic function
7.1
Performance Index
No.
Item
Index
1
Applicable Voltage Range
185-253V, 342-418V
2
A/C Frequency
50Hz
3
Working environment temperature
-7°C- +45°C
7.2
Main data Introduction
Ts : Set temperature,
T1 : Room temperature
T2: Evaporator pipe temperature
7.3
Operation Modes and Functions
7.3.1
Manual Operation
7.3.2
Heating Mode
7.3.2.1
Four-way valve opens at once, while defrosting process closes.
7.3.2.2
Condition for the compressor action: (Ts=set temperature, T1=room
temperature)
7.3.2.3
Indoor Fan Action
Anytime remote switchover for fan speed among high/low/auto, anti-cold air function
takes priority.
Auto fan in heating mode
Anti-cold air:
Switchover between fan speed and fine tune can be set according to temperature of
evaporator pipe (T2).
Condition
Compressor and outdoor fan
Room temperature up
T1-Ts=0°C
Off
T1-Ts>-1°C
On
Room temperature down
T1-Ts<-1°C
On
T1-Ts=0°C
Off
Condition
Fan speed
Room temperature up
T1-Ts>-1°C
Low
T1-Ts<-1°C
Hi.
Room temperature down
T1-Ts<-2°C
Hi.
-2°C <T1-Ts <-1°C
Low
Condition
Fan speed
Room temperature up
T2<25°C
Off
25°C <T2<32°C
Low
Summary of Contents for 42/38KCJ024713
Page 7: ...External view and display 5 3 2 Display panel ...
Page 8: ...Refrigerant cycle diagram 6 4 Refrigerant cycle diagram 4 1 Cooling only 4 2 Heat pump model ...
Page 10: ...PCB drawing Wiring diagram 8 Outdoor unit 5 3 42 38KCJ036713 Indoor unit ...
Page 11: ...PCB drawing Wiring diagram 9 Outdoor unit 5 1 42 38QCJ036713 Indoor unit ...
Page 12: ...PCB drawing Wiring diagram 10 Outdoor unit 5 1 42 38KCJ048713 Indoor unit ...
Page 13: ...PCB drawing Wiring diagram 11 Outdoor unit 5 1 42 38QCJ048713 Indoor unit ...