Exploded view & spare-part
23
At the beginning of energizing or after the stop of the compressor, 3-minute delay will be
needed to start the compressor.
When switching over between cooling/heating mode, the compressor stops
automatically.
8.1.2
Evaporator protection against high temperature
8.1.2.1
Only available under heating mode.
8.1.2.2
The operation principle is as follows: (T2 = evaporator temperature)
Condition
Outdoor fan
Compressor
T2>56°C
Off
On
T2>62°C
Off
Off
T2<62°C
On
Off
T2<50°C
On
On
Note: During protection, the indoor fan continues operating at a set speed, while the
anti-cold air function of heating and the compressor will be 3 minute delayed to shut
down for protection.
8.1.3
Evaporator Protection against low temperature
8.1.3.1
Only available under cooling and dehumidifying status.
8.1.3.2
Protection principle:
Condition
Outdoor fan
Compressor
T2<2°C
(
last 3 minute
)
Off
Off
T2>8°C
On
On
8.1.3.3
The restart of the compressor shall execute the delay protection.
8.1.4
Condenser high temperature protection
8.1.4.1
Only available to cooling and dehumidifying mode.
8.1.4.2
Action condition
Condition
Outdoor fan
Compressor
Condenser temp.>62°C
Off
Off
Condenser temp.<48°C
On
On
8.1.4.3
Delay protection should be performed when the compressor restarts.
8.1.5
Outdoor protection
When outdoor protection signal is high level, outdoor unit will perform protection: the
whole machine will be shut down while the indoor unit will indicate the corresponding
protection signal.
The A/C will recover if outdoor errors are eliminated after the outdoor protection occurs.
8.2
Self-diagnosis
Codes
Contents
P4
Protection of temperature of indoor evaporator
P5
Protection of temperature of outdoor condenser
Summary of Contents for 42/38KCJ024713
Page 7: ...External view and display 5 3 2 Display panel ...
Page 8: ...Refrigerant cycle diagram 6 4 Refrigerant cycle diagram 4 1 Cooling only 4 2 Heat pump model ...
Page 10: ...PCB drawing Wiring diagram 8 Outdoor unit 5 3 42 38KCJ036713 Indoor unit ...
Page 11: ...PCB drawing Wiring diagram 9 Outdoor unit 5 1 42 38QCJ036713 Indoor unit ...
Page 12: ...PCB drawing Wiring diagram 10 Outdoor unit 5 1 42 38KCJ048713 Indoor unit ...
Page 13: ...PCB drawing Wiring diagram 11 Outdoor unit 5 1 42 38QCJ048713 Indoor unit ...