2

5.

Connect one end of the shielded 3-core control cable to
the control wiring terminal block on the outdoor unit. See
Fig. 1.

6.

For wall-hung or under-ceiling/floor units, provide a 1-in.
by 1-in. square opening in the surface behind the unit to
route the shielded 3-core control cable, furred in to con-
nect the indoor unit display panel to the controller.
For concealed ducted, high static ducted, cassette, or
vertical units, the shielded 3-core cable can be routed
through the plenum and the wall to connect the indoor
unit display panel and the controller.

7.

Insert a flat-head screwdriver into the slots provided on
the top of the controller to open the back mounting plate.
See Fig. 2.

8.

Attach the back mounting plate directly over the opening
in the wall, using 4 screws, and route the control cable as
shown in Fig. 3.

9.

Connect the control cable and power to the back of the
controller and mount the controller back onto the mount-
ing plate. See Fig. 4.

WHITE

BLUE

BLA

CK

BLA

CK

YELLO

W

GRA

Y

a40-1879

FROM CENTRAL
CONTROLLER

TO INDOOR
UNITS

OUTDOOR UNIT
CONTROL WIRING
TERMINAL BLOCK

Fig. 1 — Control Wiring Terminal Block

BASE

FRONT
COVER

a40-1876

Fig. 2 — Opening Back Mounting Plate

MOUNTING
SCREW

a40-1880

Fig. 3 — Attaching Back Mounting Plate

X Y E F1 F2 E

FORCED ON

EMG. STOP

R

C

TO OUTDOOR UNIT

X,Y, E

NOT USED

FORCED
ON
SWITCH

EMERGENCY
STOP
SWITCH

24 VAC

a40-1904

Fig. 4 — Central Controller Wiring

Summary of Contents for 40WA900024

Page 1: ...entral controller accessory is available for use with the single phase VRF variable refrigerant flow indoor units listed in Table 1 Table 1 Central Controller Accessory Usage INSTALLATION Controller I...

Page 2: ...e slots provided on the top of the controller to open the back mounting plate See Fig 2 8 Attach the back mounting plate directly over the opening in the wall using 4 screws and route the control cabl...

Page 3: ...connections See Fig 6 for complete system central controller wiring diagram X X Y Y E E CENTRAL CONTROLLER OUTDOOR UNIT a40 1875 Fig 5 Controller Connections P Q E X Y E 3 4 3 4 3 4 3 4 3 4 5 MATCH R...

Page 4: ...1 6 INDOOR UNIT ADDRESS DISPLAY GRID NOT USED SWING ON NOT USED ERROR PROTECTION CODE CENTRAL CONTROLLER OPERATION STATUS NOT USED OPERATION MODE SETTING COOLING MODE LOCK HEATING MODE LOCK REMOTE CO...

Page 5: ...ontal coordinates are 00 to 15 The sum of the vertical and horizontal coordinates is the address of the indoor unit The unit s location on the grid has no relation to the unit s physical location For...

Page 6: ...e delayed operation start time for the selected indoor units Press the INC button to se lect the start hour from 0 to 24 hours Each button press incre ments the setting by 1 2 hour for the first 10 ho...

Page 7: ...the same time The controller displays 88 the display flashes 5 Use the INC and DEC buttons to set the appropriate func tion as shown below 6 Press OK 7 Use the INC and DEC buttons to select the code...

Page 8: ...tion at port on PC board Tighten the connection at port on PC board Sensor is short circuited Using multi meter measure resistance of the sensor If the resistance is 100 ohms change the sensor PC boar...

Reviews: