Table 2 — Error Codes

ERROR 

CODE

DESCRIPTION

POSSIBLE CAUSES

POSSIBLE SOLUTIONS

E1

Indoor unit and outdoor unit 
communication failure

Signal wires are short-circuited or 
disconnected.

Check or reconnect signal wire.

Signal wire order is incorrect.

Correct signal wire order.

Signal wires crossing over high voltage power 
wires.

Separate and distance the signal wire from high 
voltage power wires.

Signal wire close to electromagnetic source.

Distance signal wires from electromagnetic 
source.

Signal wire length exceeds 360 ft.

Reduce the signal wire length.

PC board fault.

Replace PC board.

E2

T1 sensor malfunction

Loose connection at port on PC board.

Tighten the connection at port on PC board.

Sensor is short-circuited.

Using multi-meter, measure resistance of the 
sensor. If the resistance is 

 100 ohms, change 

the sensor.

PC board fault.

Replace PC board.

E3

T2A sensor malfunction

Loose connection at port on PC board.

Tighten the connection at port on PC board.

Sensor is short-circuited.

Using multi-meter, measure resistance of the 
sensor. If the resistance is 

 100 ohms, change 

the sensor.

PC board fault.

Replace PC board.

E4

T2B sensor malfunction

Loose connection at port on PC board.

Tighten the connection at port on PC board.

Sensor is short-circuited.

Using multi-meter, measure resistance of the 
sensor. If the resistance is 

 100 ohms, change 

the sensor.

PC board fault.

Replace PC board.

E5

Outdoor unit fault protection

Outdoor unit fault.

Refer to outdoor unit troubleshooting guide.

E7

Indoor unit EEPROM failure

Chip or PC board fault.

Replace PC board.

EC

Change/clean filter reminder

Run time has elapsed.

Clear the code by pressing and holding the 
SWING button and pressing the QUERY button 
at the same time.

EE

Water level error

Loose connection or disconnected at port on PC 
board.

Tighten the connection or reconnect at port on 
PC board.

Water level float is stuck.

Inspect the float.

Trap slope is too steep.

Adjust the trap slope.

Drain pipe is too long.

Adjust the length of drain pipe.

Drain pump faulty.

Replace the drain pump.

P0

Evaporator temperature
protection

Evaporator coils are covered with dirt and dust

Clean the coils to increase heat transfer rate.

Incorrect sensor wiring

Correct sensor wiring as per wiring diagram.

Sensor is short-circuited

Using multi-meter, measure resistance of the 
sensor. If the resistance is 

 100 ohms, change 

the sensor.

a40-1889

In this example:

1. The indoor unit with the address 08 is being queried.
2. The unit with the address 08 has an error, code E1.
3. In the address grid, the small block at 00+,08 blinks, indicating an

error.

4. In the grid, only the indoor units at addresses 00+,00 and 16+,15 are

lit. This means only that only the indoor units with the addresses of 00
and 31 are powered on.

Fig. 13 — Error Display Screen (Example)

Summary of Contents for 40WA900024

Page 1: ...entral controller accessory is available for use with the single phase VRF variable refrigerant flow indoor units listed in Table 1 Table 1 Central Controller Accessory Usage INSTALLATION Controller I...

Page 2: ...e slots provided on the top of the controller to open the back mounting plate See Fig 2 8 Attach the back mounting plate directly over the opening in the wall using 4 screws and route the control cabl...

Page 3: ...connections See Fig 6 for complete system central controller wiring diagram X X Y Y E E CENTRAL CONTROLLER OUTDOOR UNIT a40 1875 Fig 5 Controller Connections P Q E X Y E 3 4 3 4 3 4 3 4 3 4 5 MATCH R...

Page 4: ...1 6 INDOOR UNIT ADDRESS DISPLAY GRID NOT USED SWING ON NOT USED ERROR PROTECTION CODE CENTRAL CONTROLLER OPERATION STATUS NOT USED OPERATION MODE SETTING COOLING MODE LOCK HEATING MODE LOCK REMOTE CO...

Page 5: ...ontal coordinates are 00 to 15 The sum of the vertical and horizontal coordinates is the address of the indoor unit The unit s location on the grid has no relation to the unit s physical location For...

Page 6: ...e delayed operation start time for the selected indoor units Press the INC button to se lect the start hour from 0 to 24 hours Each button press incre ments the setting by 1 2 hour for the first 10 ho...

Page 7: ...the same time The controller displays 88 the display flashes 5 Use the INC and DEC buttons to set the appropriate func tion as shown below 6 Press OK 7 Use the INC and DEC buttons to select the code...

Page 8: ...tion at port on PC board Tighten the connection at port on PC board Sensor is short circuited Using multi meter measure resistance of the sensor If the resistance is 100 ohms change the sensor PC boar...

Reviews: